Danfoss Termix One-B Operating instructions

Type
Operating instructions

Danfoss Termix One-B is an instantaneous water heater that can be used to provide domestic hot water for flats, single-family houses as well as for small apartment buildings with up to 10 apartments. It is equipped with a heat exchanger and thermostatic control, and it can be used with district heating networks or decentralized heating systems. The device is designed to cool out district heating water very efficiently, resulting in good operation economy. The domestic hot water is prepared in the heat exchanger, and the temperature is regulated with a thermostatic control valve.

Danfoss Termix One-B is an instantaneous water heater that can be used to provide domestic hot water for flats, single-family houses as well as for small apartment buildings with up to 10 apartments. It is equipped with a heat exchanger and thermostatic control, and it can be used with district heating networks or decentralized heating systems. The device is designed to cool out district heating water very efficiently, resulting in good operation economy. The domestic hot water is prepared in the heat exchanger, and the temperature is regulated with a thermostatic control valve.

Operatingguide
TermixOne-B
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
5.0Design.............................................................6
5.1Design...............................................................6
5.2Schematicdiagram................................................7
6.0Controls..........................................................9
6.1DHWtemperaturecontrol........................................9
6.2Maintenance........................................................10
7.0Troubleshooting..............................................11
7.1Troubleshootingingeneral......................................11
7.2TroubleshootingDHW............................................11
7.3Disposal.............................................................12
8.0Declaration......................................................15
8.1Declarationofconformity........................................15
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
1
OperatingguideTermixOne-B
2.0Functionaldescription
Instantaneouswaterheaterwithheatexchangerand
thermostaticcontrol.Designedforwallmounting.
Application
TheTermixOneisaninstantaneouswaterheaterfeaturingsuperb
heatextractionandhighperformance.TheTermixOneissuitable
forats,single-familyhousesaswellasforsmallapartment
buildingswithupto10apartments.Thewaterheaterisavailablein
threesizes,eitherfor1apartment,for14apartmentsorfor5up
to10apartments.TheTermixOneisapplicablefordecentralized
heatingsystemsaswellasfordistrictheatingnetworkswith
summeroperationatlowtemperaturesorchangesindifferential
pressure.TheTermixOneheatexchangercoolsoutthedistrict
heatingwaterveryefciently,therebycreatingaverygood
operationeconomy.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
thetemperatureisregulatedwithathermostaticcontrolvalve.
Thepatentedsensoracceleratoracceleratestheclosingofthe
DanfossAVTBvalveandprotectstheheatexchangeragainst
overheatingandlimescaleformation.Thesensoracceleratorand
AVTBvalvealsoworksasabypasskeepingthehousesupplyline
warm.Thisshortensthewaitingperiodsduringsummerwhenthe
heatingsystemisinreducedoperation.Thesensoraccelerator
helpstoensureastablehotwatertemperaturebyvaryingloads,
owtemperaturesanddifferentialpressurewithouttheneedfor
readjustingthevalve.Thereisnoadditionalpressurelossonthe
secondarysideoftheDHWheatexchangerwithathermostatic
control.Thereforethistypeofregulationcanbeusedbylow
pressureontheinthecoldwatermains.
2
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
3
OperatingguideTermixOne-B
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Domesticcoldwater(DCW)
2.Domestichotwater(DHW)
3.Districtheating(DH)supply
4.Districtheating(DH)return
Connectionsizes:
DH:
G¾”(int.thread)
DCW+DHW:
G¾”(int.thread)
Dimensions(mm):
Type1+2withoutcover:
H428xW312xD155
Type1+2withcover:
H430xW315xD165
Type3withoutcover:
H468xW312xD155
Type3withcover:
H470xW315xD165
Weight(approx.):1012kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
5
OperatingguideTermixOne-B
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
O
Termixsensoraccelerator
7
Thermostaticcontroller,DHW
6
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
5.2Schematicdiagram
DH
Supply
DHW
DH
Return
DCW
DH
Supply
DHW
HWC
DH
ReturnDCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Firstdiagram:TermixOne-B-withGTU.
Seconddiagram:TermixOne-B-withsafetyvalve.
Schematicdescription
B
Heatexchanger,DHW
7
Thermostaticvalve
2
Singlecheckvalve
21
Tobeorderedseparately
4
Safetyvalve
62
GTUPressureequalizer
6
Thermostatic/non-returnvalve
DHW:DomesticHotWater
DCW:
DomesticColdWater
HWC:
HotWaterCirculation
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
7
OperatingguideTermixOne-B
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
8
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
9
OperatingguideTermixOne-B
6.1.3Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
6.1.4GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe
secondarysideoftheTermixwaterheatersandcanbeusedasa
substitutetothesafetyvalve.
Furthermorethepressureequalizerabsorbsapossibleincreasein
pressure,soadischargeoutletisomitted.
TheGTUPressureEqualizermaynotbeappliedinsystemswithhot
watercirculation.
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
10
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
11
OperatingguideTermixOne-B
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
12
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
13
OperatingguideTermixOne-B
14
DEN-GT
VI.CW.J4.02/LUK38000
DanfossHeating
OperatingguideTermixOne-B
8.0Declaration
8.1Declarationofconformity
Category0withoutelectricalequipment
DanfossHeating
VI.CW.J4.02/LUK38000
DEN-GT
15
OperatingguideTermixOne-B
ProducedbyDanfossA/S©11/2016
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Danfoss Termix One-B Operating instructions

Type
Operating instructions

Danfoss Termix One-B is an instantaneous water heater that can be used to provide domestic hot water for flats, single-family houses as well as for small apartment buildings with up to 10 apartments. It is equipped with a heat exchanger and thermostatic control, and it can be used with district heating networks or decentralized heating systems. The device is designed to cool out district heating water very efficiently, resulting in good operation economy. The domestic hot water is prepared in the heat exchanger, and the temperature is regulated with a thermostatic control valve.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI