Infinite Peripherals SCOM-100 User manual

Type
User manual
SCOM-100, User guide 2
SCOM-100
Alarming & remote control unit
User guide
Manual version: 1.04, 2/2007
Firmware version: 1.04
Copyright © 2006, 2007 – Infinite Ltd
All rights reserved.
Disclaimer
While every effort has been made to ensure that the
information included in this guide is accurate and
complete, no liability can be accepted for any errors
or omissions.
Infinite Ltd reserves the right to change the
specifications of the hardware and software
described in this guide at any time without prior
notice.
No part of this guide may be reproduced,
transmitted, stored in fixed or removable media or
translated into any language in any form without the
prior written permission of Infinite Ltd.
Infinite makes no warranties for damages resulting
from device operation, corrupted or lost data, or any
loss caused by malfunction of the hardware or the
software.
SCOM-100, User guide 3
Contents
1. Device overview
1.1 Connections
1.2 LED indications
2. Wiring
2.1 Power supply
2.2 Digital inputs
2.3 Digital outputs
2.4 Analog inputs
2.4.1 Analog input 1
2.4.2 Analog input 2
2.5 I/O expansion power supply
2.6 GSM antenna
2.7 Microphone
3. Getting started
3.1 Preparing a SIM card
3.2 Installing the SIM card
3.3 First power up & factory settings
4. Device operation
4.1 SMS commands
4.2 Naming the unit
4.3 Configuring a digital input for alarming
4.3.1 Setting alarm message’s texts
4.3.2 Clearing the digital input configuration
4.4 Controlling the digital outputs
4.4.1 Setting a digital output
4.4.2 Resetting a digital output
4.4.3 Configuring a digital output as a closed contact
4.4.4 Pulse digital output
SCOM-100, User guide 4
4.4.5 Setting a digital output after a delay
4.4.6 Resetting a digital output after a delay
4.4.7 Digital output time based scheduling
4.4.8 Clearing the digital output configuration
4.5 Analog signal alarming
4.5.1 Analog input configuration
4.5.2 Setting alarm message’s texts for analog inputs
4.5.3 Clearing the analog input configuration
4.6 Special I/O Functions
4.6.1 ON/OFF and PID control
5. User administration
5.1 Create a new user
5.2 Change user configuration
5.3 Remove a user
5.4 Defining specific alarm recipients
5.4.1 Set a DI alarm recipient
5.4.2 Set an AI alarm recipient
5.4.3 Clear DI alarm recipients
5.4.4 Clear AI alarm recipients
6. Device status & mode controls
6.1 Setting the device status
6.1.1 RUN (Control) command
6.1.2 Monitor command
6.1.3 Stop command
6.2 Controlling the device status
6.3 Setting the device response
6.3.1 Send response SMS
6.3.2 Response format
6.3.3 Merge concurrent alarms
6.4 Setting up a SMS counter
SCOM-100, User guide 5
6.5 Setting date & time
6.6 Setting a GSM PIN
7. Monitoring capabilities
7.1 Monitoring commands
7.2.1 Using the HyperTerminal for configuration
7.2.2 Using the SCOM-100 Configurator for configuration
8. Using the microphone input
9. Appendix
9.1 Command reference
9.1.1 General parameter settings
9.1.2 User configuration
9.1.3 Output control & configuration
9.1.4 Input configuration
9.1.5 I/O Functions
9.1.6 RTC & Time scheduling
9.1.7 Monitoring commands
9.2 Troubleshooting
9.3 Technical specifications
9.4 Error handling
9.5 Status LED indications
9.6 Default parameter values
9.7 Setting an I/O expansion module address
9.7.1 GE-DIO-42 digital I/O expansion
9.8 RS232C connector layout
SCOM-100, User guide 6
1. Device overview
1.1 Connections
1: Start up button
2: SIM cardholder
3: GSM antenna connector (SMA jack)
4. Microphone connector
5: Serial port RS232 (RJ-42 connector)
6: Power supply connector
7: I/O expansion connector (6 pin modular jack)
8: Analog inputs screw terminals
9: Digital inputs screw terminals
10: DIN rail snap
11: Digital outputs screw terminals
SCOM-100, User guide 7
1.2 LED indications
1: Power indicator: Turns on after power up.
2: Four LEDs indicating the digital output states.
3: Turns on while sending or receiving an SMS.
4: Turns on if an error occurs during operation. See
sections 9.4 and 9.5 for details.
5: Monitors the device status (RUN/ MONITOR/
STOP). See sections 6.1 and 9.5 for details.
6. Flashes during device start up. Remains on if the
device is ready for operation. Turns off if one or more
operating conditions fail. See section 9.5 for details.
7. Flashes if a connection to the GSM provider is
established.
8. Four LEDs indicating the digital input states.
SCOM-100, User guide 8
2. Wiring
SCOM-100 is a simple device, not requiring special
technical background for configuration and operation.
However an electrical technician should undertake the
installation of the device.
2.1 Power supply
Power supply requirements are:
SCOM-100-12: 12VDC +/-15%
SCOM-100-24: 24VDC +/-15%
A low ripple power supply output is recommended.
Output voltage stabilization is not required.
See section 9.3.1 for details.
SCOM-100, User guide 9
2.2. Digital inputs
SCOM-100 has 4 built in digital inputs, which can be
expanded by the DIO-42 expansion modules. The digital
inputs are wired by means of screw terminals.
The digital inputs can be driven either by switches or
transistors (open collector stages). Transducers with
push-pull output are also applicable.
Note: Output voltages higher than +5V or negative
voltages (lower than GND) will be clamped
from the comparator input protection zener.
The impedance of the input circuit is, in this
case, 4.7K. An external transducer with 24V
output must be capable of driving a current of
5 mA.
SCOM-100, User guide 10
2.3 Digital outputs
SCOM-100 has 4 built in digital outputs, which can be
expanded by the DIO-42 expansion modules. The digital
outputs are wired by means of screw terminals. Each
output has a normally open contact power relay.
Voltage Current Mode
250VAC 10A AC1
250VAC 1A AC2,3
150VDC 0.5A DC
It is recommended to use external power relays to drive
inductive or capacitive loads demanding more than 0.5A.
SCOM-100, User guide 11
2.4 Analog inputs
SCOM-100 has 2 built in analog inputs (AI1, AI2). A1 is
designed for voltage input and A2 for current input.
2.4.1 Analog input 1
Analog input 1 is a voltage input with two wiring options.
Wiring option: A1A
The input voltage range for this wiring option is 0-1VDC.
The input resistance is 2K. The input voltage range is
converted internally to a digital raw range of 0-4095.
The circuit displayed on the left side of the page uses a
monolithic semiconductor sensor (AD592) for
temperature measurement. This sensor acts as a high
impedance temperature dependent current source of
1µA/K. The nominal current output is 298µA at 25°C. The
voltage drop on the analog input resistor (2K) is 496mV
at -25°C and 756mV at 105°C. The SCOM-100 power
supply (Vcc) can be used for the sensor’s excitation.
SCOM-100, User guide 12
The circuit displayed on the center uses an external
shunt resistor (~51.3 ) wired parallel to the input in
order to measure current signals (e.g. 0-20/4-20mA).
The circuit displayed on the right side of the page uses
an external resistor (Rx) to measure DC voltage (Vx). Rx
and Rin (2K) form a voltage divider. The following table
illustrates the applicable resistor Rx values for different
DC voltages:
Vx Rx Vin
0..1V 0 0 -1V
0..5V 8K, 1/4W 0 -1V
0..30V 58K, 1/4W 0 -1V
0..60V 118K, 1/4W 0 -1V
0..100V 198K, 1/4W 0 -1V
Note: In case of low voltage measurements, use short
and shielded wiring to avoid 50Hz (60Hz) line noise
inteference.
SCOM-100, User guide 13
Wiring option: A1B
Wiring option A1B is designed for 0..10VDC signal input
through an internal 18K & 2K voltage divider. The input
resistance is 20K.
SCOM-100, User guide 14
2.4.2 Analog input 2
Analog input 2 is designed as a current input.
It can be used in conjunction with industry standard
current loop transducers & sensors. Input impedance is
50. The 0-20mA input is converted internally to a digital
raw range of 0-4095.
Note: Applying a voltage source to the current input AI2
may damage the internal 50 input resistor and
respectively the entire input circuit.
SCOM-100, User guide 15
2.5 I/O expansion power supply
SCOM-100 has two ways to provide power supply for the
I/O expansion units.
Bridge Vcc to Vex on the main SCOM-100 unit to power
a limited number of I/O expansion units (up to 4), as
shown below. (Power is then wired through the 6th pin on
to the modular I/O expansion connector).
If the number of expansion modules is more than 4, an
external power supply source must be connected to the
power connector screw terminals of each expansion
module, as shown below, and the Vcc to Vex on the main
SCOM-100 unit must not be bridged.
SCOM-100, User guide 16
Note: The Vex pin must not be connected when an
external power source is connected on the
expansion modules because the main SCO-100 unit
will be damaged.
SCOM-100, User guide 17
2.6 GSM antenna
An external GSM antenna should be used for locations
with weak signal strength. SCOM-100 utilizes an SMA
plug connector to connect a GSM antenna.
The GSM antenna must be of appropriate frequency to
cover the frequency band of your GSM provider’s
network.
2.7 Microphone
A two-pin connector is provided to connect an electret
type microphone.
SCOM-100, User guide 18
3. Getting started
3.1 Preparing a SIM card
Before installing the SIM card, use your phone to:
1. Clear the PIN code (no PIN needed).
2. Enter your name and phone number in the first
place of the phonebook directory of the SIM card.
Note: You can alternatively power up the unit without a
SIM card and set the PIN number using a terminal
program on a PC, or you can set a PIN in later
configuration stages.
3.2 Installing the SIM card
Note: Always remove or install the SIM card, having the
unit powered down!
Slide the card tray out by pressing the cardholder’s
button with a spiky object such as a pencil or screwdriver.
SCOM-100, User guide 19
Insert the card into the tray and slide the tray with the
card faced down into the cardholder.
3.3 First power up & factory settings
Power up the unit and hold the startup button pressed
until the ready LED starts blinking rapidly.
The unit executes the startup procedure setting all
parameters to the factory defaults, reads the SIM card’s
phonebook entry, enters the RUN (Control) mode and
sends a HELLO SMS message to the mobile phone
number that was found in the SIM phonebook entry.
LED indication states are:
1. READY LED will switch on indicating the successful
reading of the SIM card’s phonebook entry.
2. STATUS LED will switch on indicating the RUN
(Control) mode.
3. NETWORK LED will be blinking to state successful
connection to the GSM provider’s network.
SCOM-100, User guide 20
4. Device operation
4.1 SMS commands
The SCOM-100 unit accepts text SMS commands to
configure operational parameters, control the unit’s
operation modes, and control the unit’s outputs. Several
commands can be packed in one SMS message.
An SMS command has the following structure:
XXXX,A..A,..,..,Z..Z
XXXX: Command identification number 0000-
9999
A..A, Z..Z: Command parameters
The comma character (‘,’) is used as a separator in the
command structure. The semicolon character (‘;’) is used
to separate more than one commands packed in a single
SMS.
4.2 Naming the unit
You can specify a unit name for identification purposes.
The unit name will be used in several device’s SMS
transmissions and responses. The command to name the
unit is:
0300,My SCOM-100
0300: Command ID
My SCOM-100: Device name
Use your mobile phone to edit an SMS containing the
above command. Type in the characters without any
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75

Infinite Peripherals SCOM-100 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI