Vanner RE Series Owner's manual

Category
Battery chargers
Type
Owner's manual

This manual is also suitable for

4282 Reynolds Drive
Hilliard Ohio, 43026
1(800) ACPOWER
www.vanner.com
RE SERIES
Renewable Energy True Sine Wave
AC Power Inverter/Charger
Owners Manual
RE-4500
RE-4500RE-4500
RE-4500
MULTI-MODE ALTERNATIVE ENERGY INVERTER
AC Power Inverter System
INVERTER
CHARGER
TEMPERATURE
GENERATOR
BATTERY
UTILITY
ON
OFF
CAUTION - Risk of Electric Shock, Do Not Remove Cover. No User Serviceable Parts Inside. Refer Servicing To Qualified Service Personnel.
CAUTION - Risk of Electric Shock, Both AC and DC Voltage Sources Are Terminated Inside This Equipment. Each Circuit Must Be Individually
Disconnected Before Servicing.
Models decribed
RE24-4500
RE48-4500
Part #D99988
07/17/01 12:20 PM
Revision 1.0
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Notes
Contents
i
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Contents
1 Introduction.............................................................................................................1-1
2 Specifications and Features ..................................................................................2-1
Standard Features....................................................................................................2-5
Parts and Accessories..............................................................................................2-6
3 Important Safety Instructions................................................................................3-1
Safety Instructions....................................................................................................3-3
General Precautions.................................................................................................3-4
Explosive Gas Precautions.......................................................................................3-5
Battery Precautions ..................................................................................................3-5
Code Compliance.....................................................................................................3-6
4 Component Identification.......................................................................................4-1
5 System Operation Description...............................................................................5-1
Modes of Operation..................................................................................................5-5
Inverting................................................................................................................................5-5
Load Demand (Load Discover).....................................................................................................5-5
Small Inverting..............................................................................................................................5-6
Normal Inverting...........................................................................................................................5-6
Surging..........................................................................................................................................5-6
Browning Out................................................................................................................................5-6
Low Battery Shutdown..................................................................................................................5-7
Charging...............................................................................................................................5-8
Battery Temperature Sensor................................................................................................5-9
Generator Start Option.......................................................................................................5-10
Grid Interactive...................................................................................................................5-11
Surplus Power....................................................................................................................5-11
Generator Support..............................................................................................................5-12
Generator Start and Grid-Interactive..................................................................................5-12
Set Current.........................................................................................................................5-12
Bypass................................................................................................................................5-13
System Control.......................................................................................................5-13
On/Off Switch .....................................................................................................................5-13
Inverter Charger Control.....................................................................................................5-14
Inverter/Charger Controller......................................................................................................5-14
Display and Key Functions ..........................................................................................................5-15
Moving Around the RE-ICC Menus..............................................................................................5-16
Turning The Inverter / Charger On and Off..................................................................................5-17
Menu Functions ...........................................................................................................................5-18
Display Menu...............................................................................................................................5-24
6 Preventive Maintenance and Trouble Shooting Procedures............................... 6-1
Preventive Maintenance ...........................................................................................6-1
Trouble Shooting Procedures ...................................................................................6-1
Preliminary Checks...................................................................................................6-2
Problem Symptoms and Troubleshooting Checks.....................................................6-3
Appendix A: Warranty........................................................................................................ 1
Appendix B: RE-ICC Menus............................................................................................... 1
Appendix C: Settings ......................................................................................................... 1
Alarm Listing................................................................................................................ 1
Calibration Data........................................................................................................... 2
RE Owners Manual
ii
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Appendix D: Application Notes..........................................................................................1
Application Notes..........................................................................................................1
Applicable Documents..................................................................................................1
List of Tables
Table 2-1: RE-4500 Inverter/Charger Specifications.......................................................... 2-1
Table 4-1: Relay Configurations for Relay A...................................................................... 4-7
Table 4-2: Relay Configurations for Relay B...................................................................... 4-7
Table 4-3: Relay Configurations for Relay C......................................................................4-8
Table 4-4: Relay Configurations for Relay D......................................................................4-8
List of Charts
Chart 2-1: Inverter Power De-Rating Chart* ...................................................................... 2-3
Chart 2-2: Output Current Surge Fault Response Time @ 25°C*...................................... 2-3
Chart 2-3: Current Regulation (Brownout) Mode Shutdown Time...................................... 2-4
Chart 5-1: Output Current Surge Fault Response Time @ 25°C*......................................5-6
Chart 5-2: Current Regulation (Brownout) Mode Shutdown Time......................................5-7
List of Figures
Figure 4-1: Inverter/Charger Front and Side View............................................................. 4-1
Figure 4-2: Inverter/Charger Front Panel Indicators........................................................... 4-3
Figure 4-3: DC Raceway Terminations..............................................................................4-6
Figure 4-4: AC Raceway Terminations.............................................................................. 4-6
Figure 5-1: Block Diagram.................................................................................................5-2
Figure 5-2: Inverter/Charger Controller............................................................................5-15
Figure 5-3: RE-ICC Menus.............................................................................................. 5-19
Figure 5-4: Main Menu.................................................................................................... 5-20
Figure 5-5: Inverter Menu................................................................................................ 5-21
Figure 5-6: Display Menu ................................................................................................ 5-25
Introduction
1-1
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
1 Introduction
Thank you for purchasing a Vanner RE-4500 Renewable
Energy Inverter System. We are confident that you will be
satisfied with its performance and its many features. With
proper installation and care, you can look forward to years of
service from this high performance product.
RE-4500” stands for Renewable Energy 4500 Watt, Inverter
System. The specific model numbers covered in this document
are the “RE48-4500” and “RE24-4500” which designate
48VDC or 24VDC respectively.
The RE SERIES is a family of dependable inverters designed
to meet the service requirements of the Renewable Energy
market and produce true sine wave AC output power.
This document will describe the operation and technical
specifications of the RE24-4500 and accessories offered in this
product family. We suggest that you acquaint yourself with this
model inverter/charger and any optional accessories that you
have purchased before proceeding with this manual. If you
require additional information please contact your dealer, or
contact us directly at 1-800-227-6937 (800 AC POWER).
WARNING: Before you install and use your RE SERIES Inverter/Charger be sure
to read and save these safety instructions.
WARNING: The RE-4500 is not designed to be a part of Life Supporting or Life
Sustaining Equipment. If the Unit is to be used in such an
application, please contact Vanner Inc. at 1-800-ACPOWER.
The RE SERIES product line is designed to meet the
requirements of a variety of applications.
RE Owners Manual
1-2
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Save these instructions!
Please note your model and serial number here for future
reference.
Model No.
Serial No.
Date of Installation
This document describes the operation, technical specifications
and installation procedures for the RE-4500 Inverter/Charger
System. If you require additional information please contact
your dealer or contact Vanner at 1-800-AC POWER (1-800-
227-6937).
Specifications and Features
2-1
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
2 Specifications and Features
AC Power Output (Inverter Output)
Rated Output Watts (-40 to +25°C) 4500 Watts
Continuous Output at 25°C (77°F) 4500 Watts
Continuous Output at 40°C (104°F) 3650 Watts
Continuous Output at 50°C (122°F) 3250 Watts
Continuous Output at 60°C (140°F) 3200 Watts
Max Continuous Output on L1 or L2 26.5 Amps (Electronically current
limited)
3 Second Surge Output (at 24 VDC input, and 25ºC) 10000 VA
AC Maximum Output Fault Current 56.25 Arms
(Inverter shuts down in 1/60 sec)
Output Waveform True Sine Wave
Output Voltage, Single Phase, 3 Wire 120/240 Vrms ±5.0%
Output Frequency 60 Hz ± 0.01 Hz
Power Factor -1 to 1
Charging or Grid Interactive Power Factor Unity
% of Rated Charger Current Available at Full Charger
Voltage 100%
Total Harmonic Distortion (THD) 5% Maximum
AC Output Wiring Method Hardwire Terminal Strip
AC Transfer Switch
Amperage Rating 30 Amp 240 Volt
Transfer Speed (a function of load) 16 milliseconds to 0.5 second
(approx.)
From Inverter to Utility Power 16 ms
From Utility Power to Inverter w/ Grid Tie Enabled 1 second
From Utility Power to Inverter w/ Grid Tie Disabled 40 ms
Table 2-1: RE-4500 Inverter/Charger Specifications
RE Owners Manual
2-2
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
AC Operating Ratings
AC Operating Voltage (Utility Interactive) 211.8 to 264 Vrms
AC Operating Voltage (Stand-alone) 211.8 to 264 Vrms
AC Maximum Output Current 18.75 Arms
AC Maximum Output Fault Current
(Measured when L1 is shorted to L2.) 56.25 Arms
AC Maximum Input Current
(From grid when charging) 30 amp APM rating
18.75 Arms for Inverter/Charger
AC Operating Frequency Range 59.75 Hz to 60.25 Hz
Output Neutral to Ground Not Bonded
(Good AC wiring practice dictates
that bonding between neutral and
ground should take place in the AC
distribution panel only.)
Charger
Maximum Charge Current Supported 100 ADC
Types of Charge supported Bulk, Absorption, Float, and Equalize
Types of Batteries Supported Lead Acid: Flooded-Cell, GEL, or
AGM
DC Input Voltage (Inverter Input)
DC Input Voltage Range 21.0 to 31.0 VDC - RE24-4500
41.0 to 62.0 VDC - RE48-4500
DC Input Current at 24VDC (Inverter Input)
Inverter OFF 1 ma
Inverter in Load Demand (No AC load) 0.5 amps
Inverter ON with no AC load 2.0 amps
Inverter with full load at 22VDC (4500W @ 25°)225 amps
System
Generator Start & Low Battery Warning Control Relays
Rating 2 Amps 120 VAC / 2 Amps up to
100VDC
Efficiency 80% Nominal (at 22VDC for 24V
System, full load, at 44VDC for 48V
System, full load)
90% peak
Ambient Operating Temperature -40° to +40°C (-40 to +104°F) (to
+60°C (+140°F) with de-rated
output)
Cooling Air Thermostatically Controlled Fan
Enclosure Powder-Coated Aluminum / Wall
Mounting
Dimensions 29½ H x 20½ W x 9¼ D
Unit Weight 95 pounds
Specifications and Features
2-3
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Temperature in Degrees C
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
Watts (Output)
Operating Range
-50 -40-30 -20 -10 0 10 20 30 40 50 60 70 80
18.75 Arms
28.13 Arms
37.50 Arms
56.25 Arms
79.55 Arms
0.0000514
Seconds
10
Seconds 3
Seconds 1 Second .01667
seconds
Indefinitely
*Note: The RE-4500 Inverter will try to power the load as per the chart
above. When the load exceeds the inverter's rated output the
Inverter/Charger Indicator LED will turn Orange. The current limit
circuit will operate in the manner indicated above, and will reduce the
AC Output Voltage as needed to keep the AC Output Current from
exceeding specifications. If the output voltage is outside the limits
shown in Chart 2-3, the inverter will shut off and the Inverter/Charger
LED will turn Red.
Chart 2-1: Inverter Power De-Rating Chart*
Chart 2-2: Output Current Surge Fault Response Time @ 25°C*
RE Owners Manual
2-4
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
254 Vrms
330 Vrms
420 Vrms
Indefinitely 10
Seconds .033
Second .01667
Second
211 Vrms
120 Vrms
60 Vrms
10
Seconds
.033
Second
.01667
Second
Chart 2-3: Current Regulation (Brownout) Mode Shutdown Time
Specifications and Features
2-5
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Standard Features True sine wave single phase 3 wire 240 VRMS output.
Unity Power Factor Corrected Battery Charger for less AC
Input Distortion, accommodating Lead Acid, Flooded-Cell,
GEL, and AGM types of batteries.
True single phase three wire 240VRMS output that can be
used with Multiwire branch circuits, without needing the
load rewiring (required by many single phase inverters).
Total harmonic distortion less than 5% for all loads up to
the Surge Output Rating.
Reliable electronic protection designed to handle output
short-circuits and output overloads.
Terminal block for hardwiring the AC outputs.
Automatic shutoff for low or high battery voltage,
overload, or over-temperature.
Relay Output circuits, providing Normally Open (NO) and
Normally Closed (NC) control for activating external
devices and alarms.
Indicator lights for Inverter, Temperature, Battery,
Generator, and Utility status.
Thermostatically controlled cooling fan.
RE Owners Manual
2-6
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Parts and Accessories
Part
Number Name Description
RE-ICC/LCD Remote Display Inverter/Charger Controller – changes and
displays the programmable settings inside the
RE-4500.
RE24-4500S 24V RE-4500 with a
Small Inverter Board This option enables greater efficiency when the
inverter is providing power for a light load (less
than 75 watts).
RE-ACM AC Control Module Includes most requirements for utility, load,
bypass, and AC generator connections, breakers,
and switches in a convenient assembly.
RE-DCM
Models:
RE48-DCM
RE24-DCM
DC Control Module Includes most requirements Solar, Battery,
Auxiliary DC Loads, Charge Controllers,
Disconnects, and connections for the DC source
and loads in a convenient assembly.
RE-BTS1 B/T Sensor Battery Temperature Sensor – an optional sensor
available to more accurately monitor the
condition of batteries in the system.
RE-SLM
Model:
RE48-SLM
Sun Lynx Module Configures the system for “battery-less
operation”. This module is used to connect to
the Solar Array instead of the RE-DCM used in
a Battery populated system.
Important Safety Instructions
3-1
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
3 Important Safety Instructions
WARNING: Before you install and use your RE-SERIES AC Power Inverter, read
and save these safety instructions!
This manual contains important safety and operating
instructions for the Vanner Incorporated RE-4500 Power
Inverter that shall be followed during installation and
maintenance of the inverter as prescribed by Underwriters
Laboratories (UL). The RE-4500 inverter is listed as compliant
with UL 1741 Power Conditioning Units for use in Residential
Photovoltaic Power Systems.
Warning Labels
Please READ ME
It should be noted that hazardous voltages are associated with
this product. This unit has connections to both DC at lethal
amperages and AC at lethal amperages and voltages.
Installation should only be done by qualified personnel and in
compliance with local regulations and codes.
Special care must be taken in working around the RE-4500
Inverter/Charger System in order to avoid hazardous voltages
and currents.
NOTE: In order to reduce the risk of damage to personnel or equipment,
please read all instructions in this manual, particularly warnings
noted by the following symbols.
RE Owners Manual
3-2
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
These symbols are used to note procedures that if not closely
followed could lead to loss of life or damage to equipment or
property due to electrocution.
Electrocution hazard exists
Fire hazard exists
A potentially dangerous
condition
Explosive hazard exists
Corrosive hazard exists
The following are additional symbols used in identifying other
aspects of the RE-4500.
AC
This symbol denotes AC Voltage is
potentially present on this termination.
DC Voltage
This symbol denotes DC Voltage is
potentially present on this termination.
L1 Phase 1
This symbol denotes that this termination
is used for the upper phase of a 240 Vrms
3 wire system consisting of Phase 1
(Black wire), Neutral (White wire), and
Phase 2 (Red wire).
Important Safety Instructions
3-3
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
NNeutral
This symbol denotes that this termination
is used for the middle wire of a 240 Vrms
3 wire system consisting of Phase 1
(Black wire), Neutral (White wire), and
Phase 2 (Red wire).
L2 Phase 2
This symbol denotes that this termination
is used for the lower phase of a 240 Vrms
3 wire system consisting of Phase 1
(Black wire), Neutral (White wire), and
Phase 2 (Red wire).
GND Ground
This symbol denotes that this termination
is used for a ground connection (Green
wire).
Safety Instructions
Caution
Read owners manual BEFORE wiring or powering up the RE-4500.
Caution
DO NOT cover or obstruct ventilation openings. DO NOT mount in
a zero-clearance compartment. Overheating may result.
Warning
Under high ambient temperature / high-power-output conditions
some parts of the inverter may become hot enough to cause
burns. The unit should be installed so that it is not to be contacted
by personnel.
Warning
This equipment employs components that tend to produce arcs
and sparks. To prevent fire or explosion, DO NOT install in
confined areas or compartments that contain batteries or
flammable gases and materials.
Warning
Improper use of this product may result in risk of electrical shock.
Both AC and DC voltage sources are terminated inside this
equipment.
RE Owners Manual
3-4
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Battery connections are for disconnection only, NOT for current
interruption.
General Precautions Do not expose the inverter/charger to direct water spray, rain, or
snow.
To reduce the risk of a fire hazard, do not cover or obstruct the
ventilation openings.
Do not install the inverter in a zero clearance compartment. This
may result in overheating and/or diminished performance.
To avoid the risk of fire, electrical shock, or injury to persons, do
not use attachments not recommended or sold by Vanner
Incorporated.
Vanner recommends that all AC and DC electrical wiring be
performed by a licensed electrician or a qualified technician to
ensure compliance with all applicable national and local wiring
regulations.
To avoid a risk of fire and/or electrical shock, always verify wiring
connections are in good electrical condition. All external
conductors must use proper wire size to avoid dangerous
overheating and/or diminished performance.
If the inverter has been dropped or damaged in any way, do not
operate the inverter until it has been verified to be safe by a
qualified technician.
To reduce the risk of electrical shock, always disconnect the AC
and DC connections using the code required AC and DC
disconnects. The On/Off switch only turns off the Inverter
electronics. Dangerous AC and DC Voltages Are Still Present!
The inverter must be properly grounded in accordance with local
and national codes and ordinances before operation. For most
installations, the negative (ground) conductor should be bonded
to the grounding system at one and only one point in the system.
For optimum inverter/charger performance, battery temperature
should be above 32 degrees Fahrenheit.
Important Safety Instructions
3-5
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Do not disassemble the inverter/charger. See the service section
of this manual for instructions on obtaining service. Attempting
to service the inverter yourself may result in a risk of electrical
shock, fire and/or loss of warranty.
Always use service disconnects to break the circuit before
attempting any kind of servicing of the RE-4500. DO NOT attempt
to service the unit while still actively connected to a power
source of any kind.
Explosive Gas Precautions
This equipment contains components, which tend to produce arcs
or sparks. To prevent fire or explosion, do not install in
compartments containing batteries or flammable materials, or in
locations that require ignition protected equipment. This includes
any space containing gasoline-powered machinery, fuel tanks, or
joints, fittings, or other connections between components of the
fuel system.
To reduce the risk of battery explosion, follow these instructions,
the battery manufacturer instructions, and the instructions of the
manufacturer of the equipment in which the battery is installed.
Working near a lead-acid battery is dangerous. Batteries generate
explosive gases during normal battery operation.
Battery Precautions
Always have someone within range of your voice to come to your
aid when you work near a lead-acid battery.
Have close access to plenty of fresh water and soap in case
battery acid contacts skin, clothing, or eyes.
Always wear complete eye protection and clothing protection.
Avoid touching eyes while working near batteries.
If battery acid contacts skin or clothing, wash immediately with
soap and water. If acid enters eye, immediately flood eye with
running cold water for at least 20 minutes. Get medical attention
immediately.
NEVER smoke or allow a spark or flame near a battery. Gases
produced by batteries are explosive.
RE Owners Manual
3-6
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Be careful when working with metal tools around batteries.
Potentials exist for sparks or short-circuit of the battery or other
electrical part which could cause an explosion.
Before attempting any sort of wiring for the DC supply to the
Inverter, turnoff the DC disconnect associated with the Batteries.
For Safety, ALWAYS check the operation of the disconnect with a
voltmeter!
In addition to the lethal current associated with the batteries, care
must be taken to avoid any potential problems or explosions from
the batteries. ALWAYS comply with the battery manufacturer’s
and local code requirements/guidelines for the installed battery
system.
Code Compliance Vanner Model RE-4500 is certified by Underwriter’s
Laboratory to meet UL listing 1741 for Photovoltaic Systems,
and complies with IEEE 929 and the National Electric Code
Article 690, Solar Photovoltaic Systems.
Component Identification
4-1
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
4 Component Identification
This section will give the reader an idea as to location and
description of various features of the RE-4500.
Note that at the top of the unit there is a parallel raceway with
terminations for connecting DC Power and Control Wiring.
The bottom of the unit contains another parallel raceway for
AC Power Wiring connections.
Left View Right View
3
3
12
1 2
28 28
Front View
RE-4500
RE-4500RE-4500
RE-4500
MULTI-MODE ALTERNATIVE ENERGY INVERTER
AC Power Inverter System
INVERTER
CHARGER
TEMPERATURE
GENERATOR
BATTERY
UTILITY
ON
OFF
CAUTION - Risk of Electric Shock, Do Not Remove Cover. No User Serviceable Parts Inside. Refer Servicing To Qualified Service Personnel.
CAUTION - Risk of Electric Shock, Both AC and DC Voltage Sources Are Terminated Inside This Equipment. Each Circuit Must Be Individually
Disconnected Before Servicing.
8910
12
14
28
29 11
467 5
13
11
Figure 4-1: Inverter/Charger Front and Side View
RE Owners Manual
4-2
Copyright 2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
(1) Knockout for High Current DC Wiring
This knockout provides for the routing and termination of high
capacity DC cables from batteries, RE-SLM, RE-DCM to the
RE-4500 Inverter/Charger.
This knockout provides access (from either the right side or the
left side of the inverter) to the DC Wiring Raceway.
This knockout matches up with the high capacity DC knockout
on Vanner accessories such as the DC Control Module (RE-
DCM), the RE48-SLM (Sun Lynx Module), and the AC
Control Module (RE-ACM). This is a standard size 2 ½”
conduit knockout.
(2) Knockout for Low Current DC Control Wiring
These knockouts provide for the routing and termination of
low capacity DC Control Wiring.
These knockouts provide access (from either the right side or
the left side of the inverter) to the DC Wiring Raceway.
These knockouts match up with the low current DC/Control
knockouts on Vanner accessories such as the DC Control
Module (RE-DCM), the RE-SLM (Sun Lynx Module), and the
AC Control Module (RE-ACM). This is a standard size ¾”
conduit knockout.
(3) Knockout for AC Wiring This knockout provides for the routing and termination of AC
Wiring.
This knockout provides access (from either the right side or the
left side of the inverter) to the AC Wiring Raceway.
This knockout matches up with the AC knockout on Vanner
accessories such as the AC Control Module (RE24-ACM), the
RE48-SLM (Sun Lynx Module), and the DC Control Module
(RE24-DCM). This is a standard size 1 ¼ “ conduit knockout.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171