Enter the Pipe and Liquid Parameters
The ultrasonic metering system calculates proper transducer spacing based on the piping and liquid information you enter
into the transmitter via the integral keypad or the software utility.
The most accuracy is achieved when the transducer spacing is exactly what the transmitter calculates, so use the calculated
spacing if the signal strength is satisfactory. If the pipe is not round, the wall thickness not correct or the actual liquid being
measured has a different sound speed than the liquid programmed into the transmitter, the spacing can vary from the
calculated value. In that case, place the transducers at the highest signal level observed when moving the transducers slowly
around the mount area.
OTE:N Transducer spacing is calculated on “ideal” pipe. Ideal pipe almost never exists, so you may need to alter the
transducer spacing. An effective way to maximize signal strength is to configure the display to show signal strength,
fix one transducer on the pipe and then—starting at the calculated spacing—move the remaining transducer small
distances forward and back to find the maximum signal strength point.
MPORTANTI
Enter all of the data on this list, save the data and reset the transmitter before mounting the transducers.
The following information is required before programming the instrument:
Transducer mounting configuration Pipe liner thickness (if present) Pipe O.D. (outside diameter) Pipe liner material (if present)
Pipe wall thickness Fluid type Pipe material Fluid sound speed
1
Pipe sound speed
1
Fluid viscosity
1
Pipe relative roughness
1
Fluid specific gravity
1
Table 4: Parameters required
1
Nominal values for these parameters are included within the transmitter’s operating system. The nominal values may be used as they appear or may be modied if exact system
values are known.
OTE:N Much of the data relating to material sound speed, viscosity and specific gravity is pre-programmed into the
transmitter. You need to modify this data only if you know that a particular application’s data varies from the
reference values. See “Configuration” on page35 for instructions on entering configuration data into the transmitter
via the transmitter’s keypad. See “Parameter Configuration Using the Software Utility” on page46 for data entry via
the software.
After entering the data listed above, the transmitter will calculate proper transducer spacing for the particular data set. The
distance will be in inches if the transmitter is configured in English units, or millimeters if configured in metric units.
Mount the Transducer
After selecting an optimal mounting location and determining the proper transducer spacing, mount the transducers onto
the pipe.
1. Clean the surface of the pipe. If the pipe has external corrosion or dirt, wire brush, sand or grind the mounting location
until it is smooth and clean. Paint and other coatings, if not flaked or bubbled, need not be removed. Plastic pipes typically
do not require surface preparation other than soap and water cleaning.
2. Orient and space the FDT-47, FDT-48 and FDT-47-HT transducers on the pipe to provide optimum reliability and
performance. On horizontal pipes, when Z-Mount is required, mount the transducers 180 radial degrees from one another
and at least 45 degrees from the top-dead-center and bottom-dead-center of the pipe. See Figure 10. Also see “Z-Mount
Configuration” on page22. On vertical pipes, the orientation is not critical.
The spacing between the transducers is measured between the two spacing marks on the sides of the transducers. These
marks are approximately 0.75 inches (19 mm) back from the nose of the FDT-47 and FDT-47-HT transducers, and 1.2 inches
(30 mm) back from the nose of the FDT-48 transducers. See Figure 11.
Mount FDT-41…46 and FDT-41…46-xxx-HT transducers with the cable exiting within ±45 degrees of the side of a horizontal
pipe. On vertical pipes, the orientation does not apply.
Alignment
Marks
Figure 11: Transducer alignment marks
Page 19