Tripp Lite PDUMV30HVNET Owner's manual

Category
Power distribution units (PDUs)
Type
Owner's manual

This manual is also suitable for

1
Owner’s Manual
Monitored Rack PDU
Switched Rack PDU
Zero U (Vertical) Format
AGPD7897 (208/230V 16 Amp Models) • AGPD7898 (208V 24 Amp Models)
AG00CA (200-240V 32A models)
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2013 Tripp Lite. All rights reserved.
Important Safety Instructions 2
Monitored Rack PDU Features 2
Switched Rack PDU Features 3
Installation 3
Features 8
Configuration and Operation 10
Warranty and Warranty Registration 11
Español 13
Français 25
Русский 37
Warranty
Registration
Register online today for a
chance to win a FREE Tripp Lite
product! www.tripplite.com/warranty
13-11-194-933093.indb 1 12/5/2013 5:21:52 PM
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed
during the installation, operation, and storage of this product. Failure to
heed these instructions and warnings will void the product warranty.
Important Safety Instructions
Monitored Rack PDU Features
• ThePDUprovidesconvenientmultipleoutlets,butitDOESNOTprovidesurgeorlinenoise
protection for connected equipment.
• ThePDUisdesignedforindooruseonlyinacontrolledenvironmentisolatedfromexcess
moisture,temperatureextremes,conductivecontaminants,dustordirectsunlight.
• DonotconnectthePDUtoanungroundedoutletortoextensioncordsoradaptersthat
eliminate the connection to ground.
• ThepowerrequirementforeachitemofequipmentconnectedtothePDUmustnotexceed
the individual outlet’s load rating.
• ThetotalpowerrequirementforequipmentconnectedtothePDUmustnotexceedthe
maximumloadratingforthePDU.
• DonotdrillintoorattempttoopenanypartofthePDUhousing.Therearenouser-
serviceablepartsinside.
• DonotattempttomodifythePDU,includingitsinputplugsandpowercables.
• DonotattempttousethePDUifanypartofitisdamaged.
• DonotattempttomountthePDUtoaninsecureorunstablesurface.
• Neverattempttoinstallelectricalequipmentduringathunderstorm.
• Useofthisequipmentinlifesupportapplicationswherefailureofthisequipmentcan
reasonablybeexpectedtocausethefailureofthelifesupportequipmentortosignificantly
affectitssafetyoreffectivenessisnotrecommended.Donotusethisequipmentinthe
presenceofaflammableanestheticmixturewithair,oxygenornitrousoxide.
•InstallinaccordancewithNationalElectricalCodes.Besuretousetheproperovercurrent
protectionfortheinstallation,inaccordancewiththeplugrating.
•Theelectricalsocketssupplyingpowertotheequipmentshallbeinstallednearthe
equipmentandbeeasilyaccessible.
•Networkinterfaceenablesremotepowermonitoringandeventnotification
•Digitalampmeterforon-siteloadmonitoring
•CentralizedmanagementofhundredsofPDUsandenvironmentalsensorswithTrippLite’s
freePowerAlertNetworkManagementSystem
•OptionalENVIROSENSEaccessoryallowsmonitoringofnetworkambienttemperature,
humidity and up to three dry contacts
•Toollessbutton-mountinstallationinTrippLiteSmartRack™andmanythird-partyenclosures
13-11-194-933093.indb 2 12/5/2013 5:21:53 PM
3
Switched Rack PDU Features
•Networkinterfaceenablesremotepowermonitoringandindividualoutletcontrol
•Individuallycontrollableoutletsallowremoterebootingoflocked-upnetworkdevices
•Digitalampmeterforon-siteloadmonitoring
•CentralizedmanagementofhundredsofPDUsandenvironmentalsensorswithTrippLite’s
freePowerAlertNetworkManagementSystem
•OptionalENVIROSENSEaccessoryallowsmonitoringofnetworkambienttemperature,
humidity and up to three dry contacts
•Toollessbutton-mountinstallationinTrippLiteSmartRackandmanythird-partyenclosures
Mounting the PDU
Note: The illustrations may differ somewhat from your PDU model. Regardless of configuration, the user must
determine the fitness of hardware and procedures before mounting. The PDU and included hardware are
designed for common rack and rack enclosure types and may not be appropriate for all applications. Exact
mounting configurations may vary. Screws for attaching the mounting brackets and cord retention shelf to the
PDU are included. Use only the screws supplied by the manufacturer, or their exact equivalent (#6-32, ¼"
flat head).
IfinstallingthePDUinarackthathasbutton-mountslots,youonlyneedtoperformstep
1-1
.
Ifyourrackenclosuredoesnothavebutton-mountslots,proceedtostep
1-2
.
Installation
1-1
ToinstallthePDUinarackequipped
withbutton-mountslots,insertthe
mountingbuttonsontherearofthe
PDUintothebutton-mountslotson
therackandslidethePDUdownuntil
themountingbuttonsengagethe
narrowsectionoftheofthebutton-
mount slots.
Note: To install the PDU with its outlets
facing the rear of the rack, use the
included PDUMVROTATEBRKT accessory.
This V-shaped bracket provides a mounting
button on one leg of the V and a button-
mount slot on the other, effectively
repositioning the mounting buttons. See
Features section for image.
1-2
Attachthemountingbracketstothe
PDU.
1-3
(Optional)Attachthecordretention
bracket(s)tothePDU.
1-4
AttachthePDUtoaverticalrailin
yourrackorrackenclosure.(Usethe
mounting hardware that came with
yourrackorrackenclosuretoattach
themountingbracketstotherail.)
1-2
1-1
1-3 1-4
13-11-194-933093.indb 3 12/5/2013 5:21:54 PM
4
Connecting the PDU
2-1
(ModelswithIECpowerinletor3-pole
IEC309plugonly.)Selectmodelshave
adetachablepowercord.Attachthe
includedpowercordtothePDUby
insertingtheIECconnector
A
of the
powercordintotheIECpowerinlet
B
locatedneartheendofthePDU.Use
theincludedbracket
C
to secure the
power cord connection.
Note: Optionally, a user-supplied power cord
can be attached to the PDU by connecting it
to the IEC inlet. Do not attempt to attach a
user-supplied power cord unless it is certified
to be compatible with the input power source
that will be used by the PDU.
2-2
(Optional-modelswithinputplug
adapteronly.)Selectmodelsincludean
input plug adapter that converts the
twist-lockinputplugtoastraight-blade
input plug. Attach the input plug adapter
A
to the input plug
B
if you wish to
plugthePDUintoacompatiblestraight-
bladeoutlet.
2-3
Connecttheinputplugtoacompatible
ACpoweroutlet.IfthePDUdoesnot
haveacircuitbreaker,itshouldbe
providedwithabranch-ratedover-
current protection device that matches
theratedamperageofthePDU.
Note: The AC power source should not share
a circuit with a heavy electrical load.
2-4
(Option1-selectmodelsonly.)Ifyou
attachedthecordretentionbracket(s),
tie each equipment power cord to the
retentionbracket.Attacheachcordto
theretentionshelfbyloopingthecord
and securing it with one of the included
cableties
A
.Makesurethateachcord
canbeunpluggedfromthePDUwithout
removingthecabletie.
(Option2)UsetheincludedC14and
C20 plastic sleeves to secure plugs to
receptacles. Attach the sleeve to the
plug,makingsurethatthepulltabs
B
remain outside the plug and that the fit
issecure.Tounplugequipmentproperly,
usethepulltabstoremovetheplug
and sleeve from the receptacle.
Installation continued
2-1
2-2
2-3
A
C
B
A
B
2-4
B
A
13-11-194-933093.indb 4 12/5/2013 5:21:56 PM
5
Installation continued
2-5
Connect your equipment's input plugs
A
to the outlets
B
ofthePDU.TheLED
C
near each outlet (Switched Models
Only) illuminates when the outlet is
readytodistributeliveACpower.The
digital load meter
D
displays the total
connected equipment load in amps.
(Selectmodelsprovideadditionalload
data.SeetheFeatures section for
moreinformation.)
Note: In order to minimize interference among
connected devices, connect each device to
the nearest PDU outlet and coil excess power
cord length.
Networking the PDU
Note: The MAC address of the PDU (a 12-digit string in this format: 000667xxxxxx) is printed on a label
attached to the PDU enclosure.
Ifyournetwork'sDHCPserverwillassignadynamicIPaddresstothePDUautomatically,goto
Step
3-1
.IfyouwillassignastaticIPaddresstothePDUmanually,gotoStep
4-1
.Ifyouare
uncertainwhichmethodtouse,contactyournetworkadministratorforassistancebefore
continuing the installation process.
Dynamic IP Address Assignment
3-1
Connect PDU to Network: While the
PDUispowered,connectastandard
EthernetpatchcabletotheRJ-45
Ethernet port
A
onthePDU.
Note: This port is not compatible with PoE
(Power over Ethernet) applications. The PDU
will attempt to obtain an IP address via DHCP.
This may take as long as several minutes,
depending on your network environment.
3-2
Discover IP Address:ContactyournetworkadministratortodeterminewhichdynamicIP
addresshasbeenassignedtothePDUbytheDHCPserver.ThePDUcanbeidentifiedon
theDHCPserverbyreferringtoitsMACaddress.(TheMACaddressisa12-digitstringin
thisformat:000667xxxxxx.RefertotheMACaddresslabelattachedtothePDU.)Youmay
wishtorequestalong-termleaseperiodfortheIPaddress,dependingonyourapplication.
AfteryouhavediscoveredtheIPaddress,skipSteps
4-1
through
4-6
and proceed
directlytoStep
5-1
.
Static IP Address Assignment
4-1
Determine IP Information:BeforeassigningastaticIPaddress,you'llneedtoknowthe
IPaddress,gatewayaddressandsubnetmask.Ifyoudonothavethisinformation,contact
yournetworkadministratorforassistance.
(Will vary by model.)
2-5
A
D
24 23 22 21
20
19 18 17 16 15
14
13
ENVIROSENSEENVIROSENSE
CONFIGCONFIGACCYACCY
RESETRESET
LINKLINK
STATUSSTATUS
12
11 10 9 8 7
6 5 4 3
2 1
INLET
3-1
A
B
C
13-11-194-933093.indb 5 12/5/2013 5:21:58 PM
6
Bitspersecond: 9600
Databits: 8
Parity: None
Stopbits: 1
Flowcontrol: None
Installation continued
4-2
Configure Terminal Emulation Program:OpenaVT100-compatibleterminalemulation
program(suchastheHyperTerminalprogrambundledwithMicrosoft
®
Windows
®
)ona
computerwithanavailableDB9serialport.(Anotebookcomputermaybethemost
convenientchoice.)SettheterminalemulationprogramtousetheCOMportthat
correspondstothecomputer’sDB9serialport.Specifytheparametersrequiredto
communicatewiththePDUterminalinterface:
Iftheterminalemulationprogramsupportsmultipleemulationmodes,youmayalsoneed
tospecifyVT100emulation.
4-3
Connect PDU to Computer: Usethe
RJ-45toDB9serialcable(partnumber
73-1243)includedwiththePDUto
connectthePDUtothecomputer.The
RJ-45connector
A
at one end of the
cableattachestotheCONFIGport
B
onthePDU.TheDB9connector
C
at
theotherendofthecableconnectsto
the computer's serial port
D
.
4-4
Connect PDU to Network: While the
PDUispowered,connectastandard
EthernetpatchcabletotheRJ-45
Ethernet port
A
onthePDU.
Note: This port is not compatible with PoE
(Power over Ethernet) applications.
4-5
Configure PDU in Terminal Mode:
Afterabriefpause,aninitializationpage
should appear in the terminal emulation
program.Pressanykeyonthekeyboard
within10secondstochangethePDU
settings.(Ifthe10-secondperiodhas
elapsed,youcanrebootthePDUby
pressingtheSNMPresetswitch.)
Followthesequenceofresponsesbelow
inordertoassignanIPaddresstothe
PDU.Thedefaultterminalmoderoot
password is TrippLite.SampleIPsettings
areshown-supplyyourownIP
information when you configure your
PDU.
4-3
4-5
B
24 23 22 21
20
19 18 17 16 15
14
13
ENVIROSENSEENVIROSENSE
CONFIGCONFIGACCYACCY
RESETRESET
LINKLINK
STATUSSTATUS
12
11 10 9 8 7
6 5 4 3
2 1
INLET
4-4
A
A
C
D
13-11-194-933093.indb 6 12/5/2013 5:22:00 PM
7
Press A to Accept the settings, or M to Modify? M
Enter the root password: *********
Reset configuration to default values (Y/N)? N
For each of the following questions, you can press <Return> to select the value shown in
braces, or you can enter a new value.
NETWORK INTERFACE PARAMETERS:
Should this target obtain IP settings from the network?[N] N
Static IP address [192.168.1.19]? 192.168.0.123
Static IP address is 192.168.0.123
Subnet Mask IP address [255.255.0.0]? 255.255.255.0
Subnet Mask IP address is 255.255.255.0
Gateway address IP address [192.168.1.1]? 192.168.0.1
Gateway address IP address is 192.168.0.1
Youcanalsochangetherootpassword,real-timeclockandothersettings.(TrippLite
recommends against changing the default settings unless you are an advanced user with a
specificpurpose.)Afteryouhavefinishedenteringsettings,thePDUwillsavechangestomemory
andreboot(thismaytakeseveralminutes).AfterthePDUreboots,theinitializationpageshould
displaythenewstaticIPsettings.
4-6
Remove Serial Cable: RemovetheserialcablefromthePDUandproceedtoStep
5-1
.
Testing Network Connection
5-1
Access PDU with Web Browser:
AfteranIPaddresshasbeenassigned
tothePDU,attempttoaccessitwitha
Webbrowserthatsupportsframes,
formsandJava™.OpenaWebbrowser
onacomputerconnectedtotheLAN
andentertheIPaddressassignedto
thePDU.Youshouldbepromptedfora
password
A
. The user name is admin
and the default password is admin.
After you enter the user name and
password,thePowerAlertstatuspage
B
willappearinthebrowserwindow.
Formoreinformationabout
configurationandoperationofthePDU
viathePowerAlertinterface,refertothe
SNMPWEBCARDUser'sGuide,included
ontheCD-ROMbundledwiththePDU.
Note for Network Management System Users
Only: Two MIB files - Tripplite.mib and
RFC1628.mib - must be loaded on each
Network Management Station that will
monitor the PDU via SNMP. The files are
provided on the CD-ROM included in the
product package.
Installation continued
A
B
13-11-194-933093.indb 7 12/5/2013 5:22:00 PM
8
Input Plug Adapter (Select Models): ConvertsthePDU's
twist-lockinputplugtoastraight-bladeinputplug.
Power Inlet (Select Models): TheIECpowerinletconnectsto
theincludedpowercordoracompatibleuser-suppliedpower
cord.Theinletincludesabrackettosecurethecordconnection.
IEC 309 3-Pole Input Plug:Availableonselectmodels.
Outlets (Vary by Model): Duringnormaloperation,theoutlets
distributeACpowertoconnectedequipment.Selectmodels
featureanLEDthatindicatesoutletstatus.
Outlet LEDs: Onswitchedmodels,eachoutletLEDilluminates
whentheassociatedoutletisreadytodistributeliveACpower.
Digital Load Meter (Ammeter): The total connected
equipmentloadinamperesisdisplayedbythedigitalmeter
A
.
20-ampmodelsfeatureaScrollIP/RotateSwitch
B
.Pressthis
switchforonesecondtodisplaythePDU’sIPaddress(two
charactersatatime).PressfortwosecondstorotatetheLED
display for ease of reading in vertical installations with the input
cordatthetoporbottomofthePDU.30-ampmodelsfeaturea
Select/RotateSwitch
C
andadedicatedScrollIPSwitch
D
.
PresstheSelect/RotateSwitchoncetodisplaythetotalload(in
amps)onthePDU.PressagaintodisplaytheloadonBank1of
thePDUandagaintodisplaytheloadonBank2.TheLoadBank
LEDs
E
willindicatedisplaystatusasfollows.Bothoutletbank
LEDsilluminated:totalPDUloaddisplayed.Bank1orBank2
LEDilluminated:loadoncorrespondingloadbankdisplayed.
PresstheSelect/RotateSwitchfortwosecondstorotatetheLED
display for ease of reading in vertical installations with the input
cordatthetoporbottomofthePDU.
Features
IEC-60320-C132-PositionIEC-60320-C13 IEC-60320-C19
.8.8
.8.8
Scroll I
P
/
Rota
t
e
LOAD (AMPS)LOAD (AMPS)
LOAD (AMPS)LOAD (AMPS)
Bank1
Bank2
Scroll
IP
LOAD (AMPS)
LOAD (AMPS)
Select /
Rotate
30 Amp 20 Amp
A
C
A
D
E
E
B
13-11-194-933093.indb 8 12/5/2013 5:22:03 PM
9
Features continued
Circuit Breakers (Select Models):Iftheconnected
equipmentloadonaloadbankexceedstheMaximumLoad
Ratingoftheloadbank,thecircuitbreakerwilltrip.Disconnect
excessequipmentandswitchbreakertotheonpositiontoreset
thebreaker.Modelswithmultipleoutletbankshaveacircuit
breakerforeachbank.Circuitbreakersareonlyusedtoprotect
outputloadbanks.
Cord Retention Bracket (Select Models):Providessecure
attachment points for connected equipment cords.
C14 Plug Sleeve: (Optional)UsetheincludedC14plastic
sleeves to secure plugs to C13 receptacles. Attach the sleeve to
theplugmakingsurethatthepulltabsremainoutsidetheplug
andthatthefitissecure.Tounplugequipmentproperly,usethe
pulltabstoremovetheplugandsleevefromthereceptacle.
C20 Plug Sleeve: (Optional)UsetheincludedC20plastic
sleevestosecureplugstoC19receptacles.Attachthesleeveto
theplugmakingsurethatthepulltabsremainoutsidetheplug
andthatthefitissecure.Tounplugequipmentproperly,usethe
pulltabstoremovetheplugandsleevefromthereceptacle.
Mounting Brackets:UsethesebracketstomountthePDU.
PDUMVROTATEBRKT Mounting Accessory: Usethese
V-shapedbracketstomountthePDUwithitsoutletsfacingthe
rearoftherack.
SNMP Reset Button: Presstheresetbutton
A
for 3 seconds
torebootthePDU'snetworkcard.Rebootingthenetworkcard
willnoterasenetworksettingsorinterruptACpower.Thereset
buttonisrecessed;useasuitabletooltopressit.
ACCY Port: Theportisreservedforfutureexpansion.
24 23 22 21
20
19 18 17 16 15
14
13
ENVIROSENSEENVIROSENSE
CONFIGCONFIGACCYACCY
RESETRESET
LINKLINK
STATUSSTATUS
12
11 10 9 8 7
6 5 4 3
2 1
INLET
A
13-11-194-933093.indb 9 12/5/2013 5:22:05 PM
10
Configuration and Operation
Remote Monitoring and Control
ThePDUprovidesremotemonitoring
A
,
outlet control
B
andmoreviaWebbrowser,
telnetandSNMP-basedNetwork
ManagementSystems.Formoreinformation
aboutconfigurationandoperationofthe
PDUviathePowerAlertWebbrowser
interface,refertotheSNMPWEBCARDUser's
Guide,includedontheCD-ROMbundled
withthePDU.
Features continued
PS/2 Port: UsethisporttoconnectaTrippLiteENVIROSENSE
environmental sensor to provide remote temperature/humidity
monitoring and a dry contact interface to control and monitor
alarm,securityandtelecomdevices.Visitwww.tripplite.comfor
orderinginformation.Note:Donotconnectakeyboardormouse
to this port.
RJ-45 Configuration Port: Usethisporttoprovideadirect
terminal connection to a computer with a terminal emulation
program.AnRJ-45cableisincludedwiththePDU.Ifyouneeda
replacementcable,visitwww.tripplite.comforordering
information.
Ethernet Port: UsethisRJ-45jacktoconnectthePDUtothe
networkwithastandardEthernetpatchcable.TheLinkLED
A
andStatusLED
B
indicateseveraloperatingconditions,as
showninthetablebelow.This port is not compatible with PoE
(Power Over Ethernet) applications.
Network Operating Conditions
A
Link LED Color
Off NoNetworkConnection
FlashingAmber 100MbpsNetworkConnection
FlashingGreen 10MbpsNetworkConnection
B
Status LED Color
Off CardNotInitialized
SteadyGreen CardInitializedandOperational
FlashingAmber Error-CardNotInitialized
A
B
A
B
13-11-194-933093.indb 10 12/5/2013 5:22:06 PM
11
Warranty and Warranty Registration
LIMITED WARRANTY
Sellerwarrantsthisproduct,ifusedinaccordancewithallapplicableinstructions,tobefreefromoriginaldefects
inmaterialandworkmanshipforaperiodof2years(exceptinternalUPSsystembatteriesoutsideUSAand
Canada, 1 year) from the date of initial purchase. If the product should prove defective in material or
workmanshipwithinthatperiod,Sellerwillrepairorreplacetheproduct,initssolediscretion.Serviceunderthis
Warrantycanonlybeobtainedbyyourdeliveringorshippingtheproduct(withallshippingordeliverycharges
prepaid)to:TrippLite,1111W.35thStreet,Chicago,IL60609USA.Sellerwillpayreturnshippingcharges.
Visitwww.tripplite.com/supportbeforesendinganyequipmentbackforrepair.
THISWARRANTYDOESNOTAPPLYTONORMALWEARORTODAMAGERESULTINGFROMACCIDENT,MISUSE,
ABUSEORNEGLECT.SELLERMAKESNOEXPRESSWARRANTIESOTHERTHANTHEWARRANTYEXPRESSLYSET
FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES,
INCLUDINGALLWARRANTIESOFMERCHANTABILITYORFITNESS,ARELIMITEDINDURATIONTOTHEWARRANTY
PERIODSETFORTHABOVE;ANDTHISWARRANTYEXPRESSLYEXCLUDESALLINCIDENTALANDCONSEQUENTIAL
DAMAGES.(Somestatesdonotallowlimitationsonhowlonganimpliedwarrantylasts,andsomestatesdonot
allowtheexclusionorlimitationofincidentalorconsequentialdamages,sotheabovelimitationsorexclusions
maynotapplytoyou.ThisWarrantygivesyouspecificlegalrights,andyoumayhaveotherrightswhichvary
fromjurisdictiontojurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable,
adequate or safe for the use intended. Since individual applications are subject to great variation, the
manufacturermakesnorepresentationorwarrantyastothesuitabilityorfitnessofthesedevicesforanyspecific
application.
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be
automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
*Nopurchasenecessary.Voidwhereprohibited.Somerestrictionsapply.Seewebsitefordetails.
FCC Notice
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:(1)This
devicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterferencereceived,including
interference that may cause undesired operation.
ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuanttopart
15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterference
whentheequipmentisoperatedinacommercialenvironment.Thisequipmentgenerates,uses,andcanradiate
radiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructionmanual,maycause
harmfulinterferencetoradiocommunications.Operationofthisequipmentinaresidentialareaislikelytocause
harmfulinterferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.The
usermustuseshieldedcablesandconnectorswiththisproduct.Anychangesormodificationstothisproduct
notexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidtheuser'sauthoritytooperatethe
equipment.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been
assignedauniqueseriesnumber.Theseriesnumbercanbefoundontheproductnameplatelabel,alongwith
allrequiredapprovalmarkingsandinformation.Whenrequestingcomplianceinformationforthisproduct,always
refertotheseriesnumber.Theseriesnumbershouldnotbeconfusedwiththemarkingnameormodelnumber
of the product.
TrippLitefollowsapolicyofcontinuousimprovement.Specificationsaresubjecttochangewithoutnotice.
13-11-194-933093.indb 11 12/5/2013 5:22:06 PM
12
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
13-11-194-933093.indb 12 12/5/2013 5:22:06 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Tripp Lite PDUMV30HVNET Owner's manual

Category
Power distribution units (PDUs)
Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI