CET LAM00 Owner's manual

  • Hello! I've reviewed the provided datasheet for the CET LAM 00 visualized ammeter. This document details the device's features, including its set point, delay, and hysteresis regulation capabilities, as well as its technical specifications. I'm ready to answer your questions about the ammeter and its functionality.
  • What is the nominal range of the TA?
    What are the available power supply options?
    What is the working temperature range?
• Set Point Regulation Trimmer
• Delay Regulation Trimmer
• Hysteresis Regulation Trimmer
• Multiscale Input from TA
• Timing Commend of Inhibit
• Possibility to Memorize the Intervention
• Connection with Removable Terminals
• DIN 48 x 96 execution
• Recessed assembly
• Special retaining brackets
• MONO POWER SUPPLY
• ABSORPTION
ANALOG INPUT
• NOMINAL RANGE OF THE TA (IN)
• CONTINUOS OVERLOAD
• OVERLOAD FOR 10’’
• OVERLOAD FOR 1’’
DIGITAL INPUTS
• RESET
• INHIBIT
OUTPUTS
• 1 RELAYS
VISUALIZATION AND INTERVENTIONS
• DISPLAY
• PRIMARY TA SELECTION
• MAX FULL SCALE
• READ PRECISION
• LINEARITY
• STABILITY
• WORKING TEMPERATURE RANGE
• CLIMATIC CONDITIONS
• INTERVENTION SET POINTS REGULATION
(SET. 1)
• INTERVENTION DELAY REGULATION
(DELAY 1).
• HYSTERESIS REGULATION
(HIST. 1)
• INHIBIT TIME REGULATION
THE LAM00 VISUALIZED AMMETER
CONTROLS THE CURRENT ABSORPTION
OF AN ELECTRIC SYSTEM AND IT
INTERVENES WHEN THE CONTROLLED
CURRENT IS OVER THE SETTED SET POINT
VALUE
TECHNICAL FEATURES
: 24 - 110 - 220 Vac ( 50 / 60 Hz )
: 3 VA
: 5 A
: 1,2 (IN)
: 1,5 (IN)
: 2 (IN)
: suitable for electromechanical contacts
: suitable for electromechanical contacts
: 5 A 250 V on resistive load
: 3 digits, high 14 mm
: by switches on the rear side of the device
50/5 100/5 200/5 400/5 500/5 600/5 800/5 1000/5
: 999
: +/- 0,5% +/-1 in all the range
: +/-0,5%
: 200 ppm ºC
: -5 ºC +50 ºC
: U.R. 95% a 40 ºC without condensate
: min. max of the selected TA (by frontal trimmers)
: 0 - 10 sec (by frontal trimmer)
: 3% - 50% ( of the value of the setted set point ) using the
frontal trimmers
: 0 - 30 sec. ( by the trimmer on the side of the device )
PAG. 1LAM 73
LAM Ammeter Relay
1
INTERV.
HYST1 DELAY1
SELECT
SET 1
SET 1
CET s.r.l.
To have a correct working of the instrument occurs to program
the value of the primary of the TA transformer using the fitting
microswitches positioned on the backside of the device.
Now the visualization corresponds to the same value of the
input current. Then adjust the set point value, the delay timing,
the Hysteresis and the time of Inhibit.
When the current absorption is over the setted set point value
there is the intervention with the commutation of the relay
contacts. The intervention will be in function of the
programmed delay timings; the restore will be in function of the
programmed hysteresis. To excluded the memorization of the
intervention it is necessary to make a bridge between the
inputs 12 - 14
PROGRAMMABLE PARAMETERSMAIN FEATURES
VISUALIZED AMMETER
WITH SET POINT
Type:
LAM 00
WIRING CONNECTIONS
PAG. 2 LAM 73
FRONT 10 Max.
SIDE
REMOVABLE
TERMINAL
139
115 15 9
44 X 92
96
48
L A M A m m e t e r R e l a y
INHIBIT TIME
REGULATION
RETAINING
BRACKETS
DRILL TEMPLATEBACK
93
45
44
92
1 83 5 74 62
16 914 12 1013 1115
T A S e l e c t i o n
OVERALL DIMENSION ( mm )
50
100
200
400
500
600
800
1000
TA INPUT
SELECTION
POWER
1 2 3 4 5 6 7 8
16 15 14 13 12 11 10 9
Relay Reset
Inhibit Interv.1
TA
I / 5
L
FUNCTION DIAGRAMS
INTERVENTION DELAYI N H I B I Tt
C H
A P
Power Supply
Set Point
Hysteresis
Absorption
Relay
Inhibit
CET s.r.l.
CET s.r.l.
SS 211 Km 53,550
28071 Borgolavezzaro - No - ITALY
Tel : ++39 321-885180/885301/885807
Fax : ++39 321-885560
Agent :
LAM 00
14-12= BRIDGE TO EXCLUDE THE
INTERVENTION MEMORIZATION
THIS DIAGRAM IS VALID ONLY ON
WORKING WITH THE TWO SET POINTS
COMPLETELY INDIPENDENT.
/