LG LS-D1832CN Installation guide

Category
Split-system air conditioners
Type
Installation guide
P/No.: 3828A90005G
ENGLISH
ITALIANO
Le mod e "Froid et
chauffage" est
uipÈ d'un
ROOM AIR CONDITIONERS
INSTALLATION INSTRUCTIONS
• Please read this instruction sheet completely before installing the product.
When the power cord is wanted to replace, replacement work shall be
performed by authorized personnel only.
Installation work must be performed in accordance with national wiring
standards by authorized personnel only.
1. Type "A" screw
3. Type "B" screw
4. Holder Remote-Controller
2. Installation Plate
more than 5cm
1cm
5. Copper pipe (Liquid side)
6. Copper pipe (Gas side)
7. Power supply cord(power connecting cable)
8. Connecting cable(except 18K cooling only model)
more than
10cm
more than
10cm
more than
70cm
Cooling & Heating Model has
included Drain Elbow
more than
5cm
2 ENGLISH
OUT-LINE OF INSTALLATION
Installation works
Installation Parts
Required Tools
2. Installation of indoor, outdoor Unit
1.The following should always be observed for safety
...................................................
3
1) Selection of the best location
...
4
2) Indoor unit Installation
..............
5
• Installation plate
• Four type "A" screws
• Connecting cable
• Level
• Screw driver
• Electric drill
• Hole core drill(ø70mm)
3. Piping and drainage of indoor unit
1) Preparation of pipings
............
6
2) Connection of pipings ......7~11
• For right rear piping
• For the left piping
• Pipes: Gas side
.............
1
/2",
5
/8"
Liquid side
.........
1
/4",
3
/8"
(different depending on model No.)
• Insulated drain hose
• Insulation materials
• Flaring tools set
• Specified torque wrenches
1.8 kg
.
m, 4.2 kg
.
m, 5.5 kg
.
m,
6.6 kg
.
m
(different depending on model No.)
Spanner
.........................
Half union
4. Connecting pipings and the cable to outdoor unit
1) Connection of pipings to the
outdoor unit
............................
12
2) Connection of the cable
.........
12
• Additional drain hose
(Outer Dia
.....................
15.5 mm)
• Specified torque wrenches
1.8 kg
.
m, 4.2 kg
.
m, 5.5 kg
.
m,
6.6 kg
.
m
(different depending on model No.)
5. Checking the drainage and connecting the cable to Indoor unit
1) Checking the drainage
..........
14
2) Connecting of the cable
.........
15
3) Forming the pipings
...............
16
• A glass of water
• Screw driver
6. Air Purging
7. Maximum length of pipe and freon extra change
...........................................................
19
1) Air Purging
............................
17
2) Checking a gas-leakage
........
18
• Hexagonal wrench (4mm)
• Gas-leak detector
8. Test running
1) Connection of power supply
...............................................
20
2) Evaluation performance
..............................................
20
• Tow type "B" screws • Owner's manual
• Thermometer
ENGLISH 3
ENGLISH
1. The following should be always be observed
for safety
• Please report to or take consent by the supply authority before connection to the system.
• Be sure to read "THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY" before installing
the air conditioner.
• Be sure to observe the cautions specified here as they include important items related to safety.
• The indications and meanings are as follows.
• After reading this manual, be sure to keep it together with the instruction manual in a handy place on the
customer's site.
Could lead to death, serious injury, etc.
Do not install it yourself (customer).
Perform the installation securely referring to the
installation manual.
Install the unit securely in a place which canbear the
weight ofthe unit.
Perform electrical work according tothe installation
manual andbe sure touse anexclusive circuit.
Attach the electrical part cover to the indoor unit andthe
service panel tothe outdoor unit securely.
Be sure touse the part provided orspecified parts for
theinstallation work.
Check that the refrigerant gas due not leak after
installation is completed.
Perform grounding
Do not installthe unit in a place where aninflammable
gasleaks.
Perform the drainage/piping worksecurely according to
theinstallationmanual.
Usethe specified wiresto connect the indoor and
outdoor units securelyand attach the wires firmly to the
terminal board connecting sections sothe stress ofthe
wires is not applied tothe sections.
Incomplete installation could cause injury due to fire, electric shock, the
unit falling or a leakage of water. Consult the dealer from whom you
purchased theunitorspecialinstaller.
• Incomplete installation could cause a personal injury due to fire,
electric shock, the unit falling or a leakage of water.
• When installed in an insufficient strong place, the unit could fall
causing injured.
• Incomplete connecting and fixing could cause fire.
If the capacity of the power circuit is insufficient or there is incomplete
electrical work, it could result in a fire or an electric shock.
The use of defective parts could cause an injury or leakage of water
due to a fire, electric shock, the unit falling, etc.
If gas leaks and accumulates in the area surrounding the unit, it could
cause an explosion.
• If there is a defect in the drainage/piping work, water could
drop from the unit and household goods could be wet and
damaged.
Do not connect the ground wire to a gas pipe, water pipe arrester or
telephone groundwire. Defectivegroundingcouldcausean electricshock.
If the electrical part cover if the indoor unit and/or the service panel if
the outdoor unit are not attached securely, it could result in a fire or
electric shock due to dust, water, etc.
Could lead toseriousinjury in particular environmentswhenoperatedincorrectly.
WARNING
WARNING
CAUTION
CAUTION
4 ENGLISH
2. Installation of Indoor, Outdoor unit
A
B
1) Selection of the best location
1. Indoor unit
2. Outdoor unit
3.Piping length and the elevation
There should not be any heat source or
steam near the unit.
• There should not be any obstacles to prevent
the air circulation.
• A place where air circulation in the room will
be good.
• A place where drainage can be easily
obtained.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from
the wall, ceiling, fence, or other obstacles.
• If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful
that heat radiation from the condenser is not
restricted.
• There should not be any animals or plants
which could be affected by hot air
discharged.
• Ensure the spaces indicated by arrows from
the wall, ceiling, fence, or other obstacles.
More than
5 cm
More than 5 cm
More than
5 cm
More than eye-level
More than 10 cm
More than 10 cm
More than 70 cm
Indoor unit
Outdoor
unit
Pipe Size
MODEL
GAS LIQUID
Max.
length
A (m)
Max.
Elevation
B (m)
18K 1/2" 1/4" 30 15
24K 5/8" 1/4" 30 15
ENGLISH 5
ENGLISH
A,B
A,B,C
C
D
D
5-7mm
A,B,D
C
A
B,D
C
ø70mm
2) Indoor Unit Installation
The mounting wall should be strong and solid
enough to protect it from the vibration.
1. Mount the installation plate on the wall
with four Type "A" screws.
(if mounting the unit on the concrete wall,
consider using anchor bolts.)
• Always mount the Installation plate
horizontally by aligning the marking-off line
by means of the thread and a level.
2. Drill the piping hole with 70mm dia.
holecore drill.
• For right rear piping and left rear piping,
draw a line in the direction of the arrow
marked "D". The meeting point of the two
lines is the center of the hole.
• Drill the piping hole with a ø70mm hole
core drill. Drill the piping hole at either the
right or the left with the hole slightly slanted
to the outdoor side.
Type "A" screw
Installation Plate
marking-off line
Thread
Weight
The lower left and right side of Installation
Plate
Left rear piping
Right rear piping
Indoor
Hole Center
Installation plate
Outdoor
WALL
6 ENGLISH
3. Piping and Drainage of Indoor Unit
1) Preperation of Pipings
1. Cut the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor
and the outdoor unit.
• Cut the pipes a little longer than measured
distance.
• Cut the cable 1.5m longer than the length of
the pipe.
2. Remove burrs.
• Remove burrs from cut edges of pipes.
Turn the pipe end toward down to avoid the
metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas
leakage.
3. Flaring the pipes.
• Insert the flare nuts, mounted on the
connection ports of both indoor and outdoor
unit, onto the copper pipes. Some gas may
leak, when the flare nuts are removed from
the indoor unit, as some gas is charged to
prevent the inside of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare
tool about 0.5~1.0mm higher. (See
illustration)
• Flare the pipe ends.
4. Tape the flaring portion to protect it from
the dust or damages.
"A"
When properly flared, the internal surface of the
flare will evenly shine and be of even thickness.
After the flare part comes into contact with the
connectors, carefully check the flare finish.
Pipecutter
Slanted
Rough
Pipe
Point down
Reamer
Handle
"A";ø15.88 mm (5/8") 0~1.0 mm
ø12.7 mm (1/2")
0~0.5 mm
ø9.52 mm (3/8")
0~0.5 mm
ø6.35 mm (1/4")
0~0.5 mm
Cone
Red arrow mark
Clamp handle
Yoke
Bar
Bar
Copper pipe
= Improper flaring =
Inclined
Surface
damaged
Cracked
Uneven
thickness
ENGLISH 7
ENGLISH
2) Connection of Pipings
1. Remove the indoor tubing with Drain hose
from the hole
• Remove tubing holder and pull the tubing out
of the chassis.
2. Replace the tubing holder into original
position.
For right rear piping
3. Route the tubing and the drain hose
straight backwards.
4. Insert the connecting cable into the indoor
unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
• Connecting cable
5. Tape the tubing, drain hose and the
connecting cable. Be sure that drain hose
locates at the lowest side of the bundle.
Locating at the upper side can be a reason
that drain water overflows drain pan inside
the unit.
Pull
Press
To remove the holder,
press the bottom of
chassis near the holder
upward and pull the tab
out of its hole.
Tubing holder
Connecting
cable
Gas side piping
Liquid side piping
Drain hose
Taping
Indoor/Outdoor
Connecting cable
18K
Cooling Model
Heat Pump Model
24K
8 ENGLISH
6. Indoor unit installation
• Hook the indoor unit onto the upper portion
of installation plate. (Engage the two hooks
of the rear top of the indoor unit with the
upper edge of the installation plate.)
Ensure the hooks are properly seated on the
installation plate by moving it left and right.
7. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque
wrench until the wrench clicks.
When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
8. Wrap the insulation material around the
connecting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the
picture on page 7 for inserting it
into the indoor unit and refixing
the tubing holder easily.
Connecting
cable
Drain hose
Press the lower left and right side of the unit
against the Installation Plate until the hooks
engage with their slots (sound click).
Flare nut
Pipings
Torque wrench
Spanner
Indoor unit tubing
Plastic Bands
Insulation material
Wrap the insulation material around the
connecting portion.
Pipe Size Torque
Liquid Side(1/4") 1.8kg
.
m
Liquid Side(3/8") 4.2kg
.
m
Gas Side(1/2") 5.5kg
.
m
Gas Side(5/8") 6.6kg
.
m
ENGLISH 9
ENGLISH
For the left pipings
3. Route the indoor tubing with the drain hose
to the piping hole as desired position.
4. Insert the pipings, power supply cord and
connecting cable into the piping hole.
5. Insert the connecting cable into the indoor
unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
6. Tape the tubing, drain hose and the
connecting cable.
• Connecting cable
IndoorOutdoor
Drain pipe
Connecting cable
Connecting piping
Pull
To remove theholder,
press the bottomof
chassis near theholder
upward and pullthe tab
out of its hole.
Tubing holder
Press
Indoor/outdoor
connecting cable
Connecting
cable
Taping
Gas side piping
Liquid side piping
Drain hose
18K
Cooling Model
Heat Pump Model
24K
10 ENGLISH
7. Indoor unit installation
• Hook the indoor unit onto the upper portion
of installation plate. (Engage the two hooks
of the rear top of the indoor unit with the
upper edge of the installation plate.)
Ensure the hooks are properly seated on the
installation plate by moving it in left and right.
8. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque
wrench until the wrench clicks.
When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
Flare nut
Pipings
Torque wrench
Spanner
Indoor unit tubing
Plastic Bands
Insulation material
Wrap the insulation material around the
connecting portion.
9. Wrap the insulation material around the
connecting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the right
upper picture for inserting it into
the indoor unit and refixing the
tubing holder easily.
Connecting
cable
Drain hose
Press the lower left and right side of the unit
against the Installation Plate until the hooks
engage with their slots(sound click).
Pipe Size Torque
Liquid Side(1/4") 1.8kg
.
m
Liquid Side(3/8") 4.2kg
.
m
Gas Side(1/2") 5.5kg
.
m
Gas Side(5/8") 6.6kg
.
m
ENGLISH 11
ENGLISH
10. Set the pipings and the connecting cable
to the back of the chassis with the tubing
holder
• Hook the edge of tubing holder to tap on
chassis and push the bottom of tubing holder
to be engaged in the bottom of chassis.
11. Indoor unit installation
• Hook the indoor unit onto the upper portion
of installation plate. (Engage the two hooks
of the rear top of the indoor unit with the
upper edge of the installation plate.)
Ensure the hooks are properly seated on the
installation plate by moving it in left and right.
Piping
Taping
Drain hose
Tubing holder
Hook
Push
Connecting
cable
Drain hose
Press the lower left and right side of the unit
against the Installation Plate until the lower hooks
engage with their slots (sound click).
12 ENGLISH
4. Connecting Pipings and the cable to Outdoor unit
1) Connecting the pipings to the
Outdoor unit
1. Align the center of the pipings and
sufficiently tighten the flare nut with
fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
Outdoor unit
Gas side piping
(Bigger Dia.)
Liquid side piping
(Smaller Dia.)
Torque wrench
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could give rise to
burn-out of the wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to
the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
Pipe Size Torque
Liquid Side(1/4") 1.8kg
.
m
Liquid Side(3/8") 4.2kg
.
m
Gas Side(1/2") 5.5kg
.
m
Gas Side(5/8") 6.6kg
.
m
1(L)
1(L)
1(L)
2(N)
2(N)
2(N)
3
3
3
4
5
1(L)
2(N)
3
4
5
1(L)
2(N)
ENGLISH 13
ENGLISH
2)
Connection of the cable
1. Remove the cover control from the unit by
loosening the screw.
Connect the wires to the terminals on the
control board individually as the following.
Outdoor unit
Terminal block
Connecting
cable
Power cord
(powerconnecting cable)
Cover control
Over 5mm
Power supply
2. Secure the cable onto the control board with the
holder (clamper).
3. Refix the cover control to the original position with
the screw.
4. Use a recongnized circuit breaker 20A between the
power source and the unit. A disconnection device
to adequately disconnect all supply lines must be
fitted.
Terminalsonthe outdoor unit
Terminalsonthe outdoor unit
Terminalsonthe outdoor unit
• 18K cooling only model
• 18K heat pump model
• 24K models
BROWN BLUE GN/YL BROWN
BROWN BLUE GN/YL BROWN
RED BLACK WHITE
RED BLACK WHITE
Terminalsonthe indoor unit
Terminalsonthe indoor unit
Terminalsonthe indoor unit
CAUTION
Ø10.0mm
(18K : Ø8.0mm)
Ø7.0mm
(18K : Ø5.0mm)
Ø8.0mm
The power cord connected to the
indoor unit should be complied with the
following specifications
(Type H05VV-F(Indoor), H07RN-F(Outdoor)
approved by HARorSAA).
The connecting cable connected to
the indoor and outdoor unit should be
complied with the following
specifications
(Type H07RN-Fapproved by HAR orSAA).
The power connecting cable
(18K)connected to the indoor and
outdoor unit should be complied with
the following specifications
(Type H07RN-F approved by HAR orSAA).
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
2
(18K : 1.5mm
2
)
NORMAL
CROSS-SECTIONAL
AREA 1.5mm
2
BROWN BLUE GN/YL
BROWN BLUE GN/YL
14 ENGLISH
1) Checking the Drainage
1. Remove the Grille from the cabinet.
• Set the up-and-down air direction louver to
open position (horizontally) by finger
pressure.
• Remove 4 screws.
• To remove the Grille, pull lower the left and
right side of the grille toward you (slightly
tilted) and lift it straight upward (Four tabs on
the top inside edge of chassis are clear of
their slots).
2. Check the drainage.
• Pour a glass of water on the evaporator.
• Ensure if water flows drain hose of indoor
unit without any leakage.
5. Checking the Drainage and Connecting the cable to
Indoor unit
Grille
Chassis
Screw(3places)
ENGLISH 15
ENGLISH
2) Connect the cable to the indoor
unit
1. Connect the wires to the terminals on
the control board individually according
to the outdoor unit connection.
• Ensure that the color of the wires of
outdoor unit and the terminal No. are the
same as those of indoor unit respectively.
18K heat pump model
2. Attach the Grille onto the cabinet.
• Grasp lower the left and right side of the
Grille and engage four tabs on the top
inside edge of the chassis.
• Press the Grille toward the chassis until it
will be back into place.
24K models
1(L)
1(L)
1(L)
2(N)
2(N)
2(N)
3
3
3
4
5
1(L)
2(N)
3
4
5
1(L)
2(N)
Power supply
Terminalsonthe outdoor unit
Terminalsonthe outdoor unit
Terminalsonthe outdoor unit
• 18K cooling only model
• 18K heat pump model
• 24K models
BROWN BLUE GN/YL BROWN
BROWN BLUE GN/YL BROWN
RED BLACK WHITE
RED BLACK WHITE
Terminalsonthe indoor unit
Terminals on the indoor unit
Terminalsonthe indoor unit
BROWN BLUE GN/YL
BROWN BLUE GN/YL
16 ENGLISH
3) Form the pipings
1. Wrap the connecting portion of indoor unit
with the Insulation material and secure it
with two Plastic Bands.
(for the right pipings)
• If you want to connect an additional drain
hose, the end of the drain-outlet should keep
distance from the ground.(Do not dip it into
water, and fix it on the wall to avoid swinging
in the wind.)
• Connecting cable
2. Tape the Pipings, drain hose and
Connecting Cable from down to up.
3. Form the pipings gathered by taping along
the exterior wall and fix it onto the wall by
saddle or equivalent.
2. Tape the Pipings and Connecting cable
from down to up.
3. Form the pipings gathered by taping along
the exterior wall, make the Trap to be
required to prevent water from entering
into the room.
4. Fix the pipings onto the wall by saddle or
equivalent.
In case of the Outdoor unit being installed
below position of the Indoor unit.
In case of the Outdoor unit being installed
above position of the Indoor unit.
Seal a small opening
around the pipings with
gum type sealer.
Taping
Pipings
Connectingcable
Powersupplycord
Plastic
band
Trap is required to prevent water from entering
into electrical parts.
Seal a small opening
around the pipings
with gum type sealer.
Trap
Drain hose
18K
Cooling Model
Heat Pump Model
24K
ENGLISH 17
ENGLISH
5. To open 2-way valve again, turn the
valve stem counter-clockwise until it
stops.
Re-tighten the connecting portion with torque
wrenches.
No leakage found
Ieakage found
Outdoor unit
Cover control
Gasside
To indoor unit
Liquid side
Cap
Hexagonal
wrench
Service port cap
3-way valve
(Close)
2-way valve
(Open)
leakage ceased
leakage persists
Repair
leakage ceased
6. To purge the air, push the pin on the service
port of 3-way valve for three seconds with a
hexagonal wrench and set it free for one
minute. Repeat this three times.
Result
7. Set the both liquid and gas side valves to
open position with the Hexagonal wrench
for the unit operation.
6. Air Purging
1) Air purging
The air which contains moisture remaining in the
refrigeration cycle may cause a malfunction on
the compressor.
1. Remove the caps from the 2-way and 3-way
valves.
2. Remove the service-port cap from the
3-way valve.
3. Turn the valve stem of liquid side valve
counter-clockwise approx. 90 and hold it
there for ten seconds, then close it.
4. Check a gas-leakage of the connecting
portion of the pipings.
CAUTION: Do not leak the gas in the air
during air purging. Use vacuum
pump as far as possible.
18 ENGLISH
2) Checking a gas leakage
1. Connect the manifold gauge to the service port of 3-way valve.
Measure the pressure.
2. Keep it for 5-10 minutes.
Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
NOTE:
The additional gas for air purping has been charged in the outdoor unit.
However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder
and the charge set will be needed.
CAUTION : Do not leak the gas in the air during air purging. Use vacuum pump as far as
possible.
Indoor unit
Liquid side
Closed
Outdoor unit
Gas side
Closed
CLOSE
CLOSE
ENGLISH 19
ENGLISH
7. Maximum Length of Pipe and Freon Extra Charge
In case more than 5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Oil trap should be installed every 5~7 meters.
A
B
A
B
CAUTION
7K, 9K 3/8" 1/4" 5 7 15 20
12K 1/2" 1/4" 5 7 15 20
18K 1/2" 1/4" 5 15 30 20
24K 5/8" 1/4" 5 15 30 30
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Oil trap
20 ENGLISH
Discharge air
(Cooling)
2) Evaluation of the performance
1. Measure the temperature of the intake and
discharge air.
2. Ensure the difference between the intake
temperature and the discharge one is more
than 8 C (Cooling) or reversely (Heating).
8. Test running
RESET
RESET
RESET
Settlement of Outdoor Unit
Anchor the outdoor unit with a bolt and nut
(ø10cm) tightly and horizontally on a
concrete or rigid mount.
When installing on the wall, roof or rooftop,
anchor the mounting base securely with a
nail or wire assuming the influence of wind
and earthquake.
In the case when the vibration of the unit is
conveyed to the house, settle the unit with an
anti-vibration rubber.
Bolt
Tubing connection
1) Connection of power supply
1. Connect the power supply cord to the
independent power supply.
Circuitbreaker is required.
2. Prepare the remote control.
Insert two batteries provided.
Remove the battery cover from the remote
controller.
Slide the cover according to the arrow
direction.
Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or
equivalent.)
Be sure that the (+) and (-) directions are
correct.
Be sure that both batteries are new.
Re-attach the cover.
Slide it back into position.
3. Operate the unit for fifteen minutes or more.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

LG LS-D1832CN Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI