4.5 Norms and approvals
OTHER ASPECTS
5
5 1
EMERGENCY
LIGHTING
Most electronic ballasts are suitable for use in emergency lighting
installations. Distinction must, however, be made between centralised
and decentralised emergency lighting. Provided the correct voltages
are applied, electronic ballasts can be used in centralised installations.
When talking about a decentralised emergency lighting set-up, many
different configurations are possible. In general the emergency
converter must have a four-pole switch-over relay to ensure that the
wiring between the HF ballast and the lamp is completely shut off
when the emergency lighting is in operation. Interference from the
emergency converter to the HF ballast is then out of the question.
Some emergency lighting installations equipped with a three-pole
switch-over relay can also be used in combination with HF electronic
ballasts, but this has to be checked and warranted by the emergency
lighting supplier and installer.
Fluorescent lamps can be dimmed with dimmable HF electronic
ballasts, such as the Philips HF-REGULATOR types.
Philips HF-REGULATOR ballasts can be controlled by a 1-10 V DC
input from various types of regulating systems.
In Fig. 15, an example is shown of an electronic potentiometer
(LPS 100) regulating the dimming level via the +/- DC input on the
HF-REGULATOR ballast.
It can be seen that a total number of up to 100 HF-R ballasts
powered by different phases can be controlled (see Fig. 16).
The control wiring must be dealt with like 230 V wiring.
For more information on the installation of different control systems,
contact your local sales agent.
5 2
HF BALLASTS AND DIMMING
Fig. 15. LPS 100 potentiometer.
SUPPORT NEEDED?
29
5
28
5.2 HF ballasts and dimming
MORE INFORMATION OR
6
Readers who want further information or support on installation
aspects of HF electronic ballasts, are invited to contact their local
Philips support office.
Also, for further reading the following printed documentation is
available on request:
Application guide to TL/CFL/QL lamp control gear
A 160-page booklet explaining all application and installation aspects
in depth, ordering number 3222 635 16641.
• Product information leaflets of the individual ballast types
Two- to four-page folders with technical details, ordering numbers
as per item.
• Compact product information
A CD-ROM with compact information, including dimensions and
photos, ordering number 3222 991 08201.
• Service policy and product replacement overview for
HF control gear
An historical overview of ballasts, including a replacement table.
Hint:
The dimming control wiring in the installation should be kept
separate from the mains wiring when the length of the wires exceeds
5 m. Otherwise, interference between mains and dimming wiring
might occur.This could cause light flicker or 100 Hz light modulation.
Tip:
If separation of the wiring is not possible, use shielded control wiring.
Fig. 16. Manual HF regulation.
N
L
-
HFR
ballast
N
L
-
+
HFR
ballast
L1
L2
L3
N
C
C
LPS 100
to lamps
to lamps
-
+ L1 L2
L3
N
HFR luminaire
HFR luminaire
to other
HFR luminaires
+
4
3
2
1
  • Page 1 1
  • Page 2 2