TIS KNX-PORT Owner's manual

  • Hello! I am an AI chatbot trained to assist you with the TIS KNX-PORT Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
This product is a networking convertor
designed to integrate and synchronize devices
working on TIS and KNX standard for maximum
automation and convenience.
PRODUCT INFORMATION
PRODUCT SPECIFICATIONS
Inputs KNX KNX network 2 wires connection
TIS TIS-BUS (RS485) 4 wires connection
KNX Bus (EIB)
Bus voltage 21-30 VDC via the EIB bus
Current Input, EIB <12mA
Power Consumption, EIB <360mW
Protection 2000V ESD protection
TIS Bus``
Number of devices on 1 line Max. 64
Bus voltage 12-32 V DC
Current consumption <50 mA / 24 V DC
Protection Reverse polarity protection
Functions TIS->KNX Control lights ON/OFF, dimmer and shutter
KNX->TIS Control lights ON/OFF, dimmer, shutter, infrared and air condition
Connection terminal KNX Bus Screw terminal 0,2…6mm2
TIS Bus Screw terminal 0,2…4mm2
Dimensions Width × Length × Height 36mm × 64mm × 90mm
Housing
Materials Fireproof ABS
Casing color Gray
IP rating IP 20
TIS KNX GATEWAY
KNX Standard Communicator
INSTALLATION MANUAL
Model: TIS-KNX-PORT
INSTALLATION MANUAL
MODEL : TIS-KNX-PORT
TIS KNX GaTeway
2
www.tiscontrol.com
TIS CONTROL LIMITED
Wanchai, Hong Kong
TIS CONTROL PTY LIMITED
SA , AUSTRALIA
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL.
All of the specification are subject to change without notice.
Mounting Location
Install in a dry, well-ventilated location.
Controllers may emit some mechanical
noise. Take this into account when deciding
on a mounting location.
Data Cable
Use screened, stranded KNX cable and
standard RS485 data cable with four
twisted pairs. Connect devices in a “Daisy
Chain”.
Do not cut or terminate live data cables.
Warranty
We provide a warranty as required by law.
A hologram warranty seal and product
serial number are provided on each device.
Please send the description of the defect
with Product S/N to our dealer network.
Read Instructions
We recommend that you read this
Instruction Manual before installation.
Safety instructions
Electrical equipment should only be
installed and tted by electrically skilled
persons.
Failure to observe the instructions may
cause damage to the device and other
hazards.
These instructions are an integral part of
the product and must remain with the end
customer.
Programming
Advanced programming requires TIS
Device Search software. Advanced
software programming knowledge should
be obtained in the advanced training
courses.
Simple Installation
DIN Rail mount facilitates installation.
INSTALLATION MANUAL
MODEL : TIS-KNX-PORT
TIS KNX GaTeway
3
www.tiscontrol.com
TIS CONTROL LIMITED
Wanchai, Hong Kong
TIS CONTROL PTY LIMITED
SA , AUSTRALIA
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL.
All of the specification are subject to change without notice.
INSTALLATION STEPS
2Mount the device on a DIN rail inside an
approved enclosure.
3Connect KNX Cable to the red and black
KNX terminal.
1Turn off TIS and KNX power supplies.
WARNING! HIGH VOLTAGE
Circuit Breaker
OFF
+
-
KNX cable
D- D+ 24V+
TIS-KNX-PORT
GND
INSTALLATION MANUAL
MODEL : TIS-KNX-PORT
TIS KNX GaTeway
4
www.tiscontrol.com
TIS CONTROL LIMITED
Wanchai, Hong Kong
TIS CONTROL PTY LIMITED
SA , AUSTRALIA
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL.
All of the specification are subject to change without notice.
INSTALLATION STEPS
4Connect cat5e TIS network data cable to
the TIS-BUS port as per the connection
diagram
5Turn on TIS power supply and KNX
Power supply, The module’s PRG green
LED should start blinking.
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
+
-
KNX cable
D- D+ 24V+
TIS-KNX-PORT
GND
KNX cable
To the TIS BUS Network
Cat5e
D- D+ 24V+
TIS-KNX-PORT
GND
Circuit Breaker
ON
INSTALLATION MANUAL
MODEL : TIS-KNX-PORT
TIS KNX GaTeway
5
www.tiscontrol.com
TIS CONTROL LIMITED
Wanchai, Hong Kong
TIS CONTROL PTY LIMITED
SA , AUSTRALIA
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL.
All of the specification are subject to change without notice.
TROUBLESHOOTING
Device PRG LED is not Blinking;
Device not Powered
Reason: Device is not powered on; no TIS-
BUS 24V nor KNX Power supply connected
to the device.
Device PRG RED LED is blinking Reason: Assigning the physical address on
process.
Device Search software can not
communicate with the module
Reason: Could be a short in connection
between devices in TIS BUS network.
/