Fluidwell F133 Owner's manual

Type
Owner's manual
F133-P
DELIVERY CONTROLLER / DISPENSER
with pump start and valve control
Signal input flowmeter: pulse, Namur and coil
External controls: start and stop
Digital outputs: two pump / valve control outputs
Options: Intrinsically safe, Modbus communication, backlight
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries
Page 2
FW_F133-P_M_v2201-01_EN.docx
SAFETY INSTRUCTIONS
Any responsibility is lapsed if the instructions and procedures as described in this manual
are not followed.
LIFE SUPPORT APPLICATIONS: The F133-P is not designed for use in life support
appliances, devices, or systems where malfunction of the product can reasonably be
expected to result in a personal injury. Customers using or selling these products for use
in such applications do so at their own risk and agree to fully indemnify the manufacturer
and supplier for any damages resulting from such improper use or sale.
Electro static discharge does inflict irreparable damage to electronics! Before installing or
opening the F133-P, the installer has to discharge himself by touching a well-grounded
object.
The F133-P must be installed in accordance with the EMC guidelines (Electro Magnetic
Compatibility).
Connect a proper grounding to the metal enclosure as indicated if the F133-P has an
incoming power or signal line which carries a hazardous live voltage.
The Protective Earth (PE) wire may never be disconnected or removed.
Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5.
Certificates and related documents are available on our website or from your distributor.
DISPOSAL OF ELECTRONIC WASTE
The WEEE Directive requires the recycling of disposed electrical and electronic
equipment in the European Union. When the WEEE Directive does not apply to your
region, we support its policy and ask you to be aware on how to dispose of this product.
The crossed out wheelie bin symbol as illustrated and found on our products tells that
this product shall not be disposed of into the general waste system or into a landfill.
At the end of its life, equipment shall be disposed of according to the local regulations
regarding waste of the electrical and the electronic equipment.

helpdesk for information on the product disposal.
SAFETY RULES AND PRECAUTIONARY MEASURES
The manufacturer accepts no responsibility whatsoever if the following safety rules and
precautions, instructions and the procedures as described in this manual are not
followed.
Modifications of the F133-P implemented without preceding written consent from the
manufacturer, will result in the immediate termination of product liability and warranty
period.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Check the mains voltage and information on the manufacturer's plate before installing the
F133-P.
Check all connections, settings and technical specifications of the various peripheral
devices with the F133-P supplied.
Open the enclosure only if all leads are free of potential.
Never touch the electronic components (ESD sensitivity).
Never expose the system to heavier conditions than allowed according to the
classification of the enclosure (see manufacture's plate and chapter 4.2.).
If the operator detects errors or dangers, or disagrees with the safety precautions taken,
he should inform the owner or principal responsible.
The local labor and safety laws and regulations must be adhered to.
Page 3
FW_F133-P_M_v2201-01_EN.docx
ABOUT THE MANUAL
This manual is divided into two main sections:
The daily use of the unit is described in chapter 2 "Operation". These instructions are meant for
users.
The following chapters and appendices are exclusively meant for electricians/technicians. These
provide a detailed description of all software settings and hardware installation guidance.
This manual describes the standard unit as well as the available options. For additional information,
please contact your supplier.
A hazardous situation may occur if the F133-P is not used for the purpose it was designed for
or is used incorrectly. Please carefully note the information in this manual indicated by the
pictograms:
A "warning !" indicates actions or procedures which, if not performed correctly, may lead to
personal injury, a safety hazard or damage of the F133-P or connected instruments.
A "caution !" indicates actions or procedures which, if not performed correctly, may lead to
personal injury or incorrect functioning of the F133-P or connected instruments.
A "note !" indicates actions or procedures which, if not performed correctly, may indirectly
affect operation or may lead to an instrument response which is not planned.
WARRANTY AND TECHNICAL SUPPORT
For warranty and technical support for your products, please contact your supplier, visit our internet
site www.fluidwell.com or contact us at support@fluidwell.com.
Hardware version : 03.01.xx
Software version : 03.03.xx
Manual : FW_F133-P_M_v2201-01_EN.docx
© Copyright 2023 : Fluidwell B.V. - the Netherlands
Information in this manual is subject to change without prior notice. The
manufacturer is not responsible for mistakes in this material or for incidental
damage caused as a direct or indirect result of the delivery, performance or
use of this material.
© All rights reserved. No parts of this publication may be reproduced or used
in any form or by any means without written permission of your supplier.
Page 4
FW_F133-P_M_v2201-01_EN.docx
TABLE OF CONTENTS
SAFETY INSTRUCTIONS .................................................................................................................................... 2
DISPOSAL OF ELECTRONIC WASTE ................................................................................................................ 2
SAFETY RULES AND PRECAUTIONARY MEASURES ..................................................................................... 2
ABOUT THE MANUAL ......................................................................................................................................... 3
WARRANTY AND TECHNICAL SUPPORT ......................................................................................................... 3
TABLE OF CONTENTS ........................................................................................................................................ 4
1 INTRODUCTION ..................................................................................................................................... 6
1.1 System description of the F133-P ............................................................................................ 6
2 OPERATIONAL ...................................................................................................................................... 8
2.1 General information ................................................................................................................. 8
2.2 Control panel ............................................................................................................................ 8
2.3 Operator information and functions ......................................................................................... 8
2.4 Dispenser functional diagram ................................................................................................ 10
3 CONFIGURATION ................................................................................................................................ 12
3.1 Introduction ............................................................................................................................ 12
3.2 Programming SETUP-level .................................................................................................... 12
3.2.1 Entering SETUP-level ............................................................................................................ 12
3.2.2 Navigating through SETUP-level ........................................................................................... 12
3.2.3 Programming sequence ......................................................................................................... 13
3.2.4 Returning to OPERATOR-level ............................................................................................. 14
3.3 Configuration settings ............................................................................................................ 14
3.3.1 Setup menu Settings........................................................................................................... 14
3.3.2 Menu 1 - Total ........................................................................................................................ 16
3.3.3 Menu 2 - Flow rate ................................................................................................................. 17
3.3.4 Menu 3 - Display .................................................................................................................... 17
3.3.5 Menu 4 - Power management ............................................................................................... 18
3.3.6 Menu 5 - Flowmeter ............................................................................................................... 18
3.3.7 Menu 6 - Control .................................................................................................................... 19
3.3.8 Menu 7 Status ..................................................................................................................... 19
3.3.9 Menu 8 - Communication (option) ......................................................................................... 20
3.3.10 Menu 9 - Others ..................................................................................................................... 20
4 INSTALLATION .................................................................................................................................... 21
4.1 General directions .................................................................................................................. 21
4.2 installation / surrounding conditions ....................................................................................... 21
4.3 Handling the F-Series Enclosure ........................................................................................... 22
4.3.1 Identification ........................................................................................................................... 22
4.3.2 Opening / removing the cover ................................................................................................ 23
4.3.3 Closing / replacing the cover ................................................................................................. 23
4.4 Mechanical installation ........................................................................................................... 24
4.4.1 Dimensions Aluminum and stainless steel enclosures ....................................................... 24
4.4.2 Dimensions Non-metallic enclosures .................................................................................. 25
4.4.3 Mounting 26
4.5 Electrical installation .............................................................................................................. 27
4.5.1 Electrical safety ...................................................................................................................... 27
4.5.2 Protective Earth (PE) connections ......................................................................................... 27
4.5.3 Field wiring connections......................................................................................................... 28
4.5.4 Power supply wiring ............................................................................................................... 28
4.5.5 Sensor supply ........................................................................................................................ 29
4.6 Terminal connectors .............................................................................................................. 30
4.6.1 Terminal 00-02: Power supply ............................................................................................... 30
4.6.2 Terminal 03-04: Valve control R2 .......................................................................................... 31
4.6.3 Terminal 05-06: Pump control R1 .......................................................................................... 31
4.6.4 Terminal 09-11: Flowmeter input ........................................................................................... 32
4.6.5 Terminal 12-13: Status input 1 ............................................................................................... 34
4.6.6 Terminal 15-16: Status input 2 ............................................................................................... 35
4.6.7 Terminal 26-31: Type CB / CH / CI - Communication (option) ............................................. 36
5 INTRINSICALLY SAFE APPLICATIONS ............................................................................................. 37
Page 5
FW_F133-P_M_v2201-01_EN.docx
5.1 Identification .......................................................................................................................... 37
5.2 Electrical installation in hazardous area ................................................................................ 38
5.2.1 General information and instructions ..................................................................................... 38
5.2.2 Installations based on ATEX or IECEx certificate ................................................................. 39
5.2.3 Electrical data Annex 1 ....................................................................................................... 40
5.2.4 Power supply wiring ............................................................................................................... 42
5.2.5 Sensor supply ........................................................................................................................ 42
5.3 Terminal connectors Intrinsically safe applications TYPE XI ............................................. 43
5.3.1 Terminal 26-29: Type CT - Communication .......................................................................... 43
5.4 Configuration examples ......................................................................................................... 44
6 MAINTENANCE ................................................................................................................................... 46
6.1 General directions ................................................................................................................. 46
6.2 Repair .................................................................................................................................... 46
6.3 Battery replacement instructions ........................................................................................... 47
6.3.1 Safety instructions ................................................................................................................. 47
6.3.2 Replace the battery ............................................................................................................... 48
6.3.3 Disposal of batteries .............................................................................................................. 48
APPENDIX A. TECHNICAL SPECIFICATION .............................................................................................. 49
APPENDIX B PROBLEM SOLVING ............................................................................................................. 52
APPENDIX C. COMMUNICATION VARIABLES ........................................................................................... 53
APPENDIX D. DECLARATION OF CONFORMITY ....................................................................................... 57
INDEX OF THIS MANUAL ................................................................................................................................. 58
LIST OF FIGURES IN THIS MANUAL ............................................................................................................... 59
Page 6
1 INTRODUCTION
1.1 SYSTEM DESCRIPTION OF THE F133-P
Functions and features
The delivery controller / dispenser model F133-P is a microprocessor driven instrument designed for
the delivery of beforehand unknown quantities as well as displaying the flow rate, the delivered total
and the delivered accumulated total. This product has been designed with a focus on:
ultra-low power consumption to allow long-life battery powered applications (type PB/PC)
intrinsic safety for use in hazardous applications (type XI)
several mounting possibilities with aluminum or GRP enclosures for harsh industrial
surroundings
ability to process all types of flowmeter signals
transmitting possibilities with analog, pulse and communication outputs.
Flowmeter input
This manual describes the unit with a pulse input from the flowmeter.
One flowmeter with a passive or active pulse, Namur or sine wave (coil) signal output can be
connected to the F133-P. To power the sensor, several options are available.
Standard outputs
Two passive transistor or relay outputs to control a pump and a valve.
Fig. 1: Typical application
Page 7
FW_F133-P_M_v2201-01_EN.docx
Configuration of the F133-P
The F133-P is designed for use in many types of applications. For that reason, a setup menu is
available to program the F133-P according to your specific requirements.
The setup includes several important features, such as K-Factors, engineering units, signal
selection, power management (to extend battery life-time), etc. All settings are stored in a non-
volatile memory and therefore kept in the event of a power failure or an exhausted battery.
Display information
The unit has a LCD with (optional) backlight to show the process information, status and alarm
messages. The display refresh rate is programmed in the setup menu.
At a key press, the display refresh rate will switch to FAST for 30 seconds. When 'OFF' is selected,
the display goes off after 30 seconds after the last key press. The display temporarily comes on after
a key press.
A backup of the total and accumulated total in EEPROM memory is made every minute.
Options
The following options are available: full Modbus communication RS232/485/TTL (also battery
powered), intrinsic safety, mechanical relay or active output, power- and sensor-supply options,
panel-mount, wall-mount and weather-proof enclosures, flame proof enclosure and LED backlight.
Page 8
FW_F133-P_M_v2201-01_EN.docx
2 OPERATIONAL
2.1 GENERAL INFORMATION
This chapter describes the daily use of the F133-P. This instruction is meant for users / operators.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
2.2 CONTROL PANEL
The control panel has three keys. The following keys are available:
Fig. 2: Control panel.
Functions of the keys
This key is used to program and save new values or settings.
The PROG/ENTER key is also used to gain access to the setup menu (read
chapter 3).
This key is used to START the batch process.
The START/ key is also used to increase a value after the PROG/ENTER key has
been pressed (read chapter 3).
This key is used to pause or stop the batch process. When the batch process is
stopped, it cannot be continued. The STOP/ key is also used to select the total and
the accumulated total.
The STOP/ key is also used to select a digit or an option after the PROG/ENTER
key has been pressed (read chapter 3).
2.3 OPERATOR INFORMATION AND FUNCTIONS
In general, the F133-P operates in the operator mode. The shown information depends on the
settings which are made in the setup menu.
The signal from the connected sensor is processed by the F133-P in the background, independent
from the selected display refresh rate.
When READY is shown, the data of the last delivery is shown, and the following functions are
available.
Start-up the delivery
When you press the "START" key, the F133-P initiates a new delivery, the "RUN" indicator
comes on and temporarily the total shows "8888888" and the flow rate "88888". Depending on
the setup of the F133-P, relays are switched to start the pump(s) and to open the valve(s). In the
software, a timer is started to monitor the flow rate.
When a flow is detected, the delivery will start and the total and the flow rate show the actual
status.
When the flow rate is not sufficient, the delivery will not start and the Alarm indicator comes on,
the total shows "0000000" and the flow rate shows "not started". The startup sequence is
stopped.
Page 9
FW_F133-P_M_v2201-01_EN.docx
Fig. 3: Example of display information during delivery.
Interrupt the delivery (when RUN is shown)
After the startup sequence is completed, the dispense sequence becomes active. During the
dispense sequence you can interrupt the delivery temporarily with the STOP command. The
"PAUSE" indicator comes on and an internal restart timer is started. Note that the pump stays on
and the valve is closed. The delivery is continued when the restart timer still active and the
START command is given. When the restart timer is lapsed, the delivery is stopped
automatically.
Batch-total
To display the batch-total, use the STOP button. This quantity equals the accumulated delivered
quantity (from the START moment till the READY moment) and cannot be initialized by the
operator. It will count up to 9999999.
Press STOP a few times to return to the main display information.
Batch-counter
To display the batch-counter, press STOP again. This counter displays the number of deliveries
that have been made successfully and cannot be initialized by the operator. It will count up to
9999999.
Press STOP a few times to return to the main display information.
Display Total and accumulated Total
Press STOP to display the Total and Accumulated Total. These totalizers do count the
flowmeters signal continuously, even when no process is running.
The value for Total can be initialized. To do so, be sure Total is shown.
First press PROG followed by STOP. After pressing PROG, the text "PUSH STOP" is shown. To
avoid initialization in that stage, press a different key or wait for 20 seconds. Initialization of Total
DOES NOT influence accumulated Total.
Accumulated Total can never be initialized. This value will count up to 99999999999.
Press STOP a few times to return to the main display information.
Alarms
The following alarms can occur:
Flow rate alarm:
When the actual flow rate is outside the allowed range (as set in the setup menu), the delivery
will be paused automatically and an alarm message will be shown indicating the type of flow rate
alarm: "LO RATE" or "HI RATE". If pause is enabled, the delivery can be restarted.
Maximum batch:
When the total quantity delivered exceeds a certain quantity, the F133-P will switch-off all relays
and generate an "MAX BATCH" alarm.
If pause is enabled, the delivery can be restarted.
Low-battery alarm
When the battery voltage drops, the "low-battery" icon will be displayed continuously. The battery
MUST be replaced shortly after!
The remaining lifetime after the first moment of indication is generally several days up to some
weeks. See paragraph 6.3 for further information on battery replacement.
Page 10
FW_F133-P_M_v2201-01_EN.docx
Fig. 4: Example of low-battery alarm.
Alarm
When the alarm indicator is shown, refer to Appendix B: Problem Solving.
2.4 DISPENSER FUNCTIONAL DIAGRAM
The function of the F133-P depends on the different settings in the setup menu. The example is
given for a typical configuration.
Legend
I Idle, waits for new delivery.
A Start, the START key is pushed to start a new delivery, the F133-P will reset itself.
B Delay, time for the pump to start up.
C Begin, pump is at delivery speed.
D Startup, valve opens to build up the flow, flow detection is active.
E Started, flow is present at required rate.
F Not started, there is no flow or the flow is not sufficient, the valve closes and the display shows
NOT STARTED.
Pump, stopped
Timer, predefined by software
Pump, running
61
Timer, set by setup menu 6.1
Valve, closed
Flow OK, restart timer active
Valve, open
Flow NOK, restart timer elapsed
Reset, predefined by software
Fig. 5: Functional diagram - Start delivery.
Page 11
FW_F133-P_M_v2201-01_EN.docx
Fig. 6: Functional diagram Pause or stop delivery (with pause enabled).
Fig. 7: Functional diagram Stop delivery (with set overrun timer).
Page 12
FW_F133-P_M_v2201-01_EN.docx
3 CONFIGURATION
3.1 INTRODUCTION
This and the following chapters are exclusively meant for electricians and non-operators. In these,
an extensive description of all software settings and hardware connections are provided.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the enclosure cover is
removed or the panel cabinet has been opened (danger from electrical shock). The
enclosure may only be opened by trained persons authorized by the operator of the
facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
3.2 PROGRAMMING SETUP-LEVEL
Changing the settings of the F133-P may have an influence on the current operation of the
device, even when SETUP-level is still active.
Make sure that the unit is not being used for any application when altering the settings.
3.2.1 ENTERING SETUP-LEVEL
Configuration of the F133-P is done at SETUP-level, which can be reached at all times while the
F133-P remains fully operational. At SETUP-level the display will deactivate the RUN indicator and
activate the SETUP indicator.
Use the control panel to access SETUP-level
PROG-key
To enter SETUP-level, press the PROG-key for 7 seconds at OPERATOR-level.
During this time, the symbols  will be displayed.
When SETUP-level is entered, a password might be required to continue. You can
enter the password by following the procedure for programming values as described in
the following paragraphs.
A password may be required to enter SETUP.
Without this password access to SETUP is denied.
3.2.2 NAVIGATING THROUGH SETUP-LEVEL
Each function has a unique menu-number, which is displayed below the SETUP indicator at the
bottom of the display. The menu-number is a combination of two figures, e.g. 1.2. The first number
indicates the function-group and the second number indicates the function. Additionally, each
function and function-group is expressed with a keyword.
Fig. 8: SETUP matrix structure
1.1
1.2
2.1.
2.1
1.3
2.2
3.1
3.
FUNCTION GROUP
FUNCTION
FW-4100-000001-001-EN
Page 13
FW_F133-P_M_v2201-01_EN.docx
Use the control panel to navigate through SETUP-level
PROG-key
When a function is selected, this key is used to start the programming sequence.
When only a function group is selected (and no function), this key is used to scroll
back a function group (e.g. 3 2 1 3).
START-key
This key is used to select the next function in the list (e.g. 1 1.1 1.2 1). When
the top of the list is reached, it will wrap around and return to the function group
selection.
STOP-key
This key is used to select the previous function in the list (e.g. 1.2 1.1 1 2).
When the bottom of the list is reached, it will return to the function group selection.
When only a function group is selected (and no function), this key is used to scroll to
the next function group. (e.g. 1 2 3 1).
3.2.3 PROGRAMMING SEQUENCE
After selecting a function at SETUP-level, a new value can be programmed using the control panel.
A function either contains a value (a number with optionally a decimal point, e.g. 123.45) or a list
with items (e.g. Disable Enable).
For each function that needs to change, navigate to that function and follow the steps indicated
below. During the programming sequence, the display will deactivate the SETUP indicator and
activate the PROGRAM indicator.
When programming new values, alterations will only be set after the PROG-key has been
pressed to confirm the new value! (STEP 3)
Step 1: Starting the programming sequence
PROG-key
When a function is selected at SETUP-level, this key is used to start the programming
sequence.
Step 2a: Changing a value
START-key
This key is used to increment the selected digit.
When the entered value is out of range, the increase sign or decrease-sign will
be displayed while you are programming. If this value is confirmed by pressing the
PROG-key, the value will be brought within a valid range automatically.
STOP-key
This key is used to select the next digit. If a decimal point can be set, this will be
included in the sequence as well (e.g. [decimal point] digit 1 digit 2 digit 3
[decimal point].
START-key + STOP-key
The combination of the START-key and STOP-key is used to select a negative value.
When a value can also be entered as a negative number, pressing the START-key
and STOP-
Step 2b: Changing the selected item in a list
START-key
This key is used to select the next item in the list (e.g. Disable Enable).
At the end of the list, the selection will wrap around to the first selection.
Page 14
FW_F133-P_M_v2201-01_EN.docx
STOP-key
This key is used to select the previous item in the list (e.g. Enable Disable ).
At the bottom of the list, the selection will wrap around to the last selection.
Step 3: Finishing the programming sequence
PROG-key
During the programming sequence, this key is used to confirm the new value and
return to SETUP-level. To cancel the operation, either press the PROG-key for 3
seconds or wait for 20 seconds: the programming sequence is cancelled and the
former value is reinstated.
3.2.4 RETURNING TO OPERATOR-LEVEL
When all settings are configured correctly, the unit can be returned to OPERATE-level.
Please keep a record of all settings for later reference.
Use the control panel to return to OPERATE-level
PROG-key
In order to return to the operator level, press the PROG-key for three seconds.
When no keys are pressed for 2 minutes, SETUP-level will be left automatically.
3.3 CONFIGURATION SETTINGS
All settings of the F133-P can be set via the control panel.
The following paragraphs give a detailed description of each setting.
3.3.1 SETUP MENU SETTINGS
SETUP FUNCTIONS AND VARIABLES
1
TOTAL
1.1
UNIT
L; m3; kg; lb; GAL; USGAL; bbl; no unit
1.2
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
1.3
K-FACTOR
0.000010 - 9999999
1.4
DECIMALS K-FACTOR
0 - 6
1.5
BATCH MAX
0000000 - 9999999
1.6
BATCH TOTAL
0.001 - 9999999
1.7
BATCH COUNT
0 - 9999999
2
FLOW RATE
2.1
UNIT
mL; L; m3; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm3; nL; p
2.2
TIME
/sec; /min; /hour; /day
2.3
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
2.4
K-FACTOR
0.000010 - 9,999,999
2.5
DECIMALS K-FACTOR
0 - 6
2.6
CALCULATION
per 1 - 255 pulses
2.7
CUTOFF
0.1 - 999.9 seconds
2.8
LOW FLOW RATE ALARM
0.001 - 9999999
2.9
HIGH FLOW RATE ALARM
0.001 - 9999999
2.A
DELAY TIME ALARM
0.0 - 999.9 seconds
3
DISPLAY
3.1
LIGHT
0% (off); 20%; 40%; 60%;- 80%; 100% (full brightness)
3.2
BACKLIGHT ALARM
off, on, flash
4
POWER MANAGEMENT
4.1
LCD NEW
fast; 1 sec; 3 sec; 15 sec; 30 sec; off
4.2
BATTERY MODE
operational; shelf
Page 15
FW_F133-P_M_v2201-01_EN.docx
5
FLOWMETER
5.1
SIGNAL
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
6
CONTROL
6.1
DELAY
0.1 - 999.9 seconds
6.2
BEGIN
0.1 - 999.9 seconds
6.3
START UP
0.1 - 999.9 seconds
6.4
NO PULSE
0.1 - 999.9 seconds
6.5
PAUSE
disable - enable
6.6
RESTART
0.1 - 999.9 seconds
6.7
OVERRUN
0.1 - 999.9 seconds
7
STATUS
7.1
STATUS 1
start; stop; continue; off
7.2
STATUS 2
stop; pause; both; off
8
COMMUNICATION
8.1
SPEED
1200; 2400; 4800; 9600; 9600HP; 19200; 38400
8.2
ADDRESS
1 - 247
8.3
MODE
bus-rtu; bus-asc; off
8.4
DATABITS
8 bits, 7 bits
8.5
PARITY
none, even, odd
8.6
COMM.LOCK
disable, timeout, full
9
OTHERS
9.1
MODEL
F133-P
9.2
SOFTWARE VERSION
nn:nn:nn
9.3
SERIAL NO.
nnnnnnn
9.4
PASSWORD
0000 - 9999
9.5
TAG-NR
0000000 - 9999999
Page 16
FW_F133-P_M_v2201-01_EN.docx
3.3.2 MENU 1 - TOTAL
1
TOTAL
1.1
UNIT
This setting is used to select the engineering unit for the indication of
the batch total and the accumulated total.
When you change the engineering unit, you must recalculate and
reprogram the K-factor for the (accumulated) total. When you
recalculate and reprogram the K-Factor, the history for (accumulated)
batch total is not correct anymore, because the (accumulated) batch
total is not recalculated. For future reference, best practice is to make
a note of the accumulated total before you program the recalculated
K-Factor.
1.2
DECIMALS
This setting is used to set the number of digits behind the decimal
point for the (accumulated) total indication.
1.3
K-FACTOR
This setting is used to set the K-Factor for the total. With the K-Factor,
the flowmeter pulse signals are converted to a quantity. The K-Factor
is based on the number of pulses generated by the flowmeter per
selected engineering unit, for example per m3. A more accurate K-
Factor (more decimals, as set in decimals K-Factor) allows for a more
accurate operation of the system.
Example 1: Calculating the K-Factor.
The flowmeter generates 2.4813 pulses per liter and the selected unit
is m3. A cubic meter consists of 1000 liter which gives 2.4813
pulses*1000 liter=2481.3 pulses per m3. So, the K-Factor is 2481.3.
Enter for the Flowmeter K-Factor: 24813 and for the flowmeter K-
Factor decimals: 1.
Example 2: Calculating the K-Factor.
The flowmeter generates 6.5231 pulses per gallon and the selected
engineering unit is gallons. So, the K-Factor is 6.5231. Enter for the
flowmeter K-Factor 65231 and for the flowmeter K-Factor decimals 4.
When you recalculate and reprogram a new K-Factor, the history for
(accumulated) batch total is not correct anymore, because the
(accumulated) batch total is not recalculated. For future reference,
best practice is to make a note of the accumulated total before you
program the recalculated K-Factor.
1.4
DECIMALS K-FACTOR
This setting is used to set the number of digits behind the decimal
point for the K-Factor.
1.5
BATCH MAXIMUM
This setting is used to set the upper limit for a batch volume. An
operator cannot set a batch volume which is beyond the upper limit.
1.6
BATCH TOTAL
Batch total - also shown at operator level - displays the accumulated
quantity of product being delivered. From here, this total can be
programmed to zero or to any desired quantity.
1.7
BATCH COUNTER
Batch count - also shown at operator level - displays the number of
deliveries executed. From here, this total can be reset to zero or being
programmed to any desired quantity
Page 17
FW_F133-P_M_v2201-01_EN.docx
3.3.3 MENU 2 - FLOW RATE
2
FLOW RATE
2.1
UNIT
This setting is used to select the engineering unit for the indication of
the flow rate.
Alteration of the engineering unit will have consequences for operator
and SETUP-level values, they will not be automatically recalculated to
the value of the new selected unit. The K-factor has to be adapted as
well; the calculation is not done automatically.
2.2
TIME
This setting is used to set the time unit for the flow rate calculation.
Note that the flow rate is given in engineering unit/time unit, e.g.
liters/minute (l/min).
When you change this setting, also recalculate and change the
settings for the analog rate-min and analog rate-max.
2.3
DECIMALS
This setting is used to set the number of digits behind the decimal
point for the flow rate indication.
2.4
K-FACTOR
This setting is used to set the K-Factor for the flow rate. With the K-
Factor, the flowmeter pulse signals are converted to a quantity. The
K-Factor is based on the number of pulses generated by the
flowmeter per selected engineering unit, for example per m3. A more
accurate K-Factor (more decimals, as set in decimals K-Factor)
allows for a more accurate operation of the system.
2.5
DECIMALS K-FACTOR
This setting is used to set the number of digits behind the decimal
point for the K-Factor.
2.6
CALCULATION
The flow rate is calculated by measuring the time between a number
of pulses, for example 10 pulses. The more pulses the more accurate
the flow rate will be. The maximum value is 255 pulses.
This setting does influence the update interval for the flow rate and
thus, indirectly the update interval of the analog output.. (maximum
update 10 times a second). If the output response is too slow,
decrease the number of pulses. For low frequency applications (<
10Hz): do not program more than 10 pulses, else the update time will
be very slow.
For high frequency applications (> 1kHz) 50 or more pulses are
advised.
2.7
CUTOFF
This setting is used to set the threshold for a minimum flow. If during
this time less than XXX-pulses are generated (refer to Calculation),
the flow rate will be shown as zero. The cut-off has to be entered in
seconds.
2.8
LOW FLOW RATE ALARM
Activates the related alarm condition and to set the threshold value for
a this flow alarm. The setting 0.0 disables this alarm.
2.9
HIGH FLOW RATE
ALARM
Activates the related alarm condition and to set the threshold value for
a this flow alarm. The setting 0.0 disables this alarm.
2.A
DELAY TIME ALARM
Sets a delay time for the related alarm. When the alarm condition is
still valid after the delay time, an alarm is given.
3.3.4 MENU 3 - DISPLAY
3
DISPLAY
3.1
LIGHT
The backlight brightness can be adjusted from 0% (off) to 100% (full
brightness) in steps of 20%.
3.2
BACKLIGHT ALARM
Sets the behavior of the backlight during an alarm conditions.
Page 18
FW_F133-P_M_v2201-01_EN.docx
3.3.5 MENU 4 - POWER MANAGEMENT
When used with the internal battery option (type PB/PC), the user can expect reliable measurement
over a long period of time. The F133-P has several smart power management functions to extend
the battery life time significantly. Two of these functions can be set.
4
POWER MANAGEMENT
4.1
LCD NEW
The calculation of the display-information influences the power
consumption significantly. When the application does not require a fast
display refresh rate, it is strongly advised to select a slow refresh rate.
Please understand that NO information will be lost; every pulse will be
counted and the output signals will be generated in the normal way.
At a key press, the display refresh rate will switch to FAST for 30
seconds. When 'OFF' is selected, the display goes off after 30 seconds
after the last key press. The display temporarily comes on after a key
press.
Example battery life-time with a coil pick-up:
1kHz pulse and FAST update: about 2 years;
1kHz pulse and 1 sec update: about 5 years.
4.2
BATTERY MODE
The F133-P has two modes: operational or shelf.
After "shelf" has been selected, the F133-P can be stored for several
years; it will not process the sensor signal; the display is switched off
but all settings and totals are stored. In this mode, power consumption
is extremely low.
To wake up the F133-P again, press the START/ key two times.
3.3.6 MENU 5 - FLOWMETER
With this setting the type of flowmeter output is selected. The settings with LP (low-pass) filter are
used to apply a build-in noise reduction. Selections "active pulse" offer a detection level of 50% of
the supply voltage.
5
FLOWMETER
5.1
SIGNAL
With this setting the type of flowmeter output is selected. The settings with
LP (low-pass) filter are used to apply a build-in noise reduction.
Selections "active pulse" offer a detection level of 50% of the supply voltage.
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ. / mVpp
REMARK
NPN
NPN input
100 kΩ pull-up
max. 6 kHz.
(open collector)
NPN - LP
NPN with low pass filter
100 kΩ pull-up
max. 1.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1 MΩ pull-up
max. 1.2 kHz.
REED - LP
Reed-with low pass filter
1 MΩ pull-up
max. 120 Hz.
Less sensitive
PNP
PNP input
100 kΩ pull-down
max. 6 kHz.
PNP - LP
PNP with low pass filter
100 kΩ pull-down
max 1.2 kHz.
Less sensitive
NAMUR
NAMUR input
820 Ω pull-down
max. 4 kHz.
External power
required
COIL-HI
High sensitive coil input
-
min. 20 mVpp
Sensitive for
interference!
COIL-HI (option ZF)
min. 10 mVpp
COIL-HI (option ZG)
min. 5 mVpp
COIL LO
Low sensitive coil input
-
min. 80 mVpp
Normal sensitivity
8-1 DC
Active pulse input
detection level 8.2 V DC
3.9
max. 10 kHz.
External power
required
12 DC
Active pulse input
detection level 12 V DC
4
max. 10 kHz.
External power
required
24 DC
Active pulse input
detection level 24 V DC
3
max. 10 kHz.
External power
required
Page 19
FW_F133-P_M_v2201-01_EN.docx
3.3.7 MENU 6 - CONTROL
Two control outputs are available to control relays or small valves (max. 50VDC 300mA). It is
advised to use relay 1 (R1) for pump-start and relay 2 (R2) for the valve control.
6
CONTROL
6.1
DELAY TIME
Sets the interval between the switch on of R1 (after receiving the Start
command), and the switch on of R2.
6.2
BEGIN TIME
Sets the interval in which flow should be detected, after the switch on of
R2. Flow is accepted when about two times the number of pulses set at
Setup 2.6 is received withing the BEGIN TIME. When flow is not
sufficient, delivery will be cancelled and R2 closes.
When set as 0.0 seconds, this function is disabled.
6.3
STARTUP TIME
Sets the interval between the completion of the BEGIN TIME and full
operation. There is no check on low flow during STARTUP TIME.
When set as 0.0 second, this function is disabled.
6.4
NO PULSE TIME
During full operation (after STARTUP TIME) flow can be monitored.
Relays will be switched off when no pulses are received during the time

set with Setup 6.5 and 6.6.
When set as 0.0 second, this function is disabled.
6.5
PAUSE
Enables the PAUSE function. When the process is interrupted in full
operation, by pressing the STOP key, the NO PULSE TIME function, a
FLOW RATE ALARM (Setup 2.8 and 2.9), or via STATUS INPUT
(Setup 7.1 and 7.2), the batch will be stopped but can be resumed.
In PAUSED mode R2 will be switched off but R1 remains on.
6.6
RESTART TIME
Sets the interval in which the operator should resume batching when
the unit is in PAUSED mode. When batching is not resumed timely, the
delivery is finished, R1 and R2 are shut off.
When set as 0.0 second, this function is disabled.
6.7
OVERRUN TIME
After switching off R1 and R2, some flow may still be present in the
system because of response time of mechanical parts or run off of
liquid. OVERRUN TIME is the interval during which the detected
overrun flow will still be counted as delivered.
When set as 0.0 second, this function is disabled.
3.3.8 MENU 7 STATUS
With Setup menu 7 the function of the external switches is controlle..
7
STATUS
7.1
STATUS INPUT 1
OFF
START
STOP
CONTINOUSLY
Status input 1 is disabled.
A pulse input starts delivery.
A pulse input stops delivery
Delivery is started when the input is closed and keeps running until
delivery is ready, as long as the input stays closed. When input is
opened during delivery, delivery is stopped and the F133 enters
READY mode. A new delivery can be started by closing input 1 again
after at least 100 ms.
7.2
STATUS INPUT 2
OFF
PAUSE
STOP
BOTH
Status input 2 is disabled.
A pulse input pauses delivery.
A pulse input stops delivery.
A pulse input pauses delivery, a second pulse will stop delivery.
Page 20
FW_F133-P_M_v2201-01_EN.docx
3.3.9 MENU 8 - COMMUNICATION (OPTION)
The F133-P can optionally be equipped with a communication interface using the Modbus protocol
(Type CB/CH/CI/CT). Please consult Appendix C for a more detailed explanation of the protocol,
data types and available registers.
8
COMMUNICATION
8.1
SPEED
This setting is used to set the baud rate and should match the speed
used on the communications bus.
8.2
ADDRESS
This setting is used to configure the bus address of your device on the
communications bus.
8.3
MODE
This setting is used to configure the Modbus communication mode of
your device on the communications bus.
8.4
DATABITS
Sets the number of communication databits. Select 8 for BUS-RTU
and 7 for BUS-ASC.
8.5
PARITY
As required by the connected equipment, set the parity bit.
8.6
COMMUNICATION LOCK
DISABLE
TIMEOUT
FULL
Determines if the unit will remain locked after delivery, until explicitly
released via communication (see Appendix C).
Function disabled.
Unit remains locked for 10 minutes or until communication release.
When no communication is received, the unit will unlock after 10
minutes.
Unit can only be released via communication. During lock, the display

3.3.10 MENU 9 - OTHERS
9
OTHERS
9.1
MODEL
For support and maintenance it is important to have information about
the characteristics of the F133-P. Your supplier will ask for this
information in the case of a serious breakdown or to assess the
suitability of your model for upgrade considerations.
9.2
SOFTWARE VERSION
9.3
SERIAL NO.
9.4
PASSWORD
All SETUP values can be password protected.
This protection is disabled with value 0000 (zero).
A 4 digit password can be programmed, for example 1234.
9.5
TAG-NR
For identification of the unit and communication purposes, a unique
tag number of maximum 7 digits can be entered.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Fluidwell F133 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI