PHASE CONTROL RELAY
Read all the instructions carefully
ThephasesequencerelayPSR is an electronic command device in a standardised
2-module DINcontainer,tocontrolvoltage-asymmetryandphase-sequenceinthree-
phasesystems.
SAFETY WARNINGS
During the installation and operation of the instrument, proceed in accordance with the
instructions below:
1) The instrument should be installed by a competent operator following the
installation diagrams carefully
2) The instrument should be installed in a panel from which no access can be gained to
the terminals after installation
3) Do not power or connect the instrument if any part of it is damaged
4) The electrical system of the building in which the instrument is to be installed
should have a switch and a protective device against over-currents
5) The instrument is designed for installations with over-voltage category III and
pollution level 2, in accordance with the EN 61010-1 standard
Code Model Description
VP807200 PSR Phase-controlrelay
TECHNICAL SPECIFICATIONS
• Powersupply:
400 V
~ 50 Hz
• Absorption:4VA(3W)
• Terminals:6mm2block
• Output:
–relaywithcontactinexchange8A/250V~
–maximumswitchablepower2000VAcos =1
• Sensitivity:70%÷95%ofratedvalue
• Interventiontime:2s
• Resettime:2s
• Hysteresisonreset:2%
• Signalling:RedLEDrelayintervention
• Operatingtemperature:–5°C÷+50°C
• Storagetemperature:–10°C÷+70°C
• Humidity:20%÷90%non-condensing-
• Insulation:powersupplyandcommandcircuitsgalvanicallyisolatedfromeachotherat
reinforcedinsulationlevelinaccordancewiththeEN61010standard
• Container:2DINmodules,colourRAL-7035
• Containermaterial:self-extinguishinginclassV0inaccordancewiththeUL-94standard
• Degreeofprotection:IP20/IP40whencorrectlyinstalledinanelectricalpanel
USE
• Applicationsineverycasewhereitisessentialtoadheretothephasesequenceupon
wiringortopreventsignicantoscillationsofthepowersupplyvoltageinnetwork.
• Therelaydetectstheexactphasesequenceinthree-phasesystemsandvoltageunbalance
causedbythereductionorabsenceofaphase.
OPERATION
• Theoutputrelayisexcited(
“Relay ON”
ledon)onlyifallthreephasesarepresent
andtheirsequencecorrespondstothesealontheinputterminals(seethe
“Operating
diagram 1”
).
• Whenoperative,theoutputrelaydropsout(
“Relay ON”
ledoff)ifthesequenceofthe
phasesisaltered,ifaphaseisabsentorifthevoltageunbalanceofthephasesexceedsthe
calibrationvalue(seethe
“Operating Diagram 1 and 2”
).
• Thesensitivityoftherelayisadjustablebymeansofthe
“ASYMMETRY (%)”
trimmer
onthefrontofthedevice,from95%to70%oftheratedvalue,tosetitduringinstallation
fortheunbalancevalueofthenetworkvoltagethatmaybetoleratedbytheunitorsystem
tobeprotected(seethe
“Operating diagram 2”
).
• Toavoidundesirableinterventionsbythedeviceinthepresenceofslightvoltage
unbalance,werecommendstartingtheadjustmentsfromthemaximumasymmetry
(70%ofUn).
• Theresetisautomaticwhenthenormalpowersupplyconditionsarerestoredorwhenthe
sequence error is corrected.
• Afteraninterventionduetophaseasymmetry,theresethasahysteresiswhichmakesit
possibletore-excitetheoutputrelaywhenthevoltagevaluereturnsaboveacertainxed
leveloftheThresholdofAsymmetry(seethe
“Operating Diagram 2”
).
RIFERENCE STANDARDS
ConformitytotheEUdirectives:
2006/95/EC(LowVoltage)
89/336/EECmodiedby92/31/EECand93/68/EEC(EMC)
isdeclaredwithreferencetothefollowingharmonisedstandards:
Safety:
EN61010-1
Electromagnetic compatibility:
EN61000-6-2,EN61000-6-4
Dimension
Connection diagram
Operating diagram 1
36 60
45
65
88
ON
Relay
PSR
Asymmetry
(%)
L2
L1
1
2
3
4
5
6
7
8
8A / 250 V ca
L3
Operating diagram 2
Relay
Un
HYSTERESIS
ASYMMETRY THRESHOLD %
Relay