Buderus Logamatic 2107 Applications Manual

Type
Applications Manual
Applications Manual
Logamatic 2107 Controls
Modular control system for
Buderus fl oor standing boilers with
indoor reset, outdoor reset, mixed zones,
and solar DHW capability
2
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
Applications manual
| 3
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
Table of Contents
1 Introduction 4
2 Terms 5
3  Control Programming 7
4  Installation of the Logabracket 9
5 Setting Parameters 10
6 Troubleshooting 12
7 Description of Wiring Terminals 17
8 Application Drawings 20
9 Burner/Boiler Wiring 52
10 Multi-zone Relay Controls 64
11 Mixing 67
12 Tables/Formulas 70
4
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
1 Introduction
This manual addresses some of the many applications that are
possible using Buderus outdoor reset controls. Applications
depicted in the manual are presented with both hydraulical and
electrical outlines. The drawings contained in this manual are
intended to be used as an aid to system installers and
designers and are conceptual in nature. Auxiliary equipment
depicted in this manual does not necessarily represent any one
particular manufacturer or specifi c model number. There are a
wide variety of techniques, practices and piping arrangements
possible with hydronic heating systems and it is the
responsibility of the installing contractor to determine which of
these is best suited for a specifi c application.
In an eff ort to simplify electrical drawings, they have been
limited to zone controlling only (space heating and DHW). Other
constants such as power input, boiler sensor and outdoor
sensor wiring have also been eliminated. Information for wiring
of burners can be found in section 9 of this manual. Further
information can be found in the control service manual.
Although this manual covers many common applications for our
equipment, the possibilities are virtually endless. Should you
encounter an application that is not covered in this manual or
have questions regarding any of its content, we encourage you
to contact us here at Bosch Thermotechnology Corp.
Bosch Thermotechnology Corp. reserves the right to make
changes without notice due to continuing engineering
and technological improvements .
Applications manual
| 5
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
2 Terms
Outdoor Reset: Outdoor reset is a control method that takes
outdoor air temperature into consideration when determining the
system water temperature. Instead of a fi xed high limit
temperature (i.e. 180°F (82°C)), the high limit is reset to a
temperature high enough to satisfy the heat loss at any given
outdoor temperature.
In designing a heating system the fi rst requirement is an accurate
heat loss calculation. Several factors are used in determining heat
loss; the volume of space being heated, type of materials being
used in construction, insulation values and a design temperature.
The design temperature represents the coldest day of the year.
The heat loss calculation is then used to determine the output
requirements for the boiler, baseboard, panel radiators, etc. In
short the system is sized to heat the house on the coldest day of
the year.
However, a building‘s heat loss is ever changing; and is largely
dependent on outdoor temperature. As the outdoor temperature
drops, the heat loss increases and as it rises the heat loss
decreases. The fact is that approximately 98% of the heating
season the boiler and radiators are oversized. With
outdoor reset controlling you can more accurately match the
output from the heating system to the current heat loss. For
example, it may require 180°F (82°C) water temperature
circulating through the system in order to have enough output to
maintain a 70°F (21°C) indoor temperature on a 10°F (-12°C) day.
Yet, at a 40°F (5°C) outdoor temperature it may only require
135°F (57°C) water temperature to satisfy the heat loss. By
resetting the system water temperature, a lower average water
temperature is used throughout the heating season and maximum
temperature is used only on the coldest days of the year.
Among the many benefi ts to this type of controlling is optimum
fuel economy. By only heating the water to the minimum
temperature needed, fuel economy is maximized (as much as
30% in fuel savings!). Lower standby losses during “off ” cycles
(due to a lower boiler temperature) also reduce fuel consumption.
In addition, the room comfort level is signifi cantly increased by
matching the heat output to the current heat loss. Less room
temperature fl uctuation is realized. System noise caused by
expansion of piping is signifi cantly reduced due to lower system
water temperatures.
Constant circulation zone: A constant or continuous circulation
zone is just what the term implies, water continuously circulates
through a given zone when the heating system is in operation.
The water temperature in this zone is modulated so that the heat
output from the distribution units (i.e., fi n-tube baseboard, panel
radiators, radiant fl oors, etc.) matches the rate of heat loss for that
zoned area. A constant circulation zone is typically the main
heating zone. In multi-zone systems, the constant circulation zone
must require the highest system water temperature. With this
method of controlling, a room sensor is required in order to
monitor room temperature. All secondary zones will have standard
room thermostats to intermittently operate a zone valve or zone
circulator.
The constant circulation zone will only be interrupted under the
following conditions:
• Domestic hot water priority.
• Certain setback modes (See the control Service Manual for
information on various setback modes).
• Condensate protection. If boiler water temperature falls below
the condensate protection temperature while the burner is
ring, the space heating circulator(s) will be shut off . Once the
boiler temperature reaches a safe level, circulator operation
will resume.
• When the outdoor temperature rises above the WWSD (warm
weather shut down) setting.
WWSD: Warm weather shut down or summer-winter changeover,
is the outdoor air temperature at which the space heating function
of the system shuts down. With the Buderus control system this
temperature is adjustable from 49°F to 87°F (9°C to 31°C). When
the outdoor temperature rises above the WWSD set point, the
system will only operate for domestic hot water production. (For
detailed operation of the WWSD feature refer to the control
Service Manual).
BFU Room sensor: The Buderus room sensor is similar to a
thermostat although it will not turn a circulator on or off . The
function of the room sensor is to continually monitor room
temperature and relay this information back to the control system.
This information is used to compensate for variations in room
temperature due to internal heat gains (or losses) such as solar
gain, fi replaces, wood stoves, appliances, lighting, people, open
doors or windows, etc. The control compensates for these
variations by adjusting the system water temperature (up or down)
in order to maintain the desired room temperature. Buderus room
sensors also allow the occupant to manually override
programmed setback periods.
The control system allows you to limit the amount of
compensation that the room sensor has over the selected
heating curve. This setting is referred to as “ROOM COMP” and
can be adjusted at the programming level of the control. This
setting is only available when using a room sensor.
You may want to limit compensation if secondary zones are under
radiated.
Example: The main heating zone (continuous circulation) zone is
experiencing solar heat gain. The room sensor senses the rise in
room temperature and lowers the system water temperature in
order to keep the zone from over heating. In this scenario, the
system water temperature could be lowered enough so that the
output from a secondary zone was insuffi
cient to satisfy that zone.
Only one Buderus room sensor can be used for high temperature
space heating (a second room sensor can be added when using
an FM241 module for motorized mixing of a lower water
temperature).
Careful consideration must be given to placement of room
sensors. Keep in mind that not all applications are suitable for
using a constant circulation zone. Avoid using a room sensor in a
small baseboard zone as overheating may occur during DHW
6
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
production. A standard room thermostat can be used in
conjunction with the room sensor to give high limit protection.
Setback: Buderus reset controls allow the occupant to program
setback periods in order to further reduce operating costs.
Several modes of setback can be selected with the Buderus
control. The two modes used for residential applications are
“SETBACK” and “RMSETBACK”. Unlike conventional
setback thermostats that only reduce the zone temperature
setting, the Buderus control system will operate the boiler at a
reduced water temperature. For example, at a 30°F (-1°C)
outdoor temperature the boiler water temperature may be 145°F
(63°C), at that same 30°F (1°C) outdoor temperature during a
setback period, the boiler water temperature may be reduced to
130°F (54°C).
This further reduction of water temperature will decrease the
output from the radiators by lowering the room temperature in
the living space. The extent to which the water temperature is
reduced is dependent upon the desired room temperature
reduction during setback periods. This value can be set in one
of two ways:
• SETBACK mode - a “DAYTEMP” and a “NIGHTTEMP”
would be entered on the Buderus control (this would be
done when you are not using a BFU room sensor)
• RMSETBACK mode - when using a BFU room sensor, the
room sensor allows you to select the amount of room
temperature setback.
Allowance for pick-up time must be considered when coming
out of a setback period. Systems that operate on outdoor reset
will have a longer recovery time than systems that operate at
maximum temperatures all the time. The two variables to
consider are the amount of room temperature reduction
and the length of the setback period. The use of a BFU room
sensor can speed up the recovery time, however the amount of
temperature boost is dependent upon the ROOMCOMP setting
on the Buderus control (for details refer to the control Service
Manual).
Applications manual
| 7
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
3 Control Programming
The following will allow access to the service side of the control:
1. Push and hold the turn page button " " while inserting
a pen or wire into the hole "
" on the display.
2. The word AMERICAN will be displayed.
3. Turn blue dial once to the right, BLR TEMP will be displayed.
  This is a main category.
4. Push and release return button to access sub menu.
FREEZE TEMP will be displayed. If the outdoor
temperature drops beneath the frost protection limit, the
heating system pump (contacts 61/63) will be started.
Factory default: 41°F (5°C).
5. Turn blue dial one more time and BUILD RESP will be
displayed. The current setting will be 2, change that to 1 by
holding the "
" button and turning the blue dial until
you get to the number 1 and release. This will let the boiler
respond faster to outside air temp changes.
6. Turn the dial one more time and PUMPLOGIC will be
displayed. The current setting is 104°F (40°C). This will not
let the burners and the pump run at the same time below
104°F (40°C) to protect from condensation.
7. Turn the dial one more time and MAXTEMP1 will be
displayed. The current setting for this is 176°F (80°C). To
change this to 194°F (90°C), hold down the "
" button
and turn the blue dial until 194°F (90°C) appears, then
release. (this may not be necessary unless under radiated)
8. Now push the return button "
" once.
9. Now you are back to the main categories. Turn the blue dial
once to the right and it will read CIRCUIT1.
10. Push and release the "
" button and REF TEMP will
be displayed which represents the boiler water temperature
at 14°F (-10°C). Default is 167°F (75°C). Refer to page 20
in the service manual for graphing REF TEMP changes.
11. Turn the blue dial one more time and REMOTE1 will appear.
The factory setting is off, and the only time you have to turn
this on is if you are using a BFU room sensor. Use a BFU
room sensor for constant circulation on one zone and power
the pump off of 61 and 63.
Once REMOTE1 setting is turned „on“, the ROOM COMP
parameter will be displayed. Use ROOM COMP to adjust the
room influence on the heating curve.
12. Turn the blue dial one more time and OASETBACK will
appear. Hold the "
" and turn the blue dial to
SETBACK. On the OASETBACK mode, the pumps will
turn off in the night setback mode if the temp outside is
above the freezetemp. In the SETBACK mode the curve
will drop back for fuel savings. If you have a room sensor
and want to do the temp set back by it, you will need to
change it to RMSETBACK.
13. Turn the blue dial one more time and OFFSET will appear.
 The setting will be at 0°F (0°C) and is okay with normal
radiation, but if you have an air handler, you will need to
raise the offset to 9°F (5°C). This will raise the beginning of
the curve and supply enough temperature on milder days.
14. Push and release the return button "
" again.
15. Turn the blue dial one more time and DHW PROD will
appear. The factory setting is ON. If no DHW tank is
installed, hold down the "
" button and turn until it says
OFF and release.
16. Turn the blue dial one more time and RECIRPUMP will
appear. The setting is 2, it can be changed to OFF,
1,2,4,5,6,ON. The pump will run 3 minute cycles depending
on the number of cycles you choose per hour. If you do not
have a recirc pump turn it to OFF.
17. Turn the blue dial one more time and HTG CURVE1 will
appear. Hold the "
" button and turn the blue dial. It
will show you three points on the curve so you can see what
the water temp will be at 3 different points, then release.
18. Turn the blue dial one more time and RELAYS will appear.
This will allow you to test all the components that are wired
to the 2107 control.
19. Push the "
" button and BURNER will appear. Hold
the "
" button and turn the blue dial and the LCD will
read ON, release and the burner will start. Hold the "
"
button and turn the blue dial and the LCD will read OFF,
release and the burner will turn OFF.
20. Test the Heating Pump (constant circulation pump),
DHW Tank Pump, and DHW Recirc Pump the same way.
21. When you are done with the RELAY tests push the return
button "
" .
22. Turn the blue dial one more time and LCD-TEST will
appear. To test the LCD display, hold the "
" button
and turn the blue dial, release and it should read
LCD-TEST.
23. Turn the blue dial one more time and RESET should
appear. To reset the control back to factory settings, hold
the "
" button until all of the 8‘s disappear and release.
The first thing you will need to do is go back to the language
and it will read DEUTSCH. Hold the "
" button and
turn the blue dial until you read AMERICAN on the LCD.
The control is now back to factory setting.
Now push the AUT button and you will be back in Automatic
mode.
8
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
US
C
®
This product has been tested and is certifi ed for
both the US and Canadian markets and meets all
applicable US and Canadian standards.
Notice:
To match the typical building, the following factory settings may
need adjustment:
BLDG RESP: Change to 1 if typical 2x4 or 2x6 construction
MAX TEMP: Change to 185-190°F if high temperature
baseboard is used
OASETBACK: Change to SETBACK if no room sensor is being
used or
RMSETBACK: if a room sensor is present
Refer to page 10 for additional details.
Applications manual
| 9
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
4 Installation of the Logabracket
The Logabracket is designed to create strain relief for your line
voltage and low voltage wiring for the 2107 Logamatic controls.
The bracket is mainly designed for use with the G115, G125,
GB125 and G124X boilers, but with minor modifi cations can be
used on other boiler models as well.
G115, G125, GB125, G124X
Line the bracket up with holes, place the Logamatic in place
over the holes and secure with screws provided. Four conduit
connections are provided for line voltage wiring; a slotted
opening is used to run low voltage sensor wiring.
G215
It is necessary to bend down the tabs on the rear jacket panel
to prevent interference between bracket and jacket panel.
G234X, G334X
Simply cut off the tabs of the bracket and mount on the rear
panel by drilling an additional hole for a second mounting screw.
GA124, GA244
These boilers do not require the bracket as strain relief
connections are provided on the rear of the boiler.
Figure 1 Logabracket installation
1 Logabracket
2 2107 Logamatic control
3 Screws
10
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
5 Setting parameters and display
data for the Logamatic 2107
Display
AMERICAN Language selection
BOILER Boiler parameters
FREEZE TEMP Freeze protection limit
BUILDING Building response
2-STAGE1 Burner type¹
MIN MOD² Minimum modulation output²
TIME RUN² Minimum burner run time²
PUMPLOGIC Pump logic threshold
MAX TEMP Maximum boiler switch-off temperature
CIRCUIT 01 Heating circuit 1 installation parameters (unmixed heating circuit)
PERIM HTG Heating system
REF TEMP Design temperature
REMOTE 1 Remote control ON/OFF
ROOM COMP Room temperature compensation³
OA SETBACK Type of setback
OFFSET Room temperature offset
CIRCUIT 02 Heating circuit 2 installation parameters (mixed heating circuit)4
FLOOR HTG Heating system
REF TEMP Design temperature
DHW PR5 DHW priority
MAX TEMP Maximum heating circuit temperature
REMOTE 2 Remote control ON/OFF
ROOM COMP Room temperature compensation³
OA SETBACK Type of setback
OFFSET Room temperature offset
Note: For footnotes, see next page
+
Press the ‘Display’ key and ‘Install’ key at the same time to call up the
service level. Alternatively press (1....7), clock, and return arrow button
simultaneously. See Chapter 3 for extended functions.
Applications manual
| 11
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
Display
SOLAR
7
SLR FN ON Solar function ON/OFF
MAX SL SR Maximum storage tank temperature in solar mode
MIN SL SR Minimum storage tank temperature in solar mode
DHW PROD Domestic hot water ON/OFF
RECIRC PUMP DHW circulation pump
HTG CURVE 1 Heating characteristic curve HK1
HTG CURVE 2 Heating characteristic curve HK2
RELAYS Relay test
BURNER (St.1) Burner relay stage 1
BURNER21, MOD2² Burner relay¹ stage 2, modulation output²
HTG1 PUMP Heating circuit pump (HZ1 unmixed)
HTG2 PUMP4 Heating circuit pump (HZ2 mixed)
MIX VALVE4 Mixer
4
DHW PUMP Tank DHW pump
RECIR PUMP DHW circulation pump
SLR PUMP
Solar pump
LCD TEST LCD test
TIME Time, accuracy
RESET Reset
VERSION Version number
1 Only if the FM 242 module is installed and 2-stage burner is selected.
2 Only if the FM 242 module is installed and modulating burner is selected.
3 Only if BFU remote control is installed.
4 Only if the FM 241 module is installed.
5 Only if DHW is installed.
6 Only if FM 241 module is installed and if heating circuit 2 is selected as an "FLOOR HTG" or "PERIM HTG" heating system.
7 Only if FM 244 module is installed.
12
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
6 Troubleshooting
6.1 "NO HEAT" call
ZM1
LT GRY
“BRENNER” (burner) wiring block
– Terminal 4 – 120V Neutral
– Terminal 8 – 120V input clocks hours run meter
(must be fi eld wired)
– Terminal 9 – 120V input displays “BURNER ERR”
message (must be fi eld wired)
– Terminal 10 / 11 – “dry” contacts close to energize
burner
– Terminal 12 – 120V power (drops out when manual
reset limit is tripped)
Burner operation
The R2107 is not a cold start control. It does not reply on a call
for heat from an end switch or thermostat to fi re the boiler.
The boiler will maintain a range of water temperature based on
outdoor temperature. The diff erential of this range is dynamic,
meaning that it is not fi xed, and will adjust based on outdoor
temperature and current system load. The starting point of the
diff erential is 27°F (15°C) and will adjust from there. The
diff erential will generally be wider at milder outdoor
temperatures and narrower at colder outdoor temperatures.
The diff erential is split above & below the current target
temperature.
Example: Outdoor temperature at 32°F, based on heating curve
the water temperature required is 140°F with a 26°F burner
diff erential.
The diff erential (26°F) is split (13°F) above & (13°F)
below the target temperature.
140°F target + 13°F = 153° high limit
140°F target - 13°F = 127° low limit
This 127°F to 153°F becomes the range of temperature that the
boiler will maintain. As zones call and pull heat from the boiler,
eventually the temperature in the boiler drops. Once the
temperature in the boiler hits the low limit (127°F) the R2107
control closes a switch (dry contacts) between terminals 10 & 11
to fi re the boiler (this is indicated by a fl ame symbol displayed
on the LDC screen of the R2107). When the boiler temperature
reaches the high limit (153°F), the contacts open and the boiler
stops fi ring.
Once the outdoor temperature drops below the WWSD setting,
the boiler begins to maintain temperature. Above WWSD the
boiler will only fi re on a call for DHW.
Applications manual
| 13
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
ZM1
LT GRY
Oil burners – factory jumper between terminals 12 & 10, brings
120V from 12 to 10. When contacts close between terminals 10
& 11, 120V power is sent from terminal 11 to Hot on the burner
(terminal 4 is the neutral).
Gas burners – remove factory installed jumper between
terminals 10 & 12. The contacts between terminals 10 & 11 are
now “dry” (no voltage present) and switching to the burner is
now low voltage between terminals 10 & 11 on the R2107 and
TT (or RW) on the boiler aquastat.
14
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
18
18
11
Applications manual
| 15
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
6.2 "INSUFFICIENT HEAT" call
A call for insuffi cient heat is generally a simple matter of adjusting
the heating curve.
The water temperature required for any heating system is
determined by any number of factors but the biggest infl uence we
see is the amount of radiation in comparison to the actual heat
loss. Buildings with less radiation in relation to their actual heat
loss require higher water temperature than buildings that are
overradiated. Every house is unique in terms of it’s heat
requirements. Some of the many factors include, construction,
exposure to sun, elevation, surroundings (trees, other structures,
etc), furnishings, internal heat gain (computers, lights, people,
appliances, etc) and the expectations and comfort level of the
individual.
The heating curve on a R2107 can be adjusted in several
ways:
REF TEMP – the reference temperature adjusts the slope of the
heating curve. The REF temperature in the R2107 references a
boiler water temperature at 14°F outdoor temperature. In general,
if the homeowner complains that they can never get the house up
to temperature, adjust the REF temperature up. A rule of thumb
would be: for every 1°F you want to raise the room temperature,
increase the REF temp by 2.5°F.
For example: Customer says they can’t get the house above 65°F.
We need to increase the room temperature by 5°F
…5 x 2.5 = 12.5.
You would increase the REF temperature by 12 or 13°F. The
default setting in the R2107 is 167°F REF temperature.
OFFSET – the OFFSET setting is used to raise the starting water
temperature of the system. Another way to say this is, raising the
OFFSET setting will give you higher water temperature at milder
outdoor temperatures. Common applications for adjusting the
OFFSET setting include, hydro-air, fan coils, unit heaters, etc.
These types of heating units typically require some amount of
minimum water temperature. Occasionally, you may have a call
for insuffi cient heat but only in milder weather. Even with fi n-tube
radiation, cast-iron radiators or panel radiators. With this type of a
call, you will want to increase the OFFSET setting.
USE THE QUICK REFERENCE GUIDE FOR INITIAL
PROGRAMMING
16
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
6.3 "NO DHW" Call
ZM1
LT GRY
A “DHW PROD ERR” message will appear on the LCD screen
of the R2107 control with regard to domestic hot water
production.
DHW ERR - when the tank temperature drops to the low limit
(7°F below the set point), the R2107 goes into DHW priority
mode.
The R2107 will learn through its own adaptive software
intelligence the required temperature needed in the boiler to
satisfy a call for domestic hot water. During DHW priority, it
interrupts power to the space heating circuit {terminals 61 & 63)
before the tank setpoint is reached and energizes the DHW
pump circuit {terminals 24 (N) & 25 (H)} to purge the generated
heat in the boiler into the indirect tank. The pump circuit symbol
is displayed on the LCD screen during DHW operation.
The purpose of the R2107 intelligence is such that it is designed
to operate the burner for the least amount of time to satisfy
DHW and return the boiler back to its required heating
temperature level.
In DHW priority, if the R2107 does not sense a rise in DHW
temperature in 30 minutes, it will display a DHW PROD ERR
message. The DHW PROD ERR will also be displayed if the
tank is not satisfi ed within 2 hours.
At this point, the control will go back to space heating mode and
lock out the DHW to avoid freezing the building. This message
is general in nature and the R2107 control is essentially telling
you, “I tried to make domestic hot water but nothing happened”.
IN MOST CASES THE PROBLEM IS NOT WITH THE R2107
CONTROL. To rule out the R2107, turn power off to the R2107
to reset.
The R2107 will again try to make DHW. Check terminals 24 &
25 for 120V. If power is present and boiler fi res the R2107 is
o.k.
Check the following:
1 - bad circulator
2 - stuck fl ow check
3 - piping is air bound
4 - closed valve
Applications manual
| 17
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
7 Description of wiring
terminals
ZM1
LT GRY
Line Voltage (120V) Connections:
White (ZM 1 ) Constant 120V power:
Used to supply line voltage power when using optional module FM241. The wiring harness on the
FM241 module plugs into this block.
White (Netz) Power input:
Connect 120V power source to L and N using 10 amp in-line fuse provided.
Orange (SI) Safety connections:
Terminals 17 and 18: There is a factory-installed jumper berween terminals 17 and 18. This jumper
must stay in place unless a dry contact Low Water Cutoff , CO-detector or similar
safety device is used. When using such a safety device, remove the jumper and
connect the normally closed contacts to terminals 17 and 18. On 24V devices
connect the dry contacts to 17 and 18.
NOTE: cutting this circuit will disrupt power to the burner, but keep the controls
and heating system powered.
Terminal 19: When the manual reset high-limit trips, terminal 19 puts out 120V for alarm
signal (alarm provided by others).
Green (Brenner) Burner connection:
Terminal 4: Common neutral
Terminal 8: Requires 120V input to operate the hours run meter
Terminal 9: Requires 120V input to display burner error
Terminal 10 and 11:  Dry contact closure for burner fi ring
Terminal 12: Constant 120V voltage. Power from manual reset high limit
(See section 9 of this manual for application wiring diagrams for burner circuit)
Yellow/Blue (UE) Flue gas testing:
Used on GB125. Do not remove factory installed jumper between terminals 2 and 3.
Green (HK- I ) Space heating circuit # 1 :
120V power output on terminals 61 and 63 for space heating pump(s). Not to exceed 5 amp draw. If
multiple space-heating pumps are used, refer to specifi c application wiring diagrams provided in this
manual (section 8).
Grey (PS) Domestic water circulator:
120V power output on terminals 24 and 25 for DHW production.
Purple (PZ) Domestic water recirculation pump:
120V power output on terminals 13 and 14 for DHW recirculation.
Note: Power to terminals 61 and 63 are interrupted when the system is in domestic water production. Therefore, there will
never be power on terminals 24/25 and 61/63 at the same time, while operating in automatic mode
18
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
ZM1
LT GRY
Sensor Connections (Low Voltage):
Brown (BF) BFU room sensor-circuit #I:
Connect BFU room sensor (circuit #1) using 18-2 AWG wire. Connections are polarity sensitive, terminal
1 must be wired to terminal 1 on room sensor, etc. Wiring can be run up to 500’ from control.
Light Gray (FB) Domestic tank sensor
The FB tank sensor and terminal plug are supplied with the control. For SU and ST series tanks the FB
sensor is inserted into the immersion well in the tank. For L and LT series the sensor is surface mounted
on the front of the tank using the bracket provided on the tank. Sensor wire can be extended if
necessary, using 18 AWG wire.
Green (FK) Boiler sensor:
The FK sensor comes pre-wired to the terminal block and bundled together with two capillaries. This
sensor bundle is inserted into the chrome well provided. (refer to control Service Manual for well location
for specifi c boiler model)
Blue (FA) Outdoor sensor:
The outdoor sensor is a thermistor-type sensor protected by a UV resistant enclosure. The outdoor
sensor should be installed on the North/Northeast side of the building, out of direct sunlight. Mount the
sensor at a height where it cannot be tampered with or aff ected by snow accumulation. Run 18-2 AWG
wire to the outdoor sensor up to 300’ in length. Avoid running wire parallel to telephone or line voltage
wires.
Applications manual
| 19
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018 Technical specifi cations are subject to change without prior notice
Optional modules:
FM241 Mixing module
Brown (SH/PH-HK2) Mixing and Space heating circuit #2:
Terminal 41 Power input for mixing motor
Terminal 43 “OPEN” output to mixing motor
Terminal 44 “CLOSE” output to mixing motor
Terminals 61/63 Power output for circuit #2 pump(s) (2 amp max)
(refer to section 7 of this manual for detailed wiring information for FM241)
Brown (BF) BFU room senor-circuit #2
Connect BFU room sensor (circuit #2) using 18-2 AWG wire. Connections are polarity
sensitive, terminal 1 must be wired to terminal 1 on room sensor, etc. Wiring can be run up to
500’ from control.
Light Brown (FB) Mixed circuit sensor:
The FB sensor and terminal plug are supplied with the FM241 module. The FB sensor is
strapped onto circuit #2 piping, for sensing of the mixed water temperature mount to piping
using the spiral spring and clip provided and cover with pipe insulation. The sensor leads can
be extended if necessary, using 18-2 AWG wire.
Wiring Harness Power Supply:
Connect the wiring harness attached to the FM241 module (brown, blue, and yellow/green
wires) to wiring block ZM 1 on the control.
FM242 Staging Module
White Terminal 36 Not used.
Terminal 37/39 Dry contact closure for fi ring of stage 2.
Terminal 38 Output signal for modulating burners only.
(refer to section 9 of this manual for detailed wiring information for FM242)
FM244 Solar Card
PSS Solar pump GND
61 N
63 L
FSK Terminal 1/2 Collector sensor
FSS Terminal 1/2 Tank bottom sensor
20
|
Logamatic 2107 Controls
Applications Manual
Logamatic 2107 Controls applications manual | 06.2018
Technical specifi cations are subject to change without prior notice
8 Application drawings
Description (page#)
Single temperature systems
8.1 Single Zone Space Heating with panel radiators (constant
circulation)/Indirect DHW Heating (page 22)
8.2 Single Zone Space Heating/Indirect DHW Heating (page 24)
8.3 2-Zone Space Heating with BFU and 1 thermostat (with
constant circulation zone)/Indirect DHW Heating (page 26)
8.4 Multi-Zone Space Heating/Indirect DHW Heating (page 28)
8.5 Multi-Zone Space Heating using Zone Valves (with constant
circulation zone/Indirect DHW Heating (page 30)
8.6 Multi-Zone Space Heating using Zone Valves/Indirect DHW
Heating (page 32)
Multi-Temperature Systems
8.7 Multi-Zone High Temp Space/Radiant Floor Heating with
FM241 module & Motorized Mixing Valve/Indirect DHW
Heating (page 34)
8.8 Multi-Zone Radiant Floor Heating with FM241 module and
Motorized Mixing Valve/Indirect DHW Heating (page 38)
8.9 Parallel Boiler Piping with FM242 Module / Indirect DHW
Heating (page 42)
8.10 Dual Boiler / Primary/Secondary Piping with FM242
Module / Indirect DHW Heating (page 45)
8.11 Multi-Zone Space Heating/On-demand High Temp Heating/
Indirect DHW Heating (page 48)
Boiler/Burner Wiring
In order to simplify electrical application drawings, boiler/burner
wiring has been omitted from this section. Detailed wiring
schematics for oil burners, G124X, G234X and G334X gas
boilers are located in section 9.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Buderus Logamatic 2107 Applications Manual

Type
Applications Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI