EM-5492-U0 Rev.5 P. 1 / 3
INSTALLATION BASE
(4 positions, M3.5 screw terminal / M3.5 screw terminal)
MODEL
M8BS-4U0
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Installation base ..................................................................(1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ POWER INPUT RATINGS
Operational range & power consumption: Check the power
rating for the unit on the specification label.
•Rating 85 –132V AC: 85 – 132V, 47 –63 Hz, ≥130VA
•Rating 170 –264V AC: 170 – 264V, 47 –63 Hz, ≥130VA
•Rating 24V DC: Rating ±10%, ≥0.7A
■ GENERAL PRECAUTIONS
Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
■ ENVIRONMENT
•When heavy dust or metal particles are present in the
air, install the installation base inside proper housing and
ventilate it.
•Do not install the base where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
•Environmental temperature must be within 0 to 55°C or
32 to 131°F (0 to50°C or 32 to 122°F for AC power) with
relative humidity within 30 to 90% RH in order to ensure
adequate life span and operation.
•Be sure that the ventilation slits are not covered with ca-
bles, etc.
■ WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
COMPONENT IDENTIFICATION
■ REAR VIEW
Specifications
MOUNTING REQUIREMENTS mm (inch)
160 (6.30)
50 (1.97)
4–M5 SCREW