Devatec ELECTROVAP RTH-LC Series User manual

Category
Dehumidifiers
Type
User manual
Photos non contractuelles
RTH tech. Can Eng Rev2.2
25-10-2010
R
3
ElectroVap RTH-LC
Contents
Certificate of compliance 4-5
Product accreditation 6
Safety information 7-8
Unit wall installation
Dimensions 9
Water connection 10
Steam outlet 11
Condensate draining 12
Steam distribution pipes 13
Steam pipe positioning 14-18
Fan distribution unit 19
Electrical installation
Electrical tables 21
Electrical wirings 22-23
Control connection 24
Connecting options 25
Wiring diagrams 26-27
Software assistant
Front panel indentification 28
Starting up 29
User information menu 30-31
Humidifier status menu 32
Changing parameters menu 33-34
Alerts and warnings 35
Maintenance
Steam boiler maintenance 36-37
Valve maintenance 38
Split views and component parts 39 to 44
Follow-up & maintenance sheet 45 to 47
6
Product accreditation
ElectroVap RTH-LC
DIRECTIVE APPLIED
The humidifier complies with :
NF EN 61000-6-3, EN 55022 classe B
NF EN 61000-4-3 10V/m, NF EN 61000-4-6 10V, NF EN 61000-4-4, NF EN 61000-4-5,
NF EN 61000-4-2
Manufacturer’s name & address
devatec
Rue Feu St Eloi
F-76550 Ambrumesnil
France
Representative
TYPE OF EQUIPMENT
ELECTROVAP RTH
MODEL NAME AND SERIES
RTH
YEAR OF MANUFACTURING
2007
We the undersigned, hereby declare that the equipment specified above complies with the above-
mentioned Directive(s) and Standard(s).
Mr FRAMBOT Jean-François Signature:
General Manager
Date: 02.07.2007
7
ElectroVap RTH-LC
Safety information
I
MPORTANT
This manual should be read thoroughly before specifying, designing, installing or operating
a Devatec ElectroVap RTH system. Please retain for reference and should you have any
question, please contact one of our authorized dealers.
WARNINGS & SAFETY SYMBOLS
Warning : This symbol is used to designate a danger of injury or potential
damage to the system.
Caution : High voltages are present inside the humidifier. All works concerned with the
electrical installation must be carried out by skilled and qualified personnel
Caution : Danger of scalding ! The ElectroVap RTH generates steam during operation and
therefore, surfaces and pipe-work become very hot. Ensure that equipment not sustaining
high temperare be kept away.
Take care : the end user should ensure that the equipment be disposed of according to the
prevailing regulations.
DELIVERY & STORAGE
Any loss or damage during delivery should be reported to carrier by registered letter within 3 working days
and be advised to Devatec or the authorized dealer.
It is recommended that the ElectroVap RTH humidifier be kept in its transit packaging for as long as possible
prior to maintenance. If the humidifier is to be put into storage prior to installation, it must be stored under co-
ver and protected from physical damage, dust, frost, rain and humidity. More than 6 months storage is not re-
commended.
ElectroVap RTH-LC
Safety information
IMPORTANT
This section should be read carefully to ensure the safe and correct installation of your humidifier.
GENERAL
This manual contains all details necessary for the planning and installation of the ElectroVap RTH humidifier.
In addition commissioning and maintenance details are included.
The manual is intended for use by engineers and properly trained technical personnel. Maintenance, servic-
ing or repair work must only be carried out by suitable skilled and qualified personnel, the customer must be
responsible for ensuring their suitability.
Any risks or hazards, especially when working from ladders or towers should be identified by a skilled and
Health and Safety representative and effective control measure put in place.
No liability will attach to the Distributor if any damage, injury or accident is attributable to inattentive, inappro-
priate, negligent or incorrect operation of the machinery whether or not caused deliberately. Always isolate
all electrical and water supplied before commencing any maintenance.
Every effort has been made to ensure details contained in this manual are correct, however, in view of the
wide range of conditions experienced in air handling systems, the information provided should only be used
as a guide. Please contact your Agent if any doubt.
CORRECT USE
ElectroVap RTH humidifiers are ONLY intended for use with air handling systems or direct air humidification.
ANY OTHER APPLICATION IS NOT CONSIDERED USE FOR THE INTENDED PURPOSE. THE MANU-
FACTURER CANNOT BE MADE LIABLE FOR ANY DAMAGE RESULTING FROM INCORRECT USE.
WATER
ElectroVap RTH humidifiers are designed to be used with mains, demineralized R/O (minimum 30 μs) or
softened water. On no account attempt to introduce any other fluid or chemical into the system. Water sup-
ply should not exceed 6.0 bar and installation should comply with local regulations.
ELECTRICITY
All work concerned with electrical installation MUST only be performed by skilled and qualified technical per-
sonnel (eg electrician or technicians with appropriate training). The customer MUST be responsible for en-
suring their suitability.
It is the duty of the installer to ensure that suitable sized cables and MCB protection is provided. Please ob-
serve the local regulations concerning the provision of electrical installations. The humidifier MUST be con-
nected to earth.
WARRANTY
A warranty term is applicable to the parts of the RTH humidifier to the exception of the valves and the heating
elements provided our recommendations of use & maintenance have been adhered to. Failure to specify and
fit original parts and accessories will invalidate our warranty.
NOTE
Our policy is one of continuous research and development. We therefore reserve the right to amend without
notice the specifications given in this document.
The photographs are for illustrating purposes only.
8
9
ElectroVap RTH-LC
Dimensions
Installation
Overall
Dimensions
(mm / in.)
Steam outlet
(mm / in. )
Weight
empty
Kg / lbs
Weight in
operation
Kg / lbs
A 545 / 21.46 1 135 / 5.3 a 135 / 5.3 25 / 55 35 / 77
B 675 / 26.58
C 270 / 10.60
Drain outlet
mm / in.
RTH 3 to 15
A
a
1
C
B
x Unpack the unit and check for any damage.
x Damage to packing and/or unit must be reported by registe-
red letter to carrier within 3 working days.
x Provide free space all around the unit : 1 m. to 1.20 m (3.3 to
4 ft) from the floor, 1.25 m. (4.1 ft) ahead and 0.60 m. (2 ft) on
the right hand side for allowing easy access for maintenance.
x Mark the mounting holes and drill. Insert pegs appropriate for
support.
x Screw the upper screws allowing about 10 mm (0.4") for han-
ging the cabinet. Hang the cabinet and screw the lower
screws. Thighten up all the screws for securing the installa-
tion.
x Ensure that the cabinet is level.
x Please revert to appropriate section of this manual for water
connection.
465mm /
18.3 "
505mm /
19.88"
40mm / 1.57"
4xØ6mm - 0.23" 20mm / 0.78"
110mm
4.33"
525mm /
20.67"
Water supply service
Check valve
Water inlet hose with
3/4"femelle union.
Pictures for illustrating purposes only
A fresh mains cold water service should be used to supply the
unit. The water pressure should be between 1 and 6 bars (15
to 90 psi) & should not exceed 40°C (104°F) in temperature.
The water supply connection is under bottom of the unit. The
humidifier is delivered with a water inlet hose of 50 cm (20") long
with a 3/4" female fitting to the cold water supply. A direct
copper connection is PROHIBITED.
A check valve should be located on the mains and cold wa-
ter service connection to the unit.
The inlet valve base has a basket filter (s.a. page 38).
The RTH humidifier uses water to produce steam so lea-
kage may happen causing potential damage. If an installa-
tion in false ceiling or above prime rooms (such as mu-
seum, exhibition or laboratory rooms) is considered, ensure
that the floor below the humidifier is constructed from wa-
terproof materials (with draining facilities) to withstand any
water spilling during servicing or if a problem occurs.
Information about the water quality : Chloride concentration :
< 75 mg/l ; phosphate concentration : < 5 mg/l ; chlorine concen-
tration (3 to 6° dA) : < 100 mg/l ; poor concentration in CO2 ;
organic elements in poor concentration.
The RTH humidifier can run with the following water qualities :
x Tap or raw water : water TH between 5° and 40° French
grade
x Demineralized water : 30 μS minimum (caution : the de-
mineralized water is corrosive ; use appropriate piping
material : stainless steel, PVC)
x Softened water (TH 0° not recommended) : the cation exchangers (softeners) do not suit for the water
supply as they do not bring down the mineral salt content disolved in the water., the polyphosphate mea-
suring devices as well.
A water softener consists basically in replacing a calcium ion by a sodium ion the solubility capability of which is
about 7 times higher. So a water softener does not affect the quantity of mineral salts contained in the water but
alters their nature.
An excess of sodium chloride may generate foam which disturbs greatly the correct running of the humidifier. It
is essential that a duplex softener be used.
A small volume of tap water must be added to the softened water to get a TH value of 10° minimum and a wa-
ter analysis is recommended to determine the sodium chloride content.
10 Pictures for illustrating purposes only
ElectroVap RTH-LC
Water connection
Unit mounting
11
ElectroVap RTH-LC
STEAM OUTLET
Installation
Use steam hose from our supply.
This steam hose is able to whistand 100°C (212°F)
The humidifier should be located within 3m (9.85ft)
tof he steam distribution pipe. If the distance
from the humidifier is superior to 3m insulated
copper or stainless steel tube should be used.
a. Vertical rise at least 500mm(1.65 ft) before bend
b. The steam hose should be rigidly suported.
c. Steam hose (radius of bend superior to 300
mm - 12")
d. Duct work.
e. Obstacle.
f. A condensate separator is needed at this
point to drain condensate.
g. Steam outlet hose diameter.
h. Ø 8 mm (0.31") condensate hose. Fill with
water the condensate hose siphon before
the first running of the humidifier.
i. Humidifier height (see after page n°6. )
Number of steam outlet :
RTH 3 to 15 = 1 outlet - Ø 25 mm (1")
The RTH humidifier can work with duct pressure less than
150 mm (5.9") water column (1470 Pa - 30.70 lbf/ft2)
For pressure superior to 150 mm (5.9"), our optional
i100 mm diameter mini.
g = Ø25mm (1") RTH 3 to 15
filling cup platform must be used
to drain
Mini . diameter : 4" -
8"
9.85 ft
1.65 ft
3.3 to 4 ft
12
ElectroVap RTH-LC
Condensate draining
Installation
10°
Evaporisation
320mm-12.6"
800mm-31.5"
The following drawings show the
water draining connections that should
be made.
1. The Devatec supplied steam hose
should be used :
RTH 3to 15:1.0m (39.37")Ø25mm (1")
hose with 1 hose clamp.
This hose is designed for connecting the
humidifier to the drain. Regular replace-
ment is recommended.
2. If rigid piping is used, it must be heat
resistant PVC material (100°C-212°F)
3. The drain hose must be free from any
obstacle particularly when it comes to
connecting several units.
4. It is recommended the use of offset
tundish from the underside of the unit
as shown. This will prevent any steam
and/or condensation from getting into
the cabinet.
5. A funnel can also be used provided it
is offset from the underside of the
humidifier and that a siphon is made
as per the diameter of the draining
hose.
6. Important : keep a minimum pitch of
10°
10°
Beware of steam !
Ø100mm mini
Ø60mm
mini
Open tundish Waste water tundish
with cover & handles
4"
13
ElectroVap RTH-LC
Steam dispersion pipe
Installation
The steam from the boiler enters the
duct or an air handling unit via a steam distri-
bution pipe.
In order to obtain the optimum perfor-
mance of the humidifier, select the longest
pipe.
ExpressPack
ExpressPack
Steam dispersion pipe
Steam distribution
pipe for
RTH 5 to 20
L1
mm - in.
D40 -L290 290 - 11.42
D40-L5 590 - 23.23
D40-L790 790 - 31.10
D40-L1000 1000 - 39.37
D40-L1250 1250 - 49.21
D40-L1500 1500 - 59.05
Steam distribution selection table
Ø25 mm - 1"
Ø8-0.31"
ExpressPack
L1
The Armstrong ExpressPack is a
bespoke steam humidification system made
to suit your configuration and ready to install
in a ventilation duct.
It permits to have vapor trails
(absorbing distances) as short as 600 mm.
(23.6"). For further reference, please contact
Devatec or their authorized agent.
14
ElectroVap RTH-V2
Steam pipe positioning
Installation
Absorbing distance or vapor trail « D »
A certain length is required so that the steam coming out of the steam distribution pipe be absorbed by the
air. All along this length described as the absorbing distance, the steam can still be seen in the airflow as a mist
which can condensate in water against any obstacle if placed within. To prevent condensation, this absorbing
distance should be calculated before positioning the steam distribution pipes.
How to calculate the absorbing distance « D »
In order determine the absorbing distance, the attached calcalation table can be used :
HR1 = relative humidity of air before humidification in %.
HR2 = relative humidity of air after humidification in %.
D mini = minimum humidification distance in metres (m).
Nota bene: this calculation table is to be used for temperatures between 10°C and 25°C (50°-77°F) only.
Minimal humidification distance
The steam distribution pipes must be positioned after the minimum humidification distance calculated with the
help of the above table..
% RH1 inlet air
5 10 20 30 40 50 60 70
% RH2 outlet air
40 0.9—3 0.8—2.6 0.7—2.3 0.5—1.6 - - - -
50 1.1—3.6 1—3.3 0.9—3 0.8—2.6 0.5—1.6 - - -
60 1.4—3.6 1.3—3.3 1.2—3.9 1—3.3 0.8—2.6 0.5—1.6 - -
70 1,8—5.9 1.7—5.6 1.5—4.9 1.4—4.6 1.2—3.9 1—3.3 0.7—2.3 -
80 2.3—7.5 2.2—7.2 2.1—6.9 1.9—6.2 1.7—5.6 1.5—4.9 1.2—3.9 0.8—2.6
90 3.5 -11.5 3.4-11.8 3.2-10.5 2.9-9.5 2.7-8.8 2.4-7.9 2.1-6.9 1.7-5.6
Minimum humidification distance « D » in m - ft
Before/after fan before/after heater/filter
D D 1,5 x D 5cm
1.96"
2.5 x D before particule filtre
15
ElectroVap RTH-LC
Steam pipe positioning
Installation
A high humidity limit humidistat must be installed in the duct to stop the humidifier in case the level of
humidity exceeds the preset value.
In case the recommended distances can not be observed, please contact Devatec or their authorized agent
for an alternative solution.
If accurate values cannot be reached, a distance of 2 m. (6.5 ft) should be considered as a minimum
distance between pipes & obstruction and 3 / 4 m. (10 / 13 ft) before a humidity sensor or humidistat.
Before a junction before an air opening before a humidity sensor
D
D
5 x D
0.5 x D
Before / after a constriction before an expansion before a bend
D
0.5 x D
16
ElectroVap RTH-LC
Steam pipe positioning
Installation
11
1
1
660 mm - 26 " H>
H3
H2
H1
H2
410H > mm
19,61
1
H3
H2
1
H1
11
1
H3
H2
H1
480 mm - 18.9 " H>
550 mm - 21.65" H >
11
1
H1
H2
H2
1
H3
270H > mm
1
H3
8,
5
1
H1
Please meet the following dimensions and spaces according to your configuration. For further
information, please contact Devatec or their authorized agent.
H1 = 110mm (4.33") = Minimum height between the duct floor and the axle of the steam pipe.
H2 = 140mm (5.51") = Minimum distance between 2 steam pipes.
H3 = 160mm (6.3") = Minimum height between the duct top and the axle of the steam pipe.
The H3 distance can be 80 mm (3.15")at the shortest in case the steam pipe is installed at an
angle of 30 to 45°.
The arrow shows the direction of the air flow.
1
0
.
6
"
1
6
.14 "
17
ElectroVap RTH-LC
Steam pipe positioning
Installation
1
D
1
5
°
In vertical ducts where the air flow is upward
or downward, the steam distribution pipes
must be tilted by 15° sideways.
590
47,2
d/2
d
3 à 45°
1
H3
In duct with limited height, the distribution pipe(s) can be tilted
by 30 to 45° to get the 80 mm (3.15") minimum height.
D = Humidification distance
d = Duct diameter
18
ElectroVap RTH-LC
Steam pipe positioning
Installation
Steam pipe above humidifier RTH 3 to 15 Steam pipe under humidifier RTH 3 to15
HumidiPack duct insersion RTH 3 to 15
300 mm– 12" MINI
200 mm—8" MINI
Siphon must be full of water before starting up
A loop having the right diameter may also suit
Condensates
Condensates
Condensates
Draining system
19
ElectroVap RTH-LC
Room ventilation unit
x Tow ventilation packs permit the use of the humidifier
in direct in-space applications where there is no duct-
work.
x The ventilation packs cannot possibly be set on the
top of the humidifer (s.a. the left hand side photo).
The distance between the humidifier and the ventila-
tion pack(s) should not exceed 3m (9.85 ft).
x The steam connection between the humidifier and
the ventilation pack(s) is Ø25mm (1").
x The electrical connection of the ventilation packs to
the humidifier is via terminal block 3 & 4 on the Din
rail.
x Allow a 3 m. distance ahead to the humidifier unit(s)
for a free diffusion of steam.
Dimensions of the ventilation packs
CVMC1 CV2
0,50m—2"
3m-9.85ft
maxi
1,2m-3.9 ft
Drain
3m—9.85 ft mini
A B C D E Weight
Kg / lbs dB Max. ouput
Kg/v/h –lbs m3/h Compatible
with model
CVMC1 400mm
15.75"
195mm
7.68"
165mm
6.50"
330mm
13"
35mm
1.38"
4.6
10.14
35
10
22
150
5 ft3
RTH 3 to 10
CV2 520mm
20.47"
260mm
10.24"
350mm
13.78"
360mm
14.17"
80mm
3.15"
12
26.45 38
20
44.10
300
10 ft3 RTH 15
F
35mm
1.38"
35mm
1.38"
Installation
20
ElectroVap RTH-LC
Electrical installation
Recommandations:
All works concerned with the electrical installation must be carried out by skilled
and qualified personnel (eg electrician with appropriate training). The customer
is responsible for ensuring their suitability. Please observe local regulations
concerning the provision of electrical installations.
Check all terminal screws at commissioning, after 50 hours operation and at
every service thereafter.
Caution : the RTH electronic components are very sensitive to electrostatic
shocks. Appropriate steps must be taken before any operation.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Devatec ELECTROVAP RTH-LC Series User manual

Category
Dehumidifiers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI