UNISTROBE WARNING LIGHT
GENERAL INFORMATION:
The No. 710 Unistrobe Warning Light can be installed indoors or outside to
provide brilliant,
attention-getting flashes of light upon dctivation from
the alarm system”bel 1” terminals .or other switched voltage source.
Physical:
Width:
4 3/8” (II.1 cm)
Height:
4 3/8!’ (II.1 cm)
Depth:
3 l/Z” ( 8.9 cm)
Electrical: Voltage: 5 to l5V. DC
Current :
Approximately 350 ma at 6V. DC
Approximately 250 ma at l2V. DC
Flash Rate:
Approximately 60 times per minute at 6V. DC (faster
at higher voltages up to l5V. DC max.)
INSTALLATION & WIRING:
TAMPER SWITCH (OPTIONAL):
-
If tampered installation is desired:
I .
Obtain a No. II2 or No. II3 Plunger Contact (use No.. 112 for a closed
circuit alarm system, No.
II3 for an open circuit system).
2.
Cbonect a #22 wire to each terminal of the switch.
3.
Insert switch in the tamper switch opening provided in the base of the
unit, with its terminals facing into the opening and wires exiting at
the corner of the opening. Snap switch into place.
WIRING:
Use Diagram I in conjunction with the appropriate mounting proce-
dure described below.
Note: Observe polarity with the RED (+I
and BLACK (-1 leads.
The unit will not operate with reverse polarity.
TO MOUNT ON STANDARD 4 l/2” OUTLET BOX:
I .
2.
3.
4.
5.
Connect wiring as described under WIRING and as shown in Diagram I.
Position unit so that its “tamper switch corner” is at lower left when
unit is viewed from the front.
See Diagram 2.
Place a 3/4 #8-32 Machine Screw (not provided) through hole Al at the
“tamper switch corner”
and (if a tamper switch is being used) through
?-he hole in the tamper plate provided. Thread the screw into the hole
at the corner of the outlet box.
Before tightening, position the tamper
plate (if used) under the base of the No.
710 and then tighten the screw.
Place a similar screw through diagonally opposite hole A2 and fasten
that corner to the outlet box.
Insert plastic Decor Pluqs (provided) into the two front mounting holes
of unit.
20
www.PDF-Zoo.com
TO MOUNT ON BELL HOUSING, WALL OR OTHER STURDY SURFACE:
Note : Units such as the Ademco No. 1011 Bell in Box and No, 711 Electronic
Sirenahave holes already in their cabinets to accomodate the No. 710.
I .
Use Diagram 2 Template to locate holes for drilling in the mounting sur-
face, as follows:
a.
For Front Mounting:
Drill mounting holes at Al and A2 as required
(two I” #8 self-tapping screws accompany unit) and cut a wiring hole
(l/2” minimum diameter) at C.
b.
For Rear Mounting:
Drill 3/16’ diameter holes at BI and B2 (to c
#8 self-tapping screws provided) and cut a wiring hole (l/2” min
at C.
2.
Bring DC power source and (if used) tamper circuit wires to the unit
throuqh hole C and.connect as described under WIRING and in Diagram
-1
ear
mum)
.
3.
Position unit
SO
that ‘tamper switch corner” is at lower left when unit
is viewed from front.
4.
Mount unit. The #8 self-tapping screws provided may be used for front
mounting (“A” holes) or rear mounting (“B” holes).
5. Insert plastic Decor Plugs (provided) into the two front
mounting holes
of unit.
Diagram 1: WIRING CONNECTIONS
DECOR PLUG
(AFTER MOUNT I NG,
INSERT AT THIS
AND D I AGONALLY
OPPOSITE CORNER)
NON-REMOVABLE
(MOLDED) DECOR PLUG
AT THIS AND
DIAGONALLY OPPOSITE
CORNER
TAMPER PLATE
(USE WHEN
MOUNTING UNIT
WITH TAMPER
SWITCH ON STD.
4 l/2” OUTLET
BOX) .--
TAMPER SW ITCH -
(OPTIONAL)
ADEMCO NO. 112: CLOSED C
NO. 113: OPEN C
RCU
RCU
-No. 710
5-l5V. DC FROM CONTROL
“BELL” TERM I NALS OR
OTHER
SWITCHED SOURCE
.‘S
OBSERVE POLARITY!
TO TAMPER (PROTECTIVE) CIRCUIT
OF CONTROL ( IF TAMPER USED)
21
www.PDF-Zoo.com
/
I
I
I
I
I
I
3 ‘/a”
OPENING IN
REAR OF UNIT
yy..J 1 +B2
FOR.OPTIONAL
TAMPER SW ITCH \
\
-- --
m-
I
MOUNTING
d
WIRING HOLE
IN MOUNTING
SURFACE
+
I
C
(‘i2/r”MIN.
I
DIAMETER)
UJTLINE OF
NO. 710’S
BASE
-
I
I
2
Diagram 2: MOUNTING TEMPLATE (VIEWED FROM “FRON?” OF
UNIT)
22
www.PDF-Zoo.com
TROUBLESHOOTING
a
TROUBLE: I.
A.
B.
TROUBLE: 2.
A.
B.
THE STROBE LIGHT FAILS TO WORK.
PROBABLE CAUSE
Power source polarity reversed,
disconnected, shorted, or weak
(on alarm, the unit should re-
ceive between 5 and 15 V. DC
from the control ‘s bel I termi-
nal s. Check presence of this
voltage with polarity correct
at both the control panel out-
put and the red and black wires
to the strobe light).
Defective bulb or strobe lamp
internal circuitry.
NOS. 710, 710A
A.
B.
REMEDY
Repair disconnected, shorted, or
reversed leads to the strobe,
Check
power source condition by referring
to Section L of this manual.
Unit must be returned to Ademco
for repair.
PROTECTIVE CIRCUIT DOES NOT OPERATE NORMALLY WHEN USED TO TAMPER-PROOF THE
STROBE LIGHT.
PROBABLE CAUSE
REMEDY
Incorrect use of tamper switch.
iUse No. II2 for closed-circuit
A. Replace switch with correct type.
current-carrying protective loops.
This switch is NORMALLY OPEN.
(N.0.) Use No. II3 for open-circuit
types of protective loops. This
switch is normally closed (N.C.11.
Breaks or shorts in the wiring to B. Repair wiring as required.
the tamper switch (check wiring
with an ohmmeter for continuity