  • Hello! I'm a chat assistant and I've reviewed the provided tech data sheet for the Schneider Electric fire detection control panels FX101A and FX101S. This document describes the panel's capabilities, installation guidelines, and technical specifications. I am ready to answer your questions about the device, its features, and compatibility with other fire safety equipment.
  • What kind of detectors are compatible with the FX101 panel?
    What is the mounting height for the FX101 panel?
    What software is used to configure the system?
    What is the maximum current consumption in alarm condition?
Tech Data Sheet D01758GB3 30/2018 Fire Detection
FX101A/FX101S FIRE DETECTION CONTROL PANEL
FX101 Control Panel
FX101 is a powerful one loop fire detection
control panel. The full range of Schneider
Electric’s ALC (FX101A) and SLC (FX101S)
intelligent detectors can be connected to the
system.
Versatile built-in control logic enables easy control of
both passive as well as active fire protective
equipment and even a three-stage alert and
evacuation alarm.
The panel is compatible with other fire detection
equipment, such as the fireman’s panel FMP2, zone
led panel ZLPX, alarm delay panel DAP2,
communication protocol repeater REPX and logic
control unit MCOX, as well as alarm management
system ESGRAF. The system also provides an
interface to the building management system.
Panel installation
The FX101 panel is installed on a surface with the
display at a height of approximately 170 cm. The wall
has to be strong enough to support the weight of the
panel and the batteries.
Connections
See overleaf for general overview of the connections
of the FX101 panel.
Cable entries are from behind, from above and from
below.
Commissioning and Configuration
The system can be started after the jumper settings
are verified. For customer/site specific settings and
entry of alarm texts, a PC and licensed software
“WinFX3Net” is used.
For further information, see the Installation and
commissioning manual.
FX101 control panel
Tech Data Sheet D01758GB3 Fire Detection 2
Schneider Electric Fire & Security Oy Sokerilinnantie 11 C, 02600 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103
Document Number D01758GB2 36 2014
© 2016 Schneider Electric. All rights reserved.
Technical data of the FX101 panel
FX101A Control panel
FX101S Control panel
Product code
FFS0070 3804XX
Including FX-ACC, One addressable
detection circuit with 126 addresses
FFS0070 3803XX
Including FX-SCC, One addressable
detection circuit with 159 addresses
Dimensions (h*w*d) [mm]
328 x 425 x 130
328 x 425 x 130
Weight (fully equipped, excl. batteries)
5.4 kg
5.4 kg
IP Rating
IP30
IP30
Operating ambient temperature
+5…+40 °C
+5…+40 °C
Storage ambient temperature
0…+50 °C
0…+50 °C
Maximum ambient humidity
95% RH
95% RH
Back frame material
sheet steel
sheet steel
Cover material
plastic
plastic
Cover color
bluish grey
bluish grey
Mains supply voltage
230 VAC ±10% / 50 ... 60 Hz
230 VAC ±10% / 50 ... 60 Hz
Mains supply power
45 VA
45 VA
Operating voltage range
19 ... 30 Vdc
19 ... 30 Vdc
Maximum current consumption in standby condition
0.5 A @ 24 Vdc
0.5 A @ 24 Vdc
Maximum current consumption in alarm condition
1.4 A @ 24 Vdc
1.4 A @ 24 Vdc
Applied standards
EN 54-2
EN 54-4
EN 54-2
EN 54-4
Number of card slots
No option boards slots available
No option boards slots available
Battery space
2 pcs 12 / 12 Ah
2 pcs 12 / 12 Ah
Schneider Electric Fire & Security Oy reserves the right to make modifications.
Tech Data Sheet D01758GB3 Fire Detection 3
Schneider Electric Fire & Security Oy Sokerilinnantie 11 C, 02600 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103
Document Number D01758GB2 36 2014
© 2016 Schneider Electric. All rights reserved.
FX101 panel external connections
Note!
The max. 24 V current consumption of the FX101- control panel (ACC / SCC- board, loop and all
addresses and control panel outputs) is 0,5 A in standby condition and 1,4 A in alarm condition. The
standby time required for the system may limit the max. load of the outputs.
Clean contact signal inputs (3 pcs), function configurable
Input for remote battery temperature monitoring
Master
controller
FX-Mc2c
Loop controller
FX-ACC, FX-SCC
1 pcs
Serial (RS232) communication with printer or maintenance tool (PC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply output 24 VDC (1 pcs), short circuit protected, 500 mA
Open collector outputs (4 pcs), max 10 mA each, function configurable
Battery 24 VDC (max 24 Ah)
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
FX-ACC: One addressable detection circuits, with 126 addresses
FX-SCC: One addressable detection circuits, with 159 addresses
Fire Alarm Devices (Bells, sounders, beacon), 500 mA
Power supply output 24 VDC, short circuit protected, 500 mA
USB connection, maintenance tool (PC)
Serial (RS485) communication with INFO
230 VAC / 50 Hz / 45 VA
Tech Data Sheet D01758GB3 Fire Detection 4
Schneider Electric Fire & Security Oy Sokerilinnantie 11 C, 02600 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103
Document Number D01758GB2 36 2014
© 2016 Schneider Electric. All rights reserved.
0402
Schneider Electric Fire & Security Oy
P.O. Box 415, 02601 Espoo Finland
For FX101A/S 0402-CPR-SC0954-15,
0402-CPR-SC0955-15
For FX101S 0402-CPR-SC0954-15,
0402-CPR-SC0955-15
Declaration of Performance: DP16001
EN 54-2:1997/AC:1999/A1:2006
EN 54-4:1997/AC:1999/A1:2002/A2:2006
Options:
7.8; 7.9.1; 7.10.3; 7.11; 7.12.2; 7.13; 8.3; 8.4; 8.9; 9.5;
10
Control and indicating equipment for fire detection and fire
alarm systems for buildings
FX101A, FX101S
Other technical data:
66571872: Installation and commissioning manual
66571744: operation manual
66571758 (SLC), 66571761 (ALC): system planning (held by
the manufacturer )
/