S5KC Series Quick-Start Guide
Connecting External Battery Cabinet
Up to four external battery cabinets may be connected to the SolaHD S5KC UPS to increase battery run times.
The external battery cabinet (EBC) requires one of the optional EBC cable kits for connection to the UPS. Each optional cable kit
contains the power and communication cables required for operating and monitoring the battery modules. The standard cable kit
lengths are 3.2, 9.8 and 16.4 ft. (1, 3 and 5 meters) to accommodate dierent site installation requirements.
!
WARNING
RISK OF ELECTRIC SHOCK, FIRE AND PERSONAL INJURY HAZARD PRESENT! HIGH VOLTAGE AND CURRENT CAN CAUSE
PERSONAL INJURY AND DEATH.
FAILURE TO OPEN THE EXTERNAL BATTERY CABINET (EBC) DC CIRCUIT BREAKER BEFORE CONNECTING OR
DISCONNECTING THE BATTERY CABLE BETWEEN THE UPS AND EBC FRAMES CAN RESULT IN HAZARDOUS VOLTAGES
AND ENERGY BEING PRESENT BETWEEN THE FRAMES.
To connect an external battery cabinet:
1. BE SURE TO OPEN THE EBC DC CIRCUIT BREAKER. The circuit breaker is on the front bottom of the EBC frame behind the
bottom two bezels.
2. Connect one end of the battery cable to the external battery connector on the rear of the UPS frame.
3. Connect the other end to the closest corresponding port on the rear of the EBC frame, as shown in Figure 1.
4. Install and tighten the grounding screw on the battery cable assembly, on both the UPS and EBC ends. This screw also secures
the cable assembly to the frames to prevent accidental disconnection.
5. For new systems that include an EBC, the EBC communication card should already be installed in the UPS frame (Intelligent
Card Slot Port #3, typically). If it is not provided in the UPS frame, obtain the EBC communication card and insert it into any
open Intelligent Card Slot port (preferably Port #3). Connect the provided EBC communication cable to the UPS and EBC as
shown in Figure 1.
6. Check the EBC DIP switch settings on the top rear of each EBC frame. Verify they are set correctly according to Table 1.
7. Close the EBC DC circuit breaker and replace the bezels back onto the EBC.
Figure 1:
Connecting External Battery Cabinet to the SolaHD S5KC
Communication
Cable
(provided in optional
cable kit sold separately
from EBC & UPS)
(provided in optional
cable kit sold separately
from EBC & UPS)
SolaHD S5KC
Transformer-Based
SolaHD S5KC
No Transformer
Battery
Cabinet
Battery
Cable
Battery
Cabinet
United States: 1.800.377.4384 | Asia/Pacic: + 65.6891.7600 | Australia: + 61.3.9721.0348
Brazil: São Paulo/SP + 55.11.2122.5777 | Brazil: Camaçari/BA + 55.71.3496.4427 | Canada: + 1.888.765.2226 China: +
86.21.3418.3888 | Europe: + 33.3.2254.1390 | Mexico/Latin America: + 52.55.5809.5049
Middle East/Africa/India: + 971.4.811.8100
www.solahd.com
S5KC Series Quick-Start Guide
P/N: A272-261 Rev. 0 05/2015
While every precaution has been taken to ensure the accuracy and completeness of this literature, SolaHD Corporation assumes
no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2015 SolaHD Corporation. All rights reserved throughout the world. Specications subject to change without notice.
® SolaHD is a registered trademark of SolaHD Corporation. All names referred to are trademarks or registered trademarks of
their respective owners.
Appleton Grp LLC d/b/a Appleton Group. The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Ofce.
All other product or service names are the property of their registered owners. © 2015, Appleton Grp LLC. All rights reserved.
If the number displayed is not consistent with the actual installation number of external battery cabinets:
• Ensure each external battery cabinet contains two battery modules installed on the same row and both have the locking
levers in the locked position.
• Ensure that the SolaHD Intelligent Card Slot EBC card is installed properly and the communication cables are fully inserted in
the connectors.
• Determine that the DIP switch setting of each battery cabinet is correct using the following table.
Figure 2:
Battery screen
Battery
SolaHD S5KC
2015-05-05
01:21:44
Batt temp (°C)
Discharge count
Discharge hour (H)
Ext batt-cab count
25.0
303
9.4
0
After connecting the external battery cabinet, use the user interface to determine the number of external battery cabinets, as
shown in Figure 2.
Table 1: EBC DIP Switch Settings
External Battery
Cabinet Number
DIP Switch Setting
1 2
EBC #1 Down Down
EBC #2 Up Down
EBC #3 Down Up
EBC #4 Up Up
Note: On the DIP Switch, Down is On and Up is o.
1. Longer run-time options may be available by using our S5KC-LRT-CONN-KIT. Please contact Technical Services at
(800) 377-4384 option 2 to discuss application needs and with additional questions or visit our website.
2. Up to four EBCs can be installed per UPS system utilizing a single EBC communication card. EBCs ordered separately do not
come supplied with an EBC communication card. Please order separately.