2. Installation Xgard Type 1
Product overview
Xgard are a family of gas detectors for monitoring a very wide range
of toxic and flammable gases and oxygen. Xgard are available as
either Intrinsically Safe (Exia) or Flameproof (Exd) detectors, dependant
upon sensor type and customer preference. Intrinsically Safe versions
are suitable for use in Zone 0, 1 or 2 hazardous areas when used with
a suitable Zener barrier or galvanic isolator. Flameproof versions are
suitable for use in Zone 1 or 2 hazardous areas.
Please refer to the certification label on the detector junction box to identify
the type of certification that relates to the product supplied. Hazardous
area definitions are shown in the Hazardous area classifications section
on page 3.
Note: if no certification label is fitted to the junction box, the
detector is not certified for use in hazardous areas.
Overview
Xgard Types 2,3,5,6 ATEX
and IECEx Flameproof
label
Xgard Type 4 ATEX and
IECEx Flameproof label
Xgard Intrinsically Safe - Type 1 UL
Class I, Groups A, B,CandDHaz. Loc when installed in accordance with control
CROWCON XGARD GAS DETECTOR TYPE 1
understand and adhere to the manufacturer's live maintenance procedures.
Safety.To prevent ignition of flammable or combustible atmospheres read,
drawing No S-4838-A3. WARNING Substitution of Components May Impair Intrinsic
Securite Intriseque. Classified as to Intrinsic Safety For use in
-40°C <Ta<+55°C T4
OXYGEN
XX
Exia
Vmax: 28V, Pmax: 1.2W, Ci: 15.6nF, Li: 0uH
C
A
L
C
I
S
S
66Y6
US
D
I
F
E
Diagram 1: Xgard certification labels
Xgard UL Flameproof
drawing No S-4838-A3. WARNING Substitution of Components MayImpair Intrinsic
-40°C<Ta<+55°C T4
CROWCON XGARD GAS DETECTOR TYPE 1
XX
Safety.To prevent ignition of flammable or combustible atmospheres read,
understand and adhere to the manufacturer's live maintenance procedures.
Vmax:28V, Pmax:1.2W,Imax:150mA, Ci:14.4nF, Li:0 uH
Securite Intriseque. Classified as to Intrinsic Safety For use in
Class I, Groups A, B, C and DHaz. Loc when installed in accordance with control
TOXIC
Exia
66Y6
C
C
L
A
S
S
I
F
I
E
D
CLASS I, DIVISION 1, GROUPS B, C, & D
AS TO RISK OF FIRE, ELECTRIC SHOCK & EXPLOSIVE HAZARDS ONLY.
WARNING To reduce the risk of ignition of Hazardous Atmosheres
disconnect the equipment from the supply circuit before opening.
Keep assy tightly closed when in operation. Conduit runs must have
sealing fitting connected within 18 inches of enclosure.
XGARD GAS DETECTOR TYPE
<
<
a
<
<
a
2006
C
L
S
A
I
S
66Y6
E
I
F
D
Intrinsically Safe Type 1