PRECISION DIGITAL PD603 Quick start guide

  • Hello! I'm a chat assistant, and I have analyzed the Quick Start Guide for the Sabre P PD603 Process Meter by Precision Digital. This document provides instructions on the meter's features, installation, connection and programming. The device has field selectable inputs, NEMA 4X front panel and UL/C-UL Listing for 508 Industrial Control Equipment. I know that there are also wiring diagrams and tips available. I'm here to answer all your questions about the device and the information provided in the guide.
  • What types of input signals does the meter accept?
    Does the meter have any certifications?
    Can the meter power a transmitter?
    Is the meter protected against current overload?
PD603 Sabre P Process Meter
Quick Start Guide
Front Panel Buttons Operation
Button
Symbol
Description
Menu: Press the Menu button
to enter or exit the Programming
Mode at any time.
Right Arrow: Press the Right
arrow button to move to the next
digit during digit or decimal point
programming.
Up Arrow: Press or hold the Up
arrow button to scroll through
the menus, decimal point, or to
increment the value of a digit.
Enter: Press the Enter button
to access a menu or to accept
a setting.
Safety Information
CAUTION
Read complete instructions prior to installation
and operation of the meter.
WARNINGS
Risk of electric shock or personal injury.
Hazardous voltages exist within enclosure.
Installation and service should be performed
only by trained service personnel.
This product is not recommended for life
support applications or applications where
malfunctioning could result in personal injury
or property loss. Anyone using this product
for such applications does so at their own
risk. Precision Digital Corporation shall not be
held liable for damages resulting from such
improper use.
This quick start guide briey describes some of the
common setup procedures for this meter.
The Sabre P model PD603 is an easy to use
1/8 DIN digital panel meter that has all the
important features customers want in a process
input meter. These features include eld selectable
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, or ±10 V inputs,
NEMA 4X front panel, UL and C-UL Listing for 508
Industrial Control Equipment, and optional 24 VDC
power supply for the transmitter. The meter is easily
programmed and scaled with its four front panel
buttons and simple menu structure.
For additional information about the Sabre meter
not covered in this quick start guide, consult the
instruction manual available at www.predig.com.
© 2023 Precision Digital Corporation.
All rights reserved.
WARNING
Cancer and Reproductive Harm
www.P65Warnings.ca.gov
Mounting Dimensions
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.6"
(91mm)
Figure 3. Meter Dimensions - Side View
3.61"
(92mm)
2.50"
(64mm
)
4.68"
(119mm)
Figure 4. Meter Dimensions - Top View
Connections
All connections are made to removable screw
terminal connectors, capable of accepting wire
between 12 to 24 AWG, located at the rear of the
meter.
CAUTION
Use copper wire with 60°C or 60/75°C insulation
for all line voltage connections. Observe all
safety regulations. Electrical wiring should be
performed in accordance with all applicable
national, state, and local codes to prevent
damage to the meter and ensure personnel
safety.
Connectors Labeling
The connectors label, afxed to the meter, shows
the location of all connectors available with
requested conguration.
Figure 5. Connector Labeling for PD603-6R0-0 / 7R0
24V OUT POWER
X XV+ mA+ COM
Factory
Use
Only
3 41 2 5
2 12 1
P+ P-
+-
SIGNAL
Figure 6. Connector Labeling for PD603-6R0-1
Power Connection
Power connections are made to a two-terminal
connector labeled POWER on the gures above.
The meter will operate regardless of DC polarity
connection. The + and - symbols are only a
suggested wiring convention.
12
AC or DC
POWER
AC or DC
(1)
POWER
POWER
+ -
Notes:
1. “AC” Powered meters accept 85-265 VAC or 90-265 VDC
and “DC” powered meters accept 12-36 VDC or 12-24 VAC.
2. Required External Fuse: 5 A max, Slow Blow.
3. Consult the PD603 instruction manual available online at
www.predig.com for additional wiring diagrams.
Signal Input
Connections
Signal connections are made to a five-terminal
connector labeled SIGNAL. The COM (common)
terminal is the return for all types of input signals.
The meter can either be wired to provide 24 VDC to
power the transmitter or an external power supply
can be used. There are no switches or jumpers to
set up for current and voltage inputs.
4-20 mA Input Wiring
COMmA+
21 3 54
V+ X
X
2-Wire
4-20 mA
Transmitter
-+
P+ P-
2 1
24V OUT
COMmA+
21 3 54
V+ X
X
3-Wire
4-20 mA
Transmitter
Signal
+
2 1
24V OUT
-
P+ P-
2-Wire Transmitter Powered by Meter
COMmA+
21 3 54
V+ X
X
2-Wire
4-20 mA
Transmitter
-+
P+ P-
2 1
24V OUT
COMmA+
21 3 54
V+ X
X
3-Wire
4-20 mA
Transmitter
Signal
+
2 1
24V OUT
-
P+ P-
3-Wire Transmitter Powered by Meter
COMmA+
21 3 54
V+ XX COMmA+
V+ XX
External
Power
Supply
2-Wire
4-20 mA
Transmitter
-+ + -
21 3 54
2-Wire 4-20 mA
Self-Powered
Transmitter
-+
Transmitter Powered by External Power Supply
COMmA+
21 3 54
V+ XX COMmA+
V+ XX
External
Power
Supply
2-Wire
4-20 mA
Transmitter
-+ + -
21 3 54
2-Wire 4-20 mA
Self-Powered
Transmitter
-+
Self-Powered Transmitter
The current input is protected against current
overload by an internal resettable fuse. The display
may or may not show a fault condition depending
on the nature of the overload. The fuse limits
the current to a safe level when it detects a fault
condition, and automatically resets itself when the
fault condition is removed.
10 to + 10 VDC Voltage
Input Wiring
2
13 54
Voltage
Signal
+ -
21 3 54
3-Wire
Voltage
Transducer
Signal
+
21
24V OUT
-
P+ P-
COMmA+
V+ XX COMmA+
V+ XX
21 3 54
3-Wire
Voltage
Transducer
Signal
+
21
-
P+ P-
COMmA+
V+ XX
Installation
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout -
3.622" x 1.772" (92 mm x 45 mm). Refer to
Figure 1. 1/8 DIN Panel Cutout Dimensions
below for more details.
Clearance: allow at least 4.0" (102 mm) behind
the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided
with the meter (back-off the two screws so
that there is ¼" (6.4 mm) or less through the
bracket. Slide the bracket toward the front of
the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the
screws against the panel. To achieve a proper
seal, tighten the mounting bracket screws
evenly until meter is snug to the panel along its
short side. DO NOT OVER TIGHTEN, as the
rear of the panel may be damaged.
3.622" (92mm)
1.772"
(45mm) Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 1. 1/8 DIN Panel Cutout Dimensions
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable
Connectors
Figure 2. Panel Mounting Details
PD603 Sabre P Process Meter
Quick Start Guide
LIM603QS_C
SFT039 Ver. 4.010 & up
05/23
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA
Tel (800) 343-1001 • (508) 655-7300
www.predig.com
Limited Warranty
Precision Digital Corporation warrants
this product against defects in material or
workmanship for the specied period as
detailed in the “Specications” section of the
complete manual from the date of shipment
from the factory. Precision Digital’s liability
under this limited warranty shall not exceed the
purchase value, repair, or replacement of the
defective unit. See Warranty Information and
Terms & Conditions on www.predig.com for
complete details.
Compliance Information
Safety
UL & C-UL Listed USA & Canada
UL 508 Industrial Control Equipment
UL File Number E160849
Front Panel UL Type 4X, NEMA 4X, IP65; panel
gasket provided
Low Voltage
Directive
EN 61010-1
Safety requirements for
measurement, control, and
laboratory use
Electromagnetic
Compatibility
Emissions EN 55022
Class A ITE emissions
requirements
Radiated
Emissions
Class A
AC Mains
Conducted
Emissions
Class A
Immunity EN 61326-1
Measurement, control, and
laboratory equipment
EN 61000-6-2
EMC heavy industrial generic
immunity standard
RFI -
Amplitude
Modulated
80 -1000 MHz 10 V/m 80% AM
(1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM
(1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM
(1 kHz)
Electrical
Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI -
Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge ±2kV Common, ±1kV Differential
Surge 1KV (CM)
Power-
Frequency
Magnetic
Field
30 A/m 70%V for 0.5 period
Voltage Dips 40%V for 5 & 50 periods
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Note: Testing was conducted on meters installed through
the covers of grounded metal enclosures with cable shields
grounded at the point of entry representing installations
designed to optimize EMC performance.
EU Declaration of
Conformity
For shipments to the EU and UK, a Declaration of
Conformity was printed and included with the product.
For reference, a Declaration of Conformity is also
available on our website at www.predig.com/docs.
Troubleshooting Tips
Symptom Check/Action
No display at all Check power at power connector
Not able to
change setup or
programming,
LoCd is
displayed
Meter is password-protected,
enter correct four-digit password
to unlock or see column 7 of this
Quick Start Guide if you have
forgotten the password.
Meter displays
error message
during
calibration
(Err)
Check:
1. Signal connections
2. Input selected in Setup menu
3. Minimum input span
requirements
Meter displays
• 9999
• -1999
Check:
1. Input selected in Setup menu
2. Corresponding signal at
Signal connector
Display
alternates
between
1. Hi and a
number
2. Lo and a
number
Press Menu to exit Max/Min
display readings.
If the display
locks up or the
meter does not
respond at all
Cycle the power to restart the
microprocessor.
Other
symptoms
not described
above
Call Technical Support for
assistance.
Program and Scale
4-20 mA Input
These instructions illustrate how to program the
Sabre meter to accept a 4-20 mA input and scale
it to display the desired range. When the input to
the meter is 4 mA, it displays the low end of the
programmed display range. When the input is
20 mA, it displays the high end of the programmed
display range.
For example: If the meter were used to display the
level of a 100 foot tall tank, the transmitter should
send a 4 mA signal when the tank is empty and
a 20 mA signal when the tank is full. The meter
should be programmed to interpret these inputs on
a display range of 0.0-100.0, so that at 4 mA the
meter will display 0.0 and at 20 mA the meter will
display 100.0.
User Interface Reference
Guide
1
Press to enter
Programming Mode,
press to access the
SEtu (Setup) menu.
2
Press to access the
inPt (Input) menu.
4
Press to access
the dEc.P (Decimal Point)
menu.
3
Select 4-20 (4-20 mA)
and press to
conrm input selection.
Note: This should be the default option, but if it is not, press
to scroll through the choices
5
Press to select
the decimal place, then
press .
Note: These instructions illustrate how to scale the meter using
the factory calibrated internal signal source. It is not necessary
to calibrate (CAL) a new meter.
6
Press to enter the
ProG (Program) menu.
12
Press to enter
Input 2. The default input
value of 20.00 for input
2 should be sufcient
Press to accept this value.
11
Press to increment
the digit. Press to
accept the new diS1
value once you are done.
9
Press to access
diS1 (Display 1). This
is the value that will be
displayed on the meter
when the current input is at 4 mA.
10
Press to select a
digit (the selected digit is
brighter than the others).
8
Press to access
inP1 (Input 1). This is the
input which represents
0% of the process
variable. The default
value of 4.00 (4.00 mA) should be sufcient for most
applications. Press to accept.
7
Press to enter the
ScAL (Scale) menu.
13
Press to enter diS2
(Display 2). Change the
value as described in
steps 10-11. Press
to accept value.
14
Press to return to
Run Mode.
Note: The method for inputting numeric values described above
is the same method used to input numbers in all other areas of
the Sabre meter.
Setup Password
Protection
The Sabre meter can be protected against
unauthorized changes with the use of a user
programmable password. These steps illustrate how to
set up a password.
4
Press to accept
the new password. The
meter will display LoCd
(locked) for 3 seconds.
3
Use the and
buttons to change the
password.
2
Press until the PASS
(Password) menu is
displayed, press to
access and press
again to acknowledge that the meter is unlocked.
1
Press to enter
Programming Mode.
Note: In order to unlock the meter once it has been locked,
repeat these steps and enter the password. This will remove
the password and allow programming of the meter. For more
information, please consult the instruction manual.
Forgot the Password?
The password may be disabled by the following
procedure:
1. Note display reading prior to pressing the Menu
button. Ignore decimal point and sign.
2. Access the Password menu, add 2 to the noted
reading and enter that number as the password
(e.g. display reading = -1.23, password = 0125).
/