No.710
UNISTROBE WARNING LIGHT
GENERAL INFORMATION:
The No. 710 Unistrobe Warning Light can be installed indoors or outside to
provide brilliant,
attention-getting flashes of light upon dctivation from
the alarm system”bel 1” terminals .or other switched voltage source.
Physical:
Width:
4 3/8” (II.1 cm)
Height:
4 3/8!’ (II.1 cm)
Depth:
3 l/Z” ( 8.9 cm)
Electrical: Voltage: 5 to l5V. DC
Current :
Approximately 350 ma at 6V. DC
Approximately 250 ma at l2V. DC
Flash Rate:
Approximately 60 times per minute at 6V. DC (faster
at higher voltages up to l5V. DC max.)
INSTALLATION & WIRING:
TAMPER SWITCH (OPTIONAL):
-
If tampered installation is desired:
I .
Obtain a No. II2 or No. II3 Plunger Contact (use No.. 112 for a closed
circuit alarm system, No.
II3 for an open circuit system).
2.
Cbonect a #22 wire to each terminal of the switch.
3.
Insert switch in the tamper switch opening provided in the base of the
unit, with its terminals facing into the opening and wires exiting at
the corner of the opening. Snap switch into place.
WIRING:
Use Diagram I in conjunction with the appropriate mounting proce-
dure described below.
Note: Observe polarity with the RED (+I
and BLACK (-1 leads.
The unit will not operate with reverse polarity.
TO MOUNT ON STANDARD 4 l/2” OUTLET BOX:
I .
2.
3.
4.
5.
Connect wiring as described under WIRING and as shown in Diagram I.
Position unit so that its “tamper switch corner” is at lower left when
unit is viewed from the front.
See Diagram 2.
Place a 3/4 #8-32 Machine Screw (not provided) through hole Al at the
“tamper switch corner”
and (if a tamper switch is being used) through
?-he hole in the tamper plate provided. Thread the screw into the hole
at the corner of the outlet box.
Before tightening, position the tamper
plate (if used) under the base of the No.
710 and then tighten the screw.
Place a similar screw through diagonally opposite hole A2 and fasten
that corner to the outlet box.
Insert plastic Decor Pluqs (provided) into the two front mounting holes
of unit.
20
www.PDF-Zoo.com