Aertesi SOFFIO 38 vertical Installation, Use And Maintenance Manual

Type
Installation, Use And Maintenance Manual
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 1 AER.MIU.GB.SOFFIO.000.02.15
INSTALLATION,
USE AND MAINTENANCE MANUAL
SOFFIO SOFFIO HP
Ducted units
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 2 AER.MIU.GB.SOFFIO.000.02.15
INDEX
1-INTRODUCTION...........................................................................................................................................3
2-RECEPTION…………………………………………………………………………………………………………..3
3-POSITIONING ................................................................................................................................................ 3
4-INSTALLATION .............................................................................................................................................. 4
5-AERAULIC CONNECTIONS .......................................................................................................................... 6
6-IDRAULIC CONNECTIONS ........................................................................................................................... 7
7- ELECTRICAL CONNECTIONS ..................................................................................................................... 7
8-MANTENANCE .............................................................................................................................................. 9
8.1-Filter ......................................................................................................................................................... 9
8.2- Fan (motor standard ) ........................................................................................................................... 10
8.3- Fan (HP motor high prevalence) ........................................................................................................... 12
9- TROUBLESHOOTING ................................................................................................................................ 13
10- DISPOSAL ................................................................................................................................................. 13
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 3 AER.MIU.GB.SOFFIO.000.02.15
1-INTRODUCTION
Series units SOFFIO are designed for the function of heating, cooling, dehumidification and filtration of
residential and commercial application (offices, public buildings, or so) with the counterceiling.
Following applications are not permitted:
1. Working outdoors
2. Operations in high humid environments or explosive or dusty
3. Operations in corrosive environments, in particular for the aluminum fins of the coil
The use of the unit is not suggested for persons (including children) with reduced physical, mental or sensory
abilities, or people who have not received adequate information, without the supervision of a person
responsible for their safety.
The installation and maintenance of the unit is reserved to qualified persons (each to his task) and have
received necessary instructions. These operations must be done in accordance with safety regulations in
force. These standards may be, for example, work safety (use of protections for the eyes and hands, ...),
plant and electrical installations, pressure vessels, refrigeration equipment, lifting equipment.
The manufacturer / seller is not responsible for damage to persons or property resulting from the failure of
requirements in this manual of regular maintenance or use of non-original spare parts or change in the
product status with respect to upon receipt. Also in these cases will void the warranty on the product.
This manual must be kept with the unit.
2-RECEPTION
Unit is delivered packed in carton packaging and plastic film. Do not add weight on the packaging and not to
stack more boxes than such as are preview at the time of delivery. Check in the product label is present the
same code of the order and there are no damage to the packaging or the product. In case of non-
compliance, immediately contact the manufacturer or the seller and not proceed with the installation. Do not
dispose of packaging in the environment; dispose of it in compliance with the rules on waste disposal.
3-POSITIONING
The unit must be positioned in an appropriate location, to minimize pressure drop on the channels and the
noise emitted into the environment. There should be no installed with furniture (such as shelves, cabinets,
bookcases) under the machine, which might prevent the accessibility and the correct intake. The distance
between the ceiling and the false ceiling must be at least 15mm greater than the height of the machine.
The machine must not be exposed to direct sunlight or heat sources.
It’s necessary to provide an inspection hatch in the ceiling under the machine, in order to perform
maintenance.
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 4 AER.MIU.GB.SOFFIO.000.02.15
Meet the following minimum spaces that are needed for installation and maintenance. It’s also need a
minimum space on the suction side (filter side), at least equal to the height of the unit.
Minimum respect distance
4-INSTALLATION
Remove the cardboard packaging and / or plastic film and all guards before installation.
The machine must always be handled by two people and / or with suitable lifting means for the larger sizes.
Apply four or six threaded rods M8 (not provided) to the ceiling with bolts (not supplied) or other fasteners.
Make sure that the components used are rated to support the weight of the machine.
21
31/38
41/81
91
101
Unit weight
kg
70
90
135
175
190
The length of the bars depends on the distance between the ceiling and the false ceiling. The spacing of the
bars must comply with the measures of the drawing below.
Min 400mm
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 5 AER.MIU.GB.SOFFIO.000.02.15
Positioning of suspension bars
Lift the machine using a suitable lifting device (hoist, forklift or other) appropriate, that can support the weight
of the machine. Pass the threaded rods into the holes and secure them with fixing nut, washer and nut M8
(not supplied).
We recommend using a suitable system for not transferring to the structure some possible vibration
(vibration damping rubber or other material).
Antivibrating
Washer
Nut
Locknut
Ceiling fixing bars
A
B
C
D
21
50
230
230
708
31/38
50
230
230
1148
41/81
60
275
275
1698
21HP
50
280
280
708
38HP
50
280
280
1148
81HP
60
325
325
1698
91HP
40
350
350
1748
101HP
40
350
350
1998
21 vertical
60
285
285
708
31/38 vertical
60
285
285
1148
41/81 vertical
60
385
385
1698
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 6 AER.MIU.GB.SOFFIO.000.02.15
Check that the machine is perfectly horizontal or sloping slightly towards the condensate drain (never
counter slope). If necessary adjust the height by means of the nut and locking nuts that hold the threaded
rod to the bracket.
Unit positioning
Depending on type of ceiling and installation location, you can use other procedures, provided they comply
with the current standards and with attention for the safety of people
.5-AERAULIC CONNECTIONS
Connect the channels using the appropriate outlet flange. It is advisable to interpose a flexible connection
between the car and channels to not transmit the vibrations. Channels must be appropriately sized
(according to the prevalence of the machine) and insulated to prevent condensation and deaden the noise
propagation.
To connect the suction channels, you need a special accessory, the flange shooting (FRA). If you connect
the channels in another way, it is likely to compromise the accessibility of the filter or damage the machine.
OUTLET FLANGE
Outlet Flange
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 7 AER.MIU.GB.SOFFIO.000.02.15
6-IDRAULIC CONNECTIONS
The unit is equipped with coil suitable to work with water, water mixed with glycol. In wither season there is
the possibility to empty the water circuit if there is a risk of icing inside the battery.
To avoid the formation of condensation on the surfaces of the machine during the summer period, when the
fan is not on, it is recommended to stop the flow of chilled water in the coil through a motorized valve.
All the pipes, in particular those of the chilled water, must be insulated to prevent dripping of condensation.
For ease of maintenance, it is advisable to provide manual ball valves, in order to exclude the unit from the
plant .
While connecting pipe, don’t twist coils and valves, it is recommended to use two wrench.
Valves can be supplied in the kit (to be assembled by the installer) or by delivered by the installer.
When the installation is completed and the hydraulic system has been loaded, it is necessary to remove the
air inside the coil using the appropriate valve. Repeat the purging procedure after the activation of the
circulation pump, as long for to be sure all air bubbles will be completely eliminated.
Connect the condensate drain connection to a drainage pipe of internal diameter of 20mm. The pipe must
have a constant slope of at least 2 ° downwards. It is advisable to make a siphon with a minimum height as
shown in the figure below.
Condensate drain pipe
7- ELECTRICAL CONNECTIONS
Insert a manual switch close to the unit to be able to exclude it from the electric line during the maintenance
operations.
Provide a fuse or circuit breaker to protect the unit.
h>p(p=static
pressure, in mm)
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 8 AER.MIU.GB.SOFFIO.000.02.15
Power cables must be dimensioned with reference to the maximum current absorption of the unit, indicated
in the label and in the technical manual, but not less than 0,75mmq.
The control thermostat must be able to support the current absorbed from the unit and the start current of
the fan. Otherwise, it is recommended the presence of the accessory power module ETBN or ETBN-6th.
Check that the voltage and frequency of the power supply is 230V - 50Hz.
Before attempting any operation on the unit, check the main power supply is disconnected and can not be
turned on unintentionally.
In the basic version, the electrical panel is constituted of an electrical box plastic (model PA104). To open it,
use a screwdriver and gently lift the tabs at the location shown below.
Electrical box open PA104
If there are accessories that require a specific electrical panel of larger dimensions, this will be made of
sheet metal. To remove the cover of the electrical panel, unscrew the screws on the sides. Then remove the
cover.
Remove Cover
To access with cables inside the cabinet, use the fairlead at the bottom of the picture.
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 9 AER.MIU.GB.SOFFIO.000.02.15
Cables access
Fairlead
Before the electrical installation, see the specific circuit diagram of the unit supplied with the machine. After
completing the electrical installation, replace the electrical panel cover and secure it with screws.
8-MANTENANCE
The maintenance of the machine must be done by qualified and trained people.
Before any maintenance operation on the unit, verifiy the main power is switched off and it can not be
accidentally inserted. Make sure the engine is stopped before opening the panel of the box.
The motor, the coil and the drainage pump do not require routine maintenance. The filter instead requires
periodic cleaning.
8.1-Filter
The filter must be cleaned periodically, every 6 months or more often if the environment is dusty. It can be
vacuumed or beaten slightly.
For sizes SOFFIO 21-31-38-41-81 you can remove the filter from the side or from below. To remove it from
the bottom, you must lift the filter, detach it from the bottom rail and then slide it down. To pull it out sideways
instead unscrew the knob screw and remove the filter along the rails. Additional accessories (FRA, ....) Can
change the mode of extraction of the filter.
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 10 AER.MIU.GB.SOFFIO.000.02.15
Removal from the bottom / side of the filter machines with engines average prevalence
For high prevalence sizes (HP) is only possible the extraction of the filter from below. For vertical sizes is
only possible extraction from the front. In these cases, you must remove the brackets that block the filter.
Removing the filter with engines with a high prevalence HP or vertical
8.2- Fan (motor standard)
To remove the fan, you must first remove the bottom panel (or front for vertical), unscrewing all the screws.
Disconnect the cable or cables of the fan from the terminals of the control cabinet
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 11 AER.MIU.GB.SOFFIO.000.02.15
Remove the bottom panel
Then unscrew the M6 screws that secure the motor plate to the machine frame (2 screws for size 21, 4
screws for size 31/38, 5 screws for size 41/81).
Fixing screw size 21 Fixing screw size 31/38
Fixing screw size 41/81
Then the whole plate containing motor and fan can be removed.
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 12 AER.MIU.GB.SOFFIO.000.02.15
Removing the motor plate
After replacing the fan, install all the components performing the same operations in reverse order.
8.3- Fan (HP motor high pressure)
In versions “High Prevalence, after removing the bottom panel and disconnect the motor cables as
described in the previous paragraph, you must remove individual fans, not the whole plate. Each fan is fixed
with four self-tapping screws (2 for each side), to remove it, unscrew these screws.
Removing the motor for high prevalence machines HP
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 13 AER.MIU.GB.SOFFIO.000.02.15
After replacing the fan, install all the components performing the same operations in reverse order.
9- TROUBLESHOOTING
Anomaly
Possible failures
Remedy
The fan does not
work
There is no current
Check the breaker / fuse
The thermostat is damaged
Check if there is power to the terminals of the fan (and /
or 0-10V signal for EC)
The cables are not
connected
Verify all electrical connections within the wiring
diagram suppled
Condenser broken
Replace capacitor (AC motor)
Insufficient air flow
Dirty filter
Clean or replace the filter
Battery dirty
Clean the battery with lens cleaner
Selected speed low
Select a higher speed (max or med)
Noisy fan
Fan damaged
Visually check that the fan is undamaged
SOSTITUTION REQUIRED
Fan loose
Check that the fan is firmly secured to the machine
frame
Speed to much high
Select a lower speed (min or med)
In summer or
winter hot air
comes out cold air
Water too hot / cold
Check if temperature of inlet water is less than 10 ° C
in summer or more 40 ° C in winter.
Water flow low
Check if the dT between water input and output is at
most 7K
Valve closed
Check that all manual valves are open to interception
Valve Actuator broken
Check that the actuator has opened the valve
Air in the battery
Purge the coil with the air valve
Condensation on
discharge grille
Water too cool
Raise the water inlet temperature
Speed too low
Increase the fan speed (med or max)
Drip from the tank
Condensate drain clogged
Control the outflow of the exhaust pipe
Pan counterslope
Make sure the pan is level or tilted slightly towards the
drain
Water pipes are not
insulated
Insulate all pipes chilled water
Faulty seals
Check seals of hose connections
Dirty pan
Clean the pan to allow the normal flow of condensate
10- DISPOSAL
At the end of the service, the unit must be disposed of in compliance with local regulations on waste
disposal. The main materials present are: copper, aluminum, steel, polystyrene, plastic.
AERTESI srl SOFFIO INSTALLATION USE AND MANTEINANCE MANUAL
Page 14 AER.MIU.GB.SOFFIO.000.02.15
NOTES:
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Aertesi srl. reserves the right to introduce at any time whatever modifications deemed necessary for improving the
product with possible modification of the relevant technical data
Aertesi srl Unipersonale
viale della tecnica, 6a
35026 Conselve (PD) ITALY
t. +39.049.9501109
f. +39.049.9500823
www.aertesi.com
AER.MIU.GB.SOFFIO.000.02.15
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

Aertesi SOFFIO 38 vertical Installation, Use And Maintenance Manual

Type
Installation, Use And Maintenance Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI