York YZ Magnetic Bearing Centrifugal Chiller User guide

Type
User guide
ENGINEERING GUIDE
YORK
®
YZ Centrifugal Chiller
Form: 161.01-EG1 (0819)
MODEL YZ MAGNETIC BEARING CENTRIFUGAL CHILLER
Style A
530 through 5010 kW
(150 through 1425 Tons)
Utilizing R-1233zd
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
2
Table of Contents
Nomenclature ........................................................................................................................................ 3
Introduction ........................................................................................................................................... 4
Unit Components .................................................................................................................................. 6
Equipment Overview ............................................................................................................................. 8
Codes and Standards ......................................................................................................................... 14
Chiller Options .................................................................................................................................... 16
Application Data .................................................................................................................................. 17
Unit Weights & Dimensions................................................................................................................. 22
Visit YORK.com/Next for more information
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
3
Nomenclature
SYSTEM
YZ MA033 AN030 P042N A
MOTOR
MA 033 AA
COMPRESSOR
AN 030NA AA
VARIABLE SPEED DRIVE
P 042 NA C A 6 6
HEAT EXCHANGER
FA 21 12 A2Z *** 2 CA 1 G LR B
VSD Family
VSD Size Code
Filter (N-no filter, H-harmonic filter)
VSD Cooling
Product Family
Motor Name
Compressor Name
Unit Mod Level
VSD Name
Motor Family
Motor Size Code
Motor Configuration Level
Compressor Family
Compressor Size Code
Compressor Configuration Level
Heat Exchanger Family
Nominal Diameter
Nominal Length
Bundle Code
Tube Type
Hinges
Nozzle Arrangement
Water Connection Type
Waterside DWP
Waterbox Family
Number of Passes
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
4
Introduction
The YORK® YZ Magnetic Bearing Centrifugal Chiller is a revolutionary advancement that challenges everything about
conventional chiller design. The result is a chiller fully optimized for ultimate performance with a next generation low-
GWP (global warming potential) refrigerant, delivering superior real-world performance and a new definition of
sustainability. The YORK® YZ Chiller is available from multiple global factories to meet regional customers needs.
EFFICIENCY
Johnson Controls pioneered the term “real-world efficiency” to illustrate the energy-saving potential of focusing on chiller
performance during off-design conditions. Off-design conditions are not only seen at part-load, but at full-load operation
as well, by taking advantage of reduced entering condenser water temperatures (ECWTs). These conditions are where
chillers operate up to 99% of the time, and where operating costs add up. YZ chillers are designed to operate on a
continuous basis with cold ECWT and full condenser flow at all load points, taking full advantage of real-world conditions.
YZ chillers offer the most efficient real-world operation of any chiller, meaning lower operating costs and an excellent
return on your chiller investment.
Actual chiller efficiency cannot be determined by analyzing the theoretical efficiency of any one chiller component. It
requires a specific combination of heat exchanger, compressor, and motor performance to achieve the best system
efficiency. YZ technology matches chiller system components to provide maximum chiller efficiency under actual not
just theoretical operating conditions. Now with the YORK® YZ, efficiency is improved up to an impressive 7% at part-
load and as much as an additional 5% at full-load versus our most efficient previous designs.
BETTER EFFICIENCY IN EVERY OPERATING CONDITION
The YZ chiller has been designed to take full advantage of colder cooling tower water temperatures, which are naturally
available during most operating hours. Considerable energy savings are available by letting tower water temperature
drop, rather than artificially holding it above 19°C (65°F), especially at low load, as some chillers require.
Since the vast majority of its operating hours are spent at off-design conditions, a chiller should be chosen not only to
meet the full-load design, but also for its ability to perform efficiently at lower loads, lower tower water temperatures, and
even higher leaving evaporator water temperatures. It is not uncommon for chillers with the same full-load efficiency to
have an operating cost difference of over 10% due to differences in part-load efficiencies.
Part-load is important to an owner’s operating budget, this information has been standardized within the AHRI
Certification Program in the form of an Integrated Part Load Value (IPLV), and Non-Standard Part Load Value (NPLV).
Additionally, looking at annual energy costs that use weather data specific to your city, you can get a better understanding
of the efficiency benefits the YORK® YZ offers across a wide range of operating conditions. This more detailed analysis
also takes into account actual building load profiles to provide a more accurate view of chiller operating cost. Part-load
performance data should be requested by the customer for each job using its own design criteria.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
5
RELIABILITY
Designed for the most reliable chillers we have ever made, the YORK® YZ magnetic bearing compressor achieves
superior performance because it is based on a successful line of efficient YORK® compressors. With fewer moving parts,
YORK® compressors have proven to be durable in numerous applications, especially where minimal downtime is a
critical concern. The lubrication-free, non-contact design of the YORK® YZ provides system simplicity and reliability that
far exceeds continuous-contact-oil and refrigerant-lubricated bearing chiller designs.
The majority of chiller components on YZ chillers have been time tested on the tens of thousands of air-cooled and water-
cooled YORK® chillers operating globally. The YZ chiller employs the most advanced driveline available - an active
magnetic-bearing drive to levitate the driveshaft. The result is frictionless operation and 80% fewer moving parts than
oil-lubricated or refrigerant-lubricated systems, which is why we have used this type of driveline in our mission-critical
chillers since 1998.
The YZ chiller incorporates service design principles that are consistent with our family of centrifugal chillers. We made
sure that this chiller, and specifically the driveline, was field serviceable by a single source supplier, who also happens
to be the industry’s largest service force: our own Johnson Controls service team.
AHRI CERTIFICATION PROGRAM
The performance of the YZ chiller has been certified by the Air Conditioning, Heating and Refrigeration Institute (AHRI)
as complying with the certification sections of the latest issue of AHRI Standard 550/590. Under this Certification
Program, chillers are regularly tested in strict compliance with this Standard. This provides an independent, third-party
verification of chiller performance.
COMPUTERIZED PERFORMANCE RATINGS
Each chiller is custom-matched to meet the individual building load and energy requirements. A variety of standard heat
exchangers and pass arrangements are available to provide the best possible match.
It is not practical to provide tabulated performance for each combination, as the energy requirements at both full- and
part-load vary significantly with each heat exchanger and pass arrangement. Computerized ratings are available through
each Johnson Controls sales office. Each rating can be tailored to a specific job requirement, and is part of the AHRI
Certification Program.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
6
Unit Components
Suction Line
Endsheet
OptiView™ Control
Panel
Condenser
Sight
Glass
Lockout Handle
Variable Speed
Drive
Discharge Line
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
7
Unit Components (Continued)
VSD Coolant
Reservoir
Refrigerant
Purge Unit
Compact
Waterbox
Evaporator
Direct Drive
Compressor Motor
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
8
Equipment Overview
YORK® YZ Centrifugal Chillers are completely factory-packaged including the compressor, motor, VSD, OptiView
control center, evaporator, condenser, purge unit, and all interconnecting unit piping and wiring.
When selected, the initial charge of refrigerant can be supplied for each chiller from the factory. Actual shipping
procedures for the chiller will depend on a number of project-specific details. YZ chillers are designed to keep installation
costs low. Where installation access is not a problem, the unit can be shipped completely packaged including the unit-
mounted variable speed drive, requiring minimal piping and wiring to complete the installation.
At start-up, the services of a Johnson Controls factory-trained, field service representative are required to supervise or
perform the final leak testing, charging, initial start-up, and concurrent operator instructions.
COMPRESSOR
Note: Please refer to the YZ Operations & Maintenance Manual (161.01-OM1) for a complete description of features and
functionality.
The compressor is a single-stage centrifugal design directly driven by a hermetically-sealed motor with a VSD. A cast-
aluminum, fully-shrouded impeller is mounted directly to the motor shaft. Impeller seals employ a labyrinth geometry,
sized to provide minimal thrust loading on the impeller throughout the operating range. The impeller is dynamically
balanced and overspeed tested for smooth, vibration-free operation.
CAPACITY CONTROL
Capacity control is achieved by the combined use of variable speed control and mechanical flow regulation to provide
fully modulating control from maximum to minimum load. For normal air conditioning applications, the chiller can adjust
capacity from 100% to 10% of design, without the use of hot gas bypass (HGBP). For each condition, the capacity control
devices will be automatically adjusted to maintain a constant leaving chilled liquid temperature at optimized efficiency,
based on information fed by sensors located throughout the chiller.
YZ chillers are equipped with sophisticated capacity control as standard. Our capacity control is a patented combination
of centrifugal chiller hardware and software that expands the chiller operating range and improves chiller performance.
The capacity control continuously monitors the characteristics of the compressor discharge gas and optimizes the diffuser
spacing to minimize gas-flow disruptions from the impeller.
MOTOR
The compressor motor is a hermetically-sealed, high-speed induction motor supported by active magnetic bearings. The
bearing design provides a completely lubrication-free operating system. The motor rotor and stator are cooled by a
pressure driven refrigerant loop to maintain acceptable operating temperatures.
The active magnetic bearings are equipped with balancing systems to ensure smooth and reliable operation. In the event
of a power failure, the magnetic bearings will remain in operation throughout the compressor coast-down using an
uninterruptable power supply. Mechanical bearings are included as backup to the magnetic bearings and are designed
for rare emergency touchdown situations where both the main power and uninterruptable power supply fail.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
9
VARIABLE SPEED DRIVE
Note: Please refer to the YZ Operations & Maintenance Manual (161.01-OM1) for a complete description of features and
functionality.
A variable speed drive is factory-packaged and mounted on the YZ chiller. It is designed to vary the compressor motor
speed by controlling the frequency and voltage of the electrical power to the motor. The capacity control logic shall
automatically adjust motor speed and compressor diffuser geometry for maximum part load efficiency by analyzing
information fed to it by sensors located throughout the chiller. The variable speed drive is mounted in a NEMA-1/IP22
enclosure with all power and control wiring between the drive and chiller factory-installed. The chiller uses a single-point
power connection with a circuit breaker disconnect. Electrical lugs for incoming power wiring are provided.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
10
The variable speed drive provides automatic displacement power factor correction to 0.95 or better at all load conditions.
Separate displacement power factor correction capacitors are not required. The displacement power factor is 0.98 or
better when the optional harmonic filter is provided. Additionally, variable speed drives provide the following advantages:
Lowest chiller operating cost through part load energy savings.
Soft start with input current less than full load current.
Smooth acceleration reduces stresses on motor and driveline.
Rugged and reliable with no moving parts.
Standard features include: a door interlocked lockable circuit breaker; UL/cUL listed and CE approved ground fault
protection; over-voltage and under-voltage protection; 3-phase sensing motor over-current protection; single-phase
protection; insensitive to phase rotation; over-temperature protection and readouts of important values on the OptiView
control panel.
OPTIVIEW CONTROL CENTER
Note: Please refer to the YZ Operations & Maintenance Manual (161.01-OM1) for a complete description of features and
functionality.
The YORK® OptiView Control Center is a factory mounted, wired and tested microprocessor based control system for
centrifugal chillers. It provides control of chiller operation and monitoring of chiller sensors, actuators, relays and switches.
As part of the capacity control logic, OptiView controls the leaving chilled liquid temperature and adjusts the motor
current via control of the Variable Geometry Diffuser (VGD) and Variable Speed Drive (VSD).
The panel comes configured with a full screen graphic display mounted in the middle of a keypad interface with soft keys.
The operator may view a graphical representation of the historical operation of the chiller as well as the present operation.
The locations of various chiller parameters are clearly marked, and instructions for specific operations are provided on
many of the screens. To prevent unauthorized changes of setpoints and operating conditions, security access is provided
with three different levels of access and passwords.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
11
The graphic display also allows information to be represented in both SI and Imperial units of measure, and has the
ability to display many languages.
OptiView continually monitors the system operation and records the cause of any shutdowns (safety, cycling or
normal). This information is recorded in memory and is preserved even through a power failure condition, so the user
may recall it for viewing at any time. During operation, the user is continually advised of the operating conditions by
various status and warning messages. By providing a common networking protocol through the Building Automation
System (BAS), YORK® chillers not only work well individually, but also as a part of the building system. This networking
protocol allows increased remote control of the chiller, as well as 24-hour performance monitoring via a remote site. In
addition, compatibility is maintained with the present network of BAS communications. Both of these remote control
capabilities allow for the standard Energy Management System (EMS) interface:
1. Remote Start
2. Remote Stop
3. Remote leaving chilled liquid temperature setpoint adjustment
4. Remote current limit setpoint adjustment
5. Pulse Width Modulation
6. Remote “Ready to Start” Contacts
7. Safety Shutdown Contacts
8. Cycling Shutdown Contacts
HEAT EXCHANGERS
Shells
Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams or carbon steel
pipe. Carbon steel tube sheets, drilled and reamed to accommodate the tubes, are welded to the end of each shell.
Intermediate tube supports are fabricated from carbon steel plates, and drilled and reamed to eliminate sharp edges.
The refrigerant side of each shell is designed, tested, and stamped in accordance with local pressure vessel codes.
Tubes
Heat exchanger tubes are copper alloy high-efficiency, externally and internally enhanced to provide optimum
performance. Utilizing the “skip-fin” tube design provides a smooth internal and external surface at each intermediate
tube support. This provides extra wall thickness (up to twice as thick) and non work-hardened copper at the support
location, extending the life of the heat exchangers. Each tube is expanded into the tube sheets providing a leak-proof
seal, and is individually replaceable.
Evaporator
The evaporator is a patented hybrid falling-film type heat exchanger. It contains a balance of flooded and falling-film
technology to optimize efficiency, minimize refrigerant charge, and maintain reliable control. A specifically designed spray
header provides uniform distribution of refrigerant over the entire shell length to yield optimum heat transfer. A suction
eliminator is located above the tube bundle to prevent liquid refrigerant carryover into the compressor. A 38 mm (1.5")
liquid level sight glass is conveniently located on the side of the shell to aid in determining proper refrigerant charge. The
evaporator shell contains a dual refrigerant relief valve arrangement or a single relief valve arrangement if the chiller is
supplied with the optional refrigerant isolation valves. A 25.4 mm (1") refrigerant charging valve is provided for service
access.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
12
Condenser
The condenser is a shell and tube type heat exchanger with a discharge gas baffle to prevent direct high velocity
impingement on the tubes. The baffle is also used to distribute the refrigerant gas flow properly for the most efficient heat
transfer. An integral subcooler is located at the bottom of the condenser shell, providing highly effective liquid refrigerant
subcooling to provide the highest possible cycle efficiency. A 38 mm (1.5") liquid level sight glass is conveniently located
on the side of the shell to aid in determining proper refrigerant charge. The condenser contains dual refrigerant relief
valves.
Waterboxes
The removable waterboxes are fabricated of steel. Integral steel water baffles are located and welded within the waterbox
to provide the required pass arrangements. Stub-out water nozzle connections welded to the waterboxes are suitable
for ANSI/AWWA C-606 couplings, welding or flanged, and are capped for protection during shipment. Plugged 19 mm
(3/4") drain and vent connections are provided in each waterbox.
Water Flow Switches
Thermal or differential pressure type water flow switches are factory mounted in the evaporator and condenser water
nozzles, and are factory wired to the OptiView control panel.
Refrigerant Flow Control
Refrigerant flow to the evaporator is controlled by the YORK® variable orifice control system. Liquid refrigerant level is
continuously monitored to provide optimum subcooler, condenser and evaporator performance. The variable orifice
electronically adjusts to all real-world operating conditions, providing the most efficient and reliable operation of
refrigerant flow control without the use of a refrigerant pump.
Refrigerant Purge Unit
The purge is designed to meet the ASHRAE Standard 147 where at most one unit mass of refrigerant is purged per one
unit mass of air removed by the unit. This automatic, self-contained, high-efficiency purge unit collects non-condensable
gases to be removed from the chiller. The YORK® purge is factory assembled, mounted, piped, and wired, and operates
automatically. Purge exhaust cycles are monitored, and if excessive, provide warning of a potential system leak to the
OptiView Control Center.
ISOLATION MOUNTING
The unit is provided with four vibration isolation mounts of nominal 25.4 mm (1") operating height. The isolators have a
neoprene pad to contact the foundation, bonded to a steel plate. The vibration isolation pad assemblies mount under
steel plates welded to the chiller tube sheets.
Optionally, spring isolation mounting is available instead of standard isolation mounting pads. Four level-adjusting,
spring-type vibration isolator assemblies with non-skid pads are provided for field-installation. Isolators are designed for
25.4 mm (1") of deflection.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
13
REFRIGERANT CONTAINMENT
The standard unit has been designed as a complete factory-packaged chiller, which minimizes the joints from which
refrigerant can leak. The entire assembly is thoroughly leak tested at the factory prior to shipment. The YZ chiller includes
service valves conveniently located to facilitate transfer of refrigerant to a remote refrigerant storage/recycling system.
Optional factory-installed isolation valves in the compressor discharge line and refrigerant liquid line allow isolation and
storage of the refrigerant charge in the chiller condenser.
FACTORY TESTING
Johnson Controls has the ability to factory performance test every type of chiller that we engineer and manufacture.
Testing options, including performance, vibration, and sound, can be performed as factory or remote customer witness
tests.
SMART EQUIPMENT
Smart Equipment by Johnson Controls allows the connection of data streams from equipment to the cloud, providing
unprecedented insights into operations. Smart Equipment helps maximize system control for greater efficiency, extended
equipment life and reduced operating costs. The YORYZ chiller has controls embedded at the factory to allow the
chiller to connect seamlessly to a controls system. On-board controls that support cloud-based data analytics, including
fault detection, enables proactive maintenance and minimizes downtime.
YORK® SMART CONNECTED CHILLERS
YORK® Smart Connected Chiller functionality feeds YZ chiller data to a secure, cloud-based dashboard, enabling
analysis of historical data to diagnose the chiller, observe long-term trends, and investigate potential issues. The
dashboard collects status-related data warnings, cycling, and safety fault codes. Advanced algorithms detect problems
such as condenser or evaporator tube fouling or low refrigerant charge. A more strategic approach to maintenance can
be implemented to stay a step ahead of emergencies to save time and money.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
14
SHIPMENT
Each unit can be broken down into several form shipment configurations for ease of transportation and installation. For
all broken down shipment options, the unit is first factory assembled, refrigerant piped, wired and leak tested; then
disassembled according to the shipment option selected.
Protective covering is furnished on the OptiView and VSD. Water nozzles are capped with fitted plastic enclosures.
Then the entire unit is protected with industrial-grade, reinforced shrink-wrap covering.
Form 1 Unit is shipped as one assembly with refrigerant charge inside the unit.
Form 2 Unit is shipped as one assembly with refrigerant charge shipped separately.
Form 3 Driveline separate from shells. Shipped as three major subassemblies with refrigerant charge shipped
separately. This form is best used when height is a limiting dimension to enter the installation site.
Driveline (motor/compressor assembly)
Evaporator/Condenser shell assembly not skidded
Variable Speed Drive
Form 7 Driveline separate from split shells. Shipped as four major subassemblies, with refrigerant charge shipped
separately. This form is best used when the chiller must fit through a tight space, limited by multiple dimensions.
Driveline (motor/compressor assembly)
Evaporator not skidded
Condenser not skidded
Variable Speed Drive
Form 11 Unit shipped as two major subassemblies, with refrigerant charge shipped separately. This form is best used
when width is a limiting dimension to enter the installation site.
Condenser side assembly (Condenser/OptiView/Variable Speed Drive) not skidded
Evaporator side assembly (Evaporator/Driveline/Magnetic Bearing Controller) not skidded
Codes and Standards
Chiller standards and codes vary based on factory source. Any of the standards and codes listed below can be met when
ordering the YZ chiller. Work with your local sales contact for a unit that will meet your local codes and standards.
PERFORMANCE & ENERGY STANDARDS
ASHRAE 90.1
AHRI Standard 550/590
IECC International Energy Conservation Code
GBCI Green Business Certification Inc.
Eurovent (EN14511, EN14825)
GB 18430.1
GB 19577/GB 50189
GB/T 50378
MEPS Minimum Energy Performance Standards
ECBC Energy Conservation Building Code
Greenmark
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
15
BEC Business Environment Council
SASO Saudi Standards, Metrology and Quality Organization
ESMA Emirates Authority for Standardization and Metrology
LEED EA4 enhanced refrigerant management credit
BREEAM Refrigerant Credit Building Research Establishment Environmental Assessment Method
SOUND RATINGS
AHRI 575
ISO 9614/3744
JB/T 4330
PRESSURE VESSEL CODES
ASME Boiler and Pressure Vessel Code Section VIII
PED European Pressure Equipment Directive
NB/T 47012
KHK High Pressure Gas Control Law
ELECTRICAL CODES
c/U.L. Underwriters Laboratory
N.E.C. National Electrical Code
CE Directive 93/68/EEC
IP Ingress Protection
GB 5226.1
ETL Electrical Testing Labs
SAFETY CODES
ASHRAE 15 Safety Code for Mechanical Refrigeration
ASME
Safety Code for Mechanical Refrigeration (EN 378-2/A2)
Machinery Directive (2006/42/EC)
EMC Directive (2004/108/EC)
Safety of machinery Electrical Equipment of Machine (EN 60204-1)
GB 25131
MANUFACTURING REQUIREMENTS
Manufactured in an EN ISO 9001 accredited organization
Conform to CE Testing Services for construction of chillers and provide CE listed mark
EN 61000-6-2:2005 and EN 61000-6-4:2007 compliance for use in an industrial environment
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
16
Chiller Options
ITEM
DESCRIPTION
STANDARD
OPTIONAL
VSD
Harmonic Filter
None
Input harmonic filter
Incoming customer wiring
60 Hz: 460V, 400V, 380V
50 Hz: 415V, 400V, 380V
VSD cooling heat exchanger protection
(for condenser fluid lines)
None
Sediment accumulator
Heat Exchangers
Tube wall thickness
0.635 mm (0.025")
0.711 mm and 0.889 mm
(0.028" and 0.035")
Factory tube testing
None
Factory Eddy current
testing
Evaporator thermal insulation
None
19 mm, 25.4 mm
1
, 32
mm
2
, and 38 mm (3/4”, 1”,
1.25”, 1.5”) standard
thickness
Waterbox
es
Customer piping connections
Grooved
Flanges
Waterbox design
Compact
Marine
Design working pressure
1034 kPa (150 psig) DWP
2070 kPa (300 psig) DWP
Hinges
None
1034 kPa & 2070 kPa
(150 psig & 300psig) DWP
Corrosion protection
None
Internally epoxy coated
waterboxes and
tubesheets, sacrificial
anodes
Unit Configuration
Ability to isolate refrigerant charge in the
condenser
None
Isolation valves
Minimum load (assuming AHRI
unloading)
Down to 10% unloading
Down to 0% with hot gas
bypass
Unit mount
Neoprene pads
Spring isolation
Flow switches in the evaporator and
condenser water nozzles
Thermal flow switch or
differential pressure flow
switch
3
Ship loose paddle flow
switches
Unit paint
Caribbean blue paint
Amerlock 400, Amershield
Factory knock-down shipment options
Form 1 or 2
4
Form 3, 7, or 11
Unit wrapped before shipment
Partial wrapping (driveline
& electrical)
Complete chiller wrapping
Temporary shipping skids
None
Shipping skids
Long term storage requirements
None
Long term storage
Contact your local sales representative for more information.
1
Asia-source only
2
Europe-source only
3
Asia-source standard
4
Europe-source standard
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
17
Application Data
The following is a guide to the application of YZ chillers to ensure reliable operation. While this guide is directed
towards normal, water-chilling applications, a Johnson Controls sales engineer can provide complete
recommendations on other types of applications.
LOCATION
YZ chillers are virtually vibration free and may generally be located at any level in a building where the construction will
support the total system operating weight.
The unit site must be a floor, mounting pad or foundation which is level within 6.5 mm (1/4") and capable of supporting
the operating weight of the unit.
Sufficient clearance to permit normal service and maintenance work should be provided all around and above the unit.
Additional space should be provided at one end of the unit to permit cleaning of evaporator and condenser tubes as
required. A doorway or other properly located opening may be used if convenient.
The chiller should be installed in an indoor location where temperatures range from 4.4°C to 40.0°C (40°F to 104°F).
The dew point temperature in the equipment room must be below the entering condenser water temperature to prevent
condensing water vapor inside of the VSD. Other areas susceptible to water vapor condensate are outside of the
condenser shell and condenser waterboxes. Example applications include cooling condenser water using chilled water,
wells, river, or other low temperature fluids.
Refrigerant Relief Piping - Each chiller is equipped with dual pressure relief valves on the condenser and two dual relief
valves on the evaporator, or two single relief valves on the evaporator if the optional refrigerant isolation valves are
ordered. The dual relief valves on the condenser are redundant and allow changing of either valve while the unit is fully
charged. The purpose of the relief valves is to quickly relieve excess pressure of the refrigerant charge, as a safety
precaution in the event of an emergency such as a fire. They are set to relieve at an internal pressure as noted on the
pressure vessel data plate, and are provided in accordance with local pressure vessel codes.
Sized to the requirements of applicable codes, a vent line must run from the relief device to the outside of the building.
This refrigerant relief piping must include a cleanable, vertical leg dirt trap to catch vent-stack condensation. Vent piping
must be arranged to avoid imposing a strain on the relief connection and should include one flexible connection.
Sound and Vibration Considerations - A YZ chiller is not a source of objectionable vibration in most air conditioning
applications. Standard neoprene isolation mounts are available with each unit to reduce vibration transmission. Optional
level-adjusting spring isolator assemblies designed for 25.4 mm (1") static deflection are also available for further
isolation. YZ chiller sound pressure level ratings will be provided upon request. Control of sound and vibration
transmission must be taken into account in the equipment room construction as well as in the selection and installation
of the equipment.
Thermal Insulation - The chiller’s cold surfaces should be insulated with a vapor barrier insulation sufficient to prevent
condensation. As an option, a chiller can be factory-insulated. This insulation will normally prevent condensation in
environments with dry bulb temperatures of 10.0°C to 32.2°C (50°F to 90°F) and relative humidity up to 75% [19 mm
(3/4") thickness], 85% [25.4 mm (1”) thickness], or 90% [38 mm (1.5") thickness]. It is intended for a chiller installed
indoors and, therefore, no protective covering of the insulation is usually required. If insulation is applied to the
waterboxes at the job site, it must be removable to permit access to the tubes for routine maintenance.
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
18
Ventilation - Some standards requires that all machinery rooms be vented to the outdoors utilizing mechanical ventilation
by one or more fans. State, local and any other related codes should be reviewed for specific requirements. Since the
YZ chiller motor is hermetically sealed, no additional ventilation is needed due to motor heat.
In addition, the ASHRAE Standard 15 requires a refrigerant vapor detector to be employed for all refrigerants. It is to be
located in an area where refrigerant from a leak would be likely to concentrate. An alarm is to be activated and the
mechanical ventilation started at a value no greater than the Threshold Limit Value (TLV) of the refrigerant.
WATER CIRCUITS
Flow Rate - For normal water chilling duty, evaporator and condenser flow rates are permitted at water velocity levels in
the heat exchanger tubes of between 0.91m/s and 3.66m/s (3.0 fps and 12.0 fps) for evaporators and 1.0m/s and 3.66m/s
(3.3 fps and 12.0 fps) for condensers. Two pass units are also limited to 134kPa (45ft H
2
O) water pressure drop. The
three pass limit is 201kPa (67.5ft H
2
O). Variable flow in the condenser is not recommended, as it generally raises the
energy consumption of the system by keeping the condenser pressure high in the chiller. Additionally, the rate of fouling
in the condenser will increase at lower water velocities associated with variable flow, raising system maintenance costs.
Cooling towers typically have narrow ranges of operation with respect to flow rates, and will be more effective with full
design flow.
The chillers can tolerate a 50% flow rate change in one minute that is typically associated with the staging on or off of an
additional chiller; however a lower flow rate change is normally used for better system stability and set point control.
Proper sequencing via the building automation system will make this a very smooth transition.
Variable Primary Flow - There is increasing interest to use variable primary flow (VPF) systems in large chilled water
plants. VPF systems can offer lower installation and operating costs in many cases, but do require more sophisticated
control and flow monitoring. YZ chillers will operate successfully in VPF systems. With a minimum allowable evaporator
tube velocity of 0.5m/s (1.5 fps) for standard tubes at part load rating conditions, YZ chillers will accommodate the wide
variation in flow required by many chilled water VPF applications.
Temperature Ranges - For normal water chilling duty, leaving chilled water temperatures may be selected between
3.5°C (38°F) and 21.0°C (70°F) to obtain temperature deltas between entering chilled and leaving chilled water
temperature of 1.7°C up to 16.7°C (3°F up to 30°F).
Water Quality - The practical and economical application of liquid chillers requires that the quality of the water supply
for the condenser and evaporator be analyzed by a water treatment specialist. Water quality may affect the performance
of any chiller through corrosion, deposition of heat-resistant scale, sedimentation or organic growth. These will degrade
chiller performance and increase operating and maintenance costs. Normally, performance may be maintained by
corrective water treatment and periodic cleaning of tubes. If water conditions exist which cannot be corrected by proper
water treatment, it may be necessary to provide a larger allowance for fouling, and/or to specify special materials of
construction.
General Piping - All chilled water and condenser water piping should be designed and installed in accordance with
accepted piping practice. Chilled water and condenser water pumps should be located to discharge through the chiller
to assure positive pressure and flow through the unit. Piping should include offsets to provide flexibility and should be
arranged to prevent drainage of water from the evaporator and condenser when the pumps are shut off. Piping should
be adequately supported and braced independently of the chiller to avoid the imposition of strain on chiller components.
Hangers must allow for alignment of the pipe. Isolators in the piping and in the hangers are highly desirable in achieving
sound and vibration control.
Convenience Considerations - To facilitate the performance of routine maintenance work, some or all of the following
steps may be taken by the purchaser. Evaporator and condenser waterboxes are equipped with plugged vent and drain
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
19
connections. If desired, vent and drain valves may be installed with or without piping to an open drain. Pressure gauges
with stop-cocks and stop-valves may be installed in the inlets and outlets of the condenser and chilled water line as close
as possible to the chiller. An overhead monorail or beam may be used to facilitate servicing.
Connections - The standard chiller is designed for 1034 kPa (150 psig) design working pressure in both the chilled
water and condenser water circuits. The connections (water nozzles) to these circuits are furnished with grooves to
ANSI/AWWA C-606 standard for grooved and shouldered joints. Piping should be arranged for ease of disassembly at
the unit for tube cleaning. All water piping should be thoroughly cleaned of all dirt and debris before final connections are
made to the chiller.
Chilled Water - A water strainer of maximum 3.2 mm (1/8") perforated holes must be field-installed in the chilled water
inlet line as close as possible to the chiller. If located close enough to the chiller, the chilled water pump may be protected
by the same strainer. The strainer is important to protect the chiller from debris or objects which could block flow through
individual heat exchanger tubes. A reduction in flow through tubes could seriously impair the chiller performance or even
result in tube freeze-up. A flow switch is factory installed in the evaporator nozzle and connected to the OptiView panel,
which assures adequate chilled water flow during operation.
Condenser Water - The chiller is engineered for maximum efficiency at both design and part load operation by taking
advantage of the colder cooling tower water temperatures which naturally occur during the winter months. Appreciable
power savings are realized from these reduced heads. At initial startup, entering condensing water temperature may be
as much as 16.7°C (30°F) colder than the standby chilled water temperature.
MULTIPLE UNITS
Selection - Many applications require multiple units to meet the total capacity requirements as well as to provide flexibility
and some degree of protection against equipment shutdown. There are several common unit arrangements for this type
of application. The YZ chiller has been designed to be readily adapted to the requirements of these various arrangements.
Parallel Arrangement - Chillers may be applied in multiples with chilled and condenser water circuits connected in
parallel between the units. Figure 1 below represents a parallel arrangement with two chillers. Parallel chiller
arrangements may consist of equally or unequally sized units. When multiple units are in operation, they will load and
unload at equal percentages of design full load for the chiller.
Figure 1 Parallel Evaporators (Evap.) Parallel Condensers (Cond.)
Cond. 1
Evap. 1
Cond. 2
Evap. 2
T
S1
S2
T
S
- Thermostat for Chiller Capacity Control
- Temperature Sensor for Chiller Capacity Control
YZ Engineering Guide
Form: 161.01-EG1 (0819)
)
20
Depending on the number of units and operating characteristics of the units, loading and unloading schemes should be
designed to optimize the overall efficiency of the chiller plant. It is recommended to use an evaporator bypass piping
arrangement to bypass fluid around evaporator of any unit which has cycled off at reduced load conditions. It is also
recommended to alternate the chiller cycling order to equalize chiller starts and run hours.
Series/Parallel Arrangement - Chillers may be applied in pairs with chilled water circuits connected in series and
condenser water circuits connected in parallel. All of the chilled water flows through both evaporators with each unit
handling approximately half of the total load. When the load decreases to a customer selected load value, one of the
units will be shut down by a sequence control. Since all water is flowing through the operating unit, that unit will cool the
water to the desired temperature.
Figure 2 Series/Parallel Arrangement
Series Counter Flow Arrangement - Chillers may be applied in pairs with chilled water circuits connected in series and
with the condenser water in series counter flow. All of the chilled water flows through both evaporators. All of the condenser
water flows through both condensers. The water ranges are split, which allows a lower temperature difference or "head"
on each chiller, than multiple units in parallel. For equal chillers, the machine at the higher temperature level will typically
provide slightly more than half the capacity. The compressor on each chiller is often matched, such that the high
temperature machine can operate at the low temperature conditions when one unit is cycled off at part load (as compared
to series-parallel chillers which are typically not identical).
Figure 3 Series Evaporators (Evap.) Series-Counter Flow Condensers (Cond.)
Cond. 1
Evap. 1
Cond. 2
Evap. 2
S1
S2
T
S
- Temperature Sensor for Chiller Capacity Control
- Thermostat for Chiller Capacity Control
T
Cond. 1
Evap. 1
Cond. 2
Evap. 2
T
S1
S2
T
S
- Temperature Sensor for Chiller Capacity Control
- Thermostat for Chiller Capacity Control
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

York YZ Magnetic Bearing Centrifugal Chiller User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI