  • Hello! I am an AI chatbot trained to assist you with the MULTISPAN MS-1208 Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
SET ENT
ENT
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
MS 1208
ºC
SCANNER
0 0 0 0
CH 1
www.multispanindia.com
Page - 1
MS-1208
OPERATING MANUAL
8 CHANNEL TEMP. SCANNER
MS-1208
Power Supply
Operating
Temperature
Relative
Humidity
100 to 250V AC,50/60 Hz, Approx 4VA
0°C To 55°C
Up to 95% RH Non Condensing
Model
Display
Size (mm)
Panel Cutout
Range
Input
96 (H) X 96 (W) X 50 (D) mm
92 X 92 mm
J Type: 0 To 600°C/K Type: 0 To 1200°C/
PT-100: -99 To 400°C (DP Selectable)
J,K,PT-100/3W Selectable
MS-1208
Technical Specification
Connection Diagram
Protection
Level
(As per request)
IP-65 (Front side) As per IS/IEC 60529 : 2001
UPPER:- 4 Digit 7 seg 0.56”, red LED Display
LOWER:- 3 Digit 7 seg 0.4”, red LED Display
- - -- -
-- -
18
14
19
13
20
12
21
11
22
10
23
24
1 2 3 4 5 6 7 8 9
16
17
15
+++
+ + +++
T/C T/C T/CT/CT/C
PT-100/3W PT-100/3W PT-100/3WPT-100/3WPT-100/3W
T/CT/C T/C
PT-100/3WPT-100/3W PT-100/3W
CH-1 CH-4 CH-5CH-3CH-2
CH-6CH-8
8 CHANNEL SCANNER (J,K, PT-100)
Range: ‘J’ : 0 To 600°C
‘K’ : 0 To 1200°C
PT-100/3W : -99 To 400°C (DP Selectable)
CH-7
AUX. SUPPLY
100 To
250V AC
~
100
250V AC
~
50/60 HZ
4VA
AUX. SUPPLY
100 To
250V AC
~
~
50/60 Hz
4VA !
100
250V AC
LN
1) Do all connection as shown in connection diagram.
2) To enter in parameter menu, press set key.
Configure: 1. Scan time
2. Sensor Selection ( J, K or PT-100 Selectable)
3. Skip or unskip channel
4. DP selection for pt-100 only.
3) If needed to add offset, press + together for 5 Sec.
Set offset for each channel if required.
Off set range will be -25°C to + 25°C.
4) Press & Hold Key for continuous scrolling or manual scrolling.
5) In hold mode use & Key to select next channel.
Procedure
ENT
ENT
www.multispanindia.com
Page - 2
9 9
J - T Y
J - T y
Press key to enter in menu
Press key to go to next parameter
(J,K & RTD)
Press key to go to next channel
Press key to go to next channel
Press key to go to next parameter
(Repeat the same procedure for all 8 channels)
(Repeat the same procedure for all 8 channels)
Press key to go to next parameter
s C N
C H 1
C H 8
Display shows scan time use & key to change it.
Display shows sensor type. Use & key to change it.
Display shows sensor type. Use & key to change it.
C H1
C H 8
D P
Channel Skip or Unskip using & Key
Channel Skip or Unskip using & Key
Decimal Point Using & Key (Yes/No)
u n S
u n S
Y E S
MS 1208
Basic Configuration
SET
Press key to change offset
Press key to go to next channel
Press key to go to next parameter
(Offset Value: ± 25°C)
(Repeat the same procedure for all 8 channels)
S E T
O F 1
O F 8
Press & key to change offset
O F S T
O 0 0 0
O 0 0 0
Display shows offset value Use & key to change it.
OFFSET Setting
Press set key to save & exit if no key is pressed, will auto exit after 10 sec.
Press key to save & exit
Press key to save & exit
Note:
Key Operation
ENT
SET
SET
SET
SET
SET
SET
SET
SET
SET
2) Press & Key to change the parameter setting.
3) Press + Key to set offset.
4) Press & hold key to enter in scroll & hold mode.
1) Press key to enter in menu.
h
h
SET ENT
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
MS 1208
ºC
SCANNER
0 0 0 0
CH 1
MS-1208
www.multispanindia.comPage - 3
All safety related codifications, symbols and instructions that appear in this operating manual
or on the equipment must be strictly followed to ensure the safety of the operating personnel as
well as the instrument.
If all the equipment is not handled in a manner specified by the manufacturer, it might impair the
protection provided by the equipment .
=> Read complete instructions prior to installation and operation of the unit.
WARNING : Risk of electric shock.
3) Cable used for connection to power source, must have a cross section of 1mm or greater. These wires
should have insulations capacity made of at least 1.5kV.
2) To reduce electro magnetic interference, use wire with adequate rating and twists of the same of
equal size shall be made with shortest connection.
4) When extending the thermocouple lead wires, always use thermocouple compensation wires for wiring
for the RTD type, use a wiring material with a small lead resistance (5Ω max per line)and no resistance
differentials among three wires should be present.
1) To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the
wiring arrangement. Do not touch the terminals while power is being supplied.
5) A better anti-noise effect can be expected by using standard power supply cable for
the instrument.
1) This equipment, being built-in-type, normally becomes a part of main control panel and in such case the
terminals do not remain accessible to the end user after installation and internal wiring.
2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product
or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
3) Circuit breaker or mains switch must be installed between power source and supply terminal to
facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be
installed at convenient place normally accessible to the operator.
4) Use and store the instrument within the specified ambient temperature and humidity ranges as
mentioned in this manual.
Warning Guidelines
Installation Guidelines
Mechanical Installation
Maintenance
Safety Precautions
1) Prepare the panel cutout with proper dimensions as show above.
2) Fit the unit into the panel with the help of clamp given.
3) The equipment in its installed state must not come in close proximity to any heating source,
caustic vapors, oils steam, or other unwanted process by products.
4) Use the specified size of crimp terminal (M3.5 screws) to wire the terminal block. Tightening the
screws on the terminal block using the tightening torque of the range of 1.2 N.m.
5) Do not connect anything to unused terminals.
1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any
other cleaning agent.
3) Fusible resistor must not be replaced by operator.
2
A
B
C
D
MODEL A
96mm 96mm 92mm 92mm 3mm 50mm
BC
D E
F
DIMENSIONS
136mm - 5.35 inches
120mm - 4.72 inches
E
F
Product improvement and upgrade is a constant procedure. So for more updated operating information and Support,
Please contact our Helpline: +91-9978991474/76/82 or Email at service Ver: 1809@multispanindia.com