Beckhoff KS2012 User manual

  • Hello! I am an AI chatbot trained to assist you with the Beckhoff KS2012 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Documentation | EN
KL2xxx and KS2xxx
Digitale output terminals
10.09.2020 | Version: 3.0.0
Table of contents
KL2xxx and KS2xxx 3Version: 3.0.0
Table of contents
1 Foreword ....................................................................................................................................................5
1.1 Notes on the documentation..............................................................................................................5
1.2 Safety instructions .............................................................................................................................6
1.3 Documentation issue status ..............................................................................................................7
2 Product overview.......................................................................................................................................8
2.1 KL2xxx terminal overview..................................................................................................................8
2.2 KL2012, KL2022, KL2032 - Introduction ...........................................................................................8
2.2.1 KL2012, KL2022, KL2032 - Technical data ..................................................................... 10
2.2.2 KL2012 - LEDs and connection ....................................................................................... 11
2.2.3 KL2022 - LEDs and connection ....................................................................................... 12
2.2.4 KL2032 - LEDs and connection ....................................................................................... 13
2.3 KL2114, KL2134 - Introduction........................................................................................................14
2.3.1 KL2114, KL2134 - Technical data ................................................................................... 15
2.3.2 KL2114 - LEDs and connection ....................................................................................... 16
2.3.3 KL2134 - LEDs and connection ....................................................................................... 17
2.4 KL2404, KL2424 - Introduction........................................................................................................18
2.4.1 KL2404, KL2424 – Technical data................................................................................... 19
2.4.2 KL2404 - LEDs and connection ....................................................................................... 20
2.4.3 KL2424 - LEDs and connection ....................................................................................... 21
2.5 KL2408, KL2488 - Introduction........................................................................................................22
2.5.1 KL2408, KL2488 – Technical data................................................................................... 23
2.5.2 KL2408 - LEDs and connection ....................................................................................... 24
2.5.3 KL2488 - LEDs and connection ....................................................................................... 25
3 Mounting and wiring................................................................................................................................26
3.1 Installation on mounting rails ...........................................................................................................26
3.2 Installation instructions for enhanced mechanical load capacity .....................................................29
3.3 Connection system ..........................................................................................................................29
3.4 ATEX - Special conditions (extended temperature range) ..............................................................33
3.5 Continuative documentation about explosion protection .................................................................34
4 TwinCAT ...................................................................................................................................................35
4.1 Programming ...................................................................................................................................36
5 Appendix ..................................................................................................................................................37
5.1 Support and Service ........................................................................................................................37
Table of contents
KL2xxx and KS2xxx4 Version: 3.0.0
Foreword
KL2xxx and KS2xxx 5Version: 3.0.0
1 Foreword
1.1 Notes on the documentation
Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under
development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff
®
, TwinCAT
®
, EtherCAT
®
, EtherCATG
®
, EtherCATG10
®
, EtherCATP
®
, SafetyoverEtherCAT
®
,
TwinSAFE
®
, XFC
®
, XTS
®
and XPlanar
®
are registered trademarks of and licensed by Beckhoff Automation
GmbH. Other designations used in this publication may be trademarks whose use by third parties for their
own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 with corresponding
applications or registrations in various other countries.
EtherCAT
®
is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.
Copyright
© Beckhoff Automation GmbH & Co. KG, Germany.
The reproduction, distribution and utilization of this document as well as the communication of its contents to
others without express authorization are prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a
patent, utility model or design.
Foreword
KL2xxx and KS2xxx6 Version: 3.0.0
1.2 Safety instructions
Safety regulations
Please note the following safety instructions and explanations!
Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.
Description of instructions
In this documentation the following instructions are used.
These instructions must be read carefully and followed without fail!
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Tip or pointer
This symbol indicates information that contributes to better understanding.
Foreword
KL2xxx and KS2xxx 7Version: 3.0.0
1.3 Documentation issue status
Version Comment
3.0.0 Migration
Structure update
Technical data updated
Installation instructions for enhanced mechanical load capacity added
Revision status updated
Firmware and hardware versions
Documentation
Version
KL2012 KL2022 KL2032 KL2114
Firmware Hardware Firmware Hardware Firmware Hardware Firmware Hardware
3.0.0 - 05 - 09 - 05 - 05
Documentation
Version
KL2134 KL2404 KL2424 KL2408
Firmware Hardware Firmware Hardware Firmware Hardware Firmware Hardware
3.0.0 - 09 - 06 - 05 - 07
Documentation
Version
KL2488
Firmware Hardware
3.0.0 - 03
The K-bus firmware and hardware version (delivery state) are indicated by the serial number printed at the
side of the terminal.
Syntax of the serial number
Structure of the serial number: WWYYFFHH
WW - week of production (calendar week)
YY - year of production
FF - K-bus firmware version
HH - hardware version
Example with ser. no.: 49 05 1B 03
49 - week of production 49
05 - year of production 2005
1B - firmware version 1B
03 - hardware version 03
Product overview
KL2xxx and KS2xxx8 Version: 3.0.0
2 Product overview
2.1 KL2xxx terminal overview
Digital Output Terminals
Terminal Number of outputs Current Comment
KL2012 [}8]
2 0.5A
KL2022 [}8]
2 2.0A
KL2032 [}8]
2 0.5A protected against reverse polarity connection
KL2114 [}14]
4 0.5A
KL2134 [}14]
4 0.5A protected against reverse polarity connection
KL2404 [}18]
4 0.5A
KL2408 [}22]
8 0.5A
KL2424 [}18]
4 2.0A
KL2488 [}22]
8 0.5A ground switching
2.2 KL2012, KL2022, KL2032 - Introduction
Fig.1: KL2012 – 2-channel digital output terminal, 24 V
DC
, 0.5 A
Product overview
KL2xxx and KS2xxx 9Version: 3.0.0
Fig.2: KL2022 – 2-channel digital output terminal, 24 V
DC
, 2 A
Fig.3: KL2032 – 2-channel digital output terminal, 24 V
DC
, 0.5 A, protected against reverse polarity
connection
Product overview
KL2xxx and KS2xxx10 Version: 3.0.0
Two-channel, digital output terminal, 24V
DC
The KL2012, KL2022 and KL2032 digital output terminals connect the binary control signals from the
automation unit on to the actuators at the process level with electrical isolation. The KL2012 and KL2022
versions handle different load currents, and their outputs are protected against overload (only KL2012) and
short circuit. The KL2032 Bus Terminal is protected against reverse polarity connection. The Bus Terminals
contain two channels that indicate their signal state by means of light emitting diodes.
2.2.1 KL2012, KL2022, KL2032 - Technical data
Technical data KL2012, KS2012 KL2022, KS2022 KL2032, KS2032
Connection technology 4 wire
Number of outputs 2
Nominal voltage 24V
DC
(-15%/+20%)
Load type ohmic, inductive, lamp load
Max. output current (per channel) 0.5A (short-circuit
proof)
2.0A (short-circuit
proof)
0.5A (short-circuit
proof)
Max. short-circuit current <2A <70A <2A
Inductive breaking energy max. <150mJ/channel <1.7J/channel <150mJ/channel
Reverse polarity protection no no yes
Electrical isolation 500V (K-bus / field voltage)
Current consumption via K-bus typ. 5mA
Current consumption power contacts typ.15mA + load typ.20mA+load typ.20mA+load
Bit width in process image 2 outputs
Configuration no address or configuration settings required
Dimensions (WxHxD) 15mmx100mmx70mm (width aligned 12mm)
Weight approx. 55g
Permissible ambient temperature
during operation
0°C ... +55°C -25°C ... +60°C
(extended
temperature range)
Permissible ambient temperature
during storage
-25°C ... +85°C -40°C ... +85°C
Permissible relative humidity 95%, no condensation
Vibration / shock resistance according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity
[}29]
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Installation position variable
Protection class IP20
Pluggable wiring for all KSxxxx Bus Terminals
Markings/ Approvals
CE, cULus, ATEX
[}33]
CE, cULus, ATEX [}33], GL
Product overview
KL2xxx and KS2xxx 11Version: 3.0.0
2.2.2 KL2012 - LEDs and connection
Fig.4: KL2012 - LEDs and connection
KL2012 - LEDs
LED Color Meaning
Signal LEDs 1 - 2 green off Signal voltage "0"
on Signal voltage "1"
KL2012 - Connection
Terminal point Description
Name No.
Output1 1 Output 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 Ground for output1 (internally connected to terminal point7 and negative power
contact)
PE 4 PE contact (internally connected to terminal point8 and PE power contact)
Output2 5 Output 2
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 Ground for output2 (internally connected to terminal point3 and negative power
contact)
PE 8 PE contact (internally connected to terminal point4 and PE power contact)
Product overview
KL2xxx and KS2xxx12 Version: 3.0.0
2.2.3 KL2022 - LEDs and connection
Fig.5: KL2022 - LEDs and connection
KL2022 - LEDs
LED Color Meaning
Signal LEDs 1 - 2 green off Signal voltage "0"
on Signal voltage "1"
KL2022 - Connection
Terminal point Description
Name No.
Output1 1 Output 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 Ground for output1 (internally connected to terminal point7 and negative power
contact)
PE 4 PE contact (internally connected to terminal point8 and PE power contact)
Output2 5 Output 2
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 Ground for output2 (internally connected to terminal point3 and negative power
contact)
PE 8 PE contact (internally connected to terminal point4 and PE power contact)
Product overview
KL2xxx and KS2xxx 13Version: 3.0.0
2.2.4 KL2032 - LEDs and connection
Fig.6: KL2032 - LEDs and connection
KL2032 - LEDs
LED Color Meaning
Signal LEDs 1 - 2 green off Signal voltage "0"
on Signal voltage "1"
KL2032 - Connection
Terminal point Description
Name No.
Output1 1 Output 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 Ground for output1 (internally connected to terminal point7 and negative power
contact)
PE 4 PE contact (internally connected to terminal point8 and PE power contact)
Output2 5 Output 2
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 Ground for output2 (internally connected to terminal point3 and negative power
contact)
PE 8 PE contact (internally connected to terminal point4 and PE power contact)
Product overview
KL2xxx and KS2xxx14 Version: 3.0.0
2.3 KL2114, KL2134 - Introduction
Fig.7: KL2114 – 4-channel digital output terminal, 24 V
DC
, 0.5 A
Fig.8: KL2134 – 4-channel digital output terminal, 24 V
DC
, 0.5 A, protected against reverse polarity
connection
Product overview
KL2xxx and KS2xxx 15Version: 3.0.0
Four-channel, digital output terminal, 24V
DC
The KL2114 and KL2134 digital output terminals connect the binary control signals from the automation unit
on to the actuators at the process level with electrical isolation. The load current output of the KL2114
version is protected against overload and short circuit. The KL2134 Bus Terminal is protected against
reverse polarity connection. The Bus Terminals contain four channels that indicate their signal state by
means of light emitting diodes.
2.3.1 KL2114, KL2134 - Technical data
Technical data KL2114, KS2114 KL2134, KS2134
Connection technology 2-wire / 3-wire
Number of outputs 4
Nominal voltage 24V
DC
(-15%/+20%)
Load type ohmic, inductive, lamp load
Max. output current 0.5A (short-circuit proof) per channel
Short circuit current <2A
Breaking energy (ind.) <150mJ/channel
Reverse polarity protection - yes
Electrical isolation 500V (K-bus / field voltage)
Current consumption power contacts typ. 30mA + load
K-Bus current consumption typ. 9mA
Bit width in process image 4 outputs
Configuration no address or configuration settings required
Weight approx. 70g
Permissible ambient temperature
during operation
0°C … +55°C -25°C ... +60°C (extended
temperature range)
Permissible ambient temperature
during storage
-25°C … +85°C -40°C ... +85°C
Permissible relative humidity 95%, no condensation
Vibration / shock resistance according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity
[}29]
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Installation position variable
Protection class IP20
Pluggable wiring for all KSxxxx Bus Terminals
Markings/ Approvals
CE, cULus, ATEX [}33] CE, cULus, ATEX [}33], GL
Product overview
KL2xxx and KS2xxx16 Version: 3.0.0
2.3.2 KL2114 - LEDs and connection
Fig.9: KL2114 - LEDs and connection
KL2114 – LEDs
LED Color Meaning
Signal LEDs 1 - 4 green off Signal voltage "0"
on Signal voltage "1"
KL2114 - Connection
Terminal point Description
Name No.
Output1 1 Output 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 0V (internally connected to terminal point 7 and negative power contact)
Output3 4 Output 3
Output2 5 Output 2
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 0V (internally connected to terminal point 3 and negative power contact)
Output4 8 Output 4
Product overview
KL2xxx and KS2xxx 17Version: 3.0.0
2.3.3 KL2134 - LEDs and connection
Fig.10: KL2134 - LEDs and connection
KL2134 - LEDs
LED Color Meaning
Signal LEDs 1 - 4 green off Signal voltage "0"
on Signal voltage "1"
KL2134 - Connection
Terminal point Description
Name No.
Output1 1 Output 1
+24V 2 +24V (internally connected to terminal point 6 and positive power contact)
0V 3 0V (internally connected to terminal point 7 and negative power contact)
Output3 4 Output 3
Output2 5 Output 2
+24V 6 +24V (internally connected to terminal point 2 and positive power contact)
0V 7 0V (internally connected to terminal point 3 and negative power contact)
Output4 8 Output 4
Product overview
KL2xxx and KS2xxx18 Version: 3.0.0
2.4 KL2404, KL2424 - Introduction
Fig.11: KL2404 – 4-channel digital output terminal, 24 V
DC
, 0.5 A
Fig.12: KL2404 – 4-channel digital output terminal, 24 V
DC
, 2 A
Product overview
KL2xxx and KS2xxx 19Version: 3.0.0
4-channel, digital output terminal, 24V
DC
The KL2404 and KL2424 digital output terminals connect the binary 24V control signals electrically isolated
with the actuators. The Bus Terminals each contain four channels, whose signal states are displayed by
LEDs. The variants KL2404 and KL2424 have different maximum output currents. The 4-channel Bus
Terminals enable the direct connection of four 2-wire sensors. Four ground connection points are provided.
2.4.1 KL2404, KL2424 – Technical data
Technical data KL2404 KL2424
Connection technology 2-wire
Number of outputs 4
Nominal voltage 24V
DC
(-15%/+20%)
Load type ohmic, inductive, lamp load
Max. output current 0.5A (short-circuit proof) per
channel
2.0A (short-circuit proof)
Short circuit current <2A <70A
Breaking energy (ind.) <150mJ/channel <1.7J/channel
Reverse polarity protection yes
Electrical isolation 500V (K-bus / field voltage)
Current consumption power contacts typ. 30mA + load
K-Bus current consumption typ. 9mA
Bit width in process image 4 outputs
Configuration no address or configuration settings required
Weight approx. 70g
Permissible ambient temperature
during operation
-25°C ... +60°C (extended temperature range)
Permissible ambient temperature
during storage
-40°C ... +85°C
Permissible relative humidity 95%, no condensation
Vibration / shock resistance according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity
[}29]
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Installation position variable
Protection class IP20
Approvals
CE, cULus, ATEX [}33] CE, cULus, ATEX [}33], GL
Product overview
KL2xxx and KS2xxx20 Version: 3.0.0
2.4.2 KL2404 - LEDs and connection
Fig.13: KL2404 - LEDs and connection
KL2404 - LEDs
LED Color Meaning
Signal LEDs 1 - 4 green off Signal voltage "0"
on Signal voltage "1"
KL2404 - Connection
Terminal point Description
Name No.
Output1 1 Output 1
0V 2 Ground for output1 (internally connected to terminal point3, 6, 7 and negative power
contact)
0V 3 Ground for output3 (internally connected to terminal point2, 6, 7 and negative power
contact)
Output3 4 Output 3
Output2 5 Output 2
0V 6 Ground for output2 (internally connected to terminal point2, 3, 7 and negative power
contact)
0V 7 Ground for output4 (internally connected to terminal point2, 3, 6 and negative power
contact)
Output4 8 Output 4
/