ZIEHL STWA1H Operating instructions

Type
Operating instructions

ZIEHL STWA1H is a current transformer designed to work with current relays for AC current detection and control systems for STW plants. It features an LED indicator that lights up when the current exceeds approximately 2 A, indicating the presence of current. The device can be connected to a ZIEHL STW current relay or an external LED, and has a built-in resistor to protect the LED from overload. It can be mounted on a DIN rail or with screws, and the maximum diameter of the monitored line is 11 mm. The electrical connection is made via screwless pluggable terminals.

ZIEHL STWA1H is a current transformer designed to work with current relays for AC current detection and control systems for STW plants. It features an LED indicator that lights up when the current exceeds approximately 2 A, indicating the presence of current. The device can be connected to a ZIEHL STW current relay or an external LED, and has a built-in resistor to protect the LED from overload. It can be mounted on a DIN rail or with screws, and the maximum diameter of the monitored line is 11 mm. The electrical connection is made via screwless pluggable terminals.

ZIEHL industrie elektronik GmbH + Co KG
Daimlerstraße 13, D 74523 Schwäbisch Hall
+ 49 791 504-0, in[email protected], www.ziehl.de
Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection
Operating Manual STWA1H
updated: 2018-12-18/Fu
STWA1H 12000-0706-04 Page
1
/ 4 www.ziehl.de
- Current-Transformer
Table of contents
1 Application and Short Description ........................................................................................................ 1
2 Overview of Functions ........................................................................................................................... 2
3 Important Information ............................................................................................................................ 2
4 Detailed Description ............................................................................................................................... 3
5 Assembly ................................................................................................................................................ 3
6 Technical Data ........................................................................................................................................ 3
7 Example for connection ......................................................................................................................... 4
8 Design H .................................................................................................................................................. 4
1 Application and Short Description
The STWA1H current transformer is made to match the current-relays for recognition of AC-current and for
controls for deducting plants type STW. Above app. 2 A the built-in LED lights and indicates a current. A
current-relay type STW or a LED can be connected to the terminals.
The STWA1H has been designed for mounting in a switchgear cabinet. The housing can be fixed on a DIN-
rail or with 2 screws.
The maximum diameter of the monitored line is 11 mm. The current is only limited by the diameter that can be
lead through the transformer. The electrical connection is made via screwless pluggable terminals.
STWA1H 12000-0706-04 Seite
2
/ 4 www.ziehl.de
2 Overview of Functions
connection to current-relays type STW
indication with LED from app. 2 A
indication of shortest current-pulses
Built-in resistor to protect LED
no supply-voltage required
electrical connection via screwless pluggable terminals
plug-in current transformer (Ø 11 mm)
3 Important Information
To use the equipment flawless and safe, transport and store properly, install and start professionally and
operate as directed.
Only let persons work with the equipment who are familiar with installation, start and use and who have
appropriate qualification corresponding to their function. They must observe the contents of the
instruction’s manual, the information which are written on the equipment and the relevant security
instructions for the setting up and the use of electrical units.
The equipment is built according to DIN / EN and checked and leave the plant according to security in
perfect condition. If, in any case the information in the instruction’s manual is not sufficient, please contact
our company or the responsible representative.
Instead of the industrial norms and regulations written in this instruction manual valid for Europe, you must
observe out of their geographical scope the valid and relevant regulations of the corresponding country.
DANGER!
Hazardous voltage!
Will cause death or serious injury. Turn off and lock out all power
supplying this device before working on this device.
DANGER!
In a non-loaded (open) secondary circuit of the current transformer STWA1H high
voltages are induced at the secondary terminals.
For primary currents > 16 A, this voltage can be dangerous for human beings.
An "open mode", i.e. operation of the current transformer without secondary wiring,
should be avoided.
Attention!
There may only one conductor be lead through the transformer!
Attention!
The connecting cable can be extended up to 50 m. When laying parallel to
power cables use twisted or shielded cables.
STWA1H 12000-0706-04 Seite
3
/ 4 www.ziehl.de
4 Detailed Description
Electronic current transformers type STWA1H are simply pushed over the conductor. A built-in and if
connected a external LED lights up at an AC-current > app. 2 A. With these LEDs shortest current-pulses can
be indicated.
At the terminals a ZIEHL current-relay type STW or an external LED can be connected. A built in resistor
protects the LED from overload.
Multiple loops of the conductor through the transformer reduces the limit accordingly, for instance to 0,5 A
with 2 loops.
The electronics in the transformers is supplied from the signal of the transformer. Thus no extra supply-
voltage is required.
Hints:
STWA1H too insensitive (current too low):
Multiple loops of the conductor through STWA1H reduces limit accordingly
STWA1H too sensitive (current of a base load shall be suppressed):
Connect resistor (0,25 W / 200 V) in parallel to the input of the affected transformer
Resistance 750 Ω = increase by factor 2
Resistance 330 Ω = increase by factor 4
Resistance 120 Ω = increase by factor 10
It is recommended to find out the optimal value by testing.
5 Assembly
The STWA1H can be assembled as follows:
just push it over the monitored conductor without fixing it
with the included mounting clip:
on 35 mm DIN-rail according to EN 60 715
surface-mount with 2 screws (M4)
6 Technical Data
Output
Possible connectivity’s: external LED
ZIEHL current-relay type STW
Switching Point LED app. 2 A
Frequency 50 - 60 Hz
Test Conditions EN 61010
Rated impulse withstand voltage 4000 V
Overvoltage category III
Pollution degree 2
Rated insulation voltage Ui 250 V
On-period 100 %
Rated ambient temperature range 0 ... 55 °C
EMC-immunity EN 61326 (industrial electromagnetic environment)
EMC-emission EN 61326 CISPR 11 class B
Vibration resistance EN 60068-2-6 2...25 Hz ±1.6 mm
25...150 Hz 5 g
Housing design H
Line connection each 1 x 0.08 mm
2
to 1.5 mm
2
protection terminals IP 20
Mounting position any
Weight approx. 90 g
Subject to technical changes
STWA1H 12000-0706-04 Seite
4
/ 4 www.ziehl.de
7 Example for connection
LED external
8 Design H
Dimensions in mm
1. Base
2. Clip for DIN-rail
3. Terminal (pluggable)
4. Surface-mount (M4)
32
35,2
35,5
ø11
1
2
17,5
3,5
41,8
56,6
3
22
50,5
27
4
18
4
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

ZIEHL STWA1H Operating instructions

Type
Operating instructions

ZIEHL STWA1H is a current transformer designed to work with current relays for AC current detection and control systems for STW plants. It features an LED indicator that lights up when the current exceeds approximately 2 A, indicating the presence of current. The device can be connected to a ZIEHL STW current relay or an external LED, and has a built-in resistor to protect the LED from overload. It can be mounted on a DIN rail or with screws, and the maximum diameter of the monitored line is 11 mm. The electrical connection is made via screwless pluggable terminals.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI