Dacor MRV48ERS Operating instructions

Type
Operating instructions

This manual is also suitable for

Installation Instructions
Renaissance
®
Downdraft Vent
Models ERV3015, ERV36-ER, ERV3615, ERV48,
ERV48-ER, PRV30, PRV36 and PRV46
Part No. 107736 Rev. B
Use these downdraft vents only with approved Dacor
®
appliances. See the
installation instructions for the particular appliance model being installed to
determine suitability.
Includes installation instructions for cabinet blower (Dacor model CABP3) which is
an option for models ERV3015 and ERV3615.
Installation Specifications ................................................ 6
Planning the Installation ................................................... 6
Planning the Duct Work ................................................... 8
Installation Instructions .................................................. 12
Installation Preparation .................................................. 12
Installing the Downdraft Vent in the Cutout ................... 13
Verifying Proper Operation ............................................. 16
Installation Checklist ...................................................... 16
Wiring Diagram - All Models .......................................... 17
CABP3 Cabinet Blower Ratings ..................................... 17
Table of Contents
Before You Begin...
Important Safety Instructions .......................................... 1
Important Information About Safety Instructions .............. 1
Safety Symbols and Labels ............................................. 1
General Safety Precautions ............................................. 2
Product Specifications ..................................................... 2
Electrical Specifications ................................................... 2
Product Dimensions - ERV3015 and ERV3615 ............... 3
Product Dimensions - ERV48 and PRV Series ............... 4
Product Dimensions - ERV36-ER and ERV48-ER .......... 5
All specifications subject to change without notice.
Dacor
assumes no liability for changes to specifications.
Important:
• Installer: In the interest of safety and to minimize problems, read these installation instructions completely and care-
fully before you begin the installation process. Leave these installation instructions with the customer.
• Customer: Keep these installation instructions for future reference and the local electrical inspector’s use.
© 2013 Dacor, all rights reserved.
If You Need Help...
If you have questions or problems with installation, contact
your Dacor
®
dealer or the Dacor Customer Service Team.
For repairs to Dacor appliances under warranty call the Dacor
Distinctive Service line. Whenever you call, have the model
and serial number of the appliance ready. The model and seri-
al number are printed on the product data label on the front of
the unit. The product data label also specifies the power sup-
ply requirements.
Dacor Customer Service
Phone: ((800) 793-0093 ex. 2813 (U.S.A. and Canada)
Monday - Friday 6:00
a.m. to 5:00 p.m. Pacific Time
Web site: www.dacor.com
Dacor Distinctive Service (for repairs under warranty only)
Phone: 793-0093 ex. 2822 (U.S.A. and Canada)
Monday - Friday 6:00
a.m. to 5:00 p.m. Pacific Time
Customer Service Information
Model Identification
ERV3015 = 30-inch wide downdraft vent with ERV
style top cap. For use with approved
Dacor cooktops and ranges.
ERV3615 = 36-inch wide downdraft vent with ERV
style top cap. For use with approved
Dacor cooktops and ranges.
ERV36-ER = 36-inch wide downdraft vent with ERV
style top cap. For use with approved
Dacor ranges.
ERV48 = wide downdraft vent with ERV style
top cap. For use with approved Dacor
cooktops and ranges.
ERV48-ER = 48-inch wide downdraft vent with ERV
style top cap. For use with approved
Dacor ranges.
PRV30 = wide downdraft vent with PRV style
top cap. For use with approved Dacor
cooktops and ranges.
PRV36 = 36-inch wide downdraft vent, PRV
style top cap. For use with approved
Dacor cooktops and ranges.
PRV46 = 46-inch wide downdraft vent, PRV
style top cap. For use with approved
Dacor cooktops.
1
Important Information About
Safety Instructions
• The Important Safety Instructions and warnings in
these instructions are not meant to cover all possible
problems and conditions that can occur. Use common
sense and caution when installing, maintaining or oper-
ating this or any other appliance.
• Always contact the Dacor Customer Service Team
about problems and conditions that you don’t under-
stand. See Customer Service Information.
Important Safety Instructions
Safety Symbols and Labels
DANGER
Immediate hazards that WILL result in severe personal
injury or death.
WARNING
Hazards or unsafe practices that COULD result in severe
personal injury or death.
CAUTION
Hazards or unsafe practices that COULD result in minor
personal injury or property damage.
WARNING
This appliance is equipped with a three prong grounding
plug for your protection against possible electric shock
hazards. It must be plugged into a dedicated, grounded
electrical outlet. Where a standard two prong electrical
outlet is encountered, it is the personal responsibility
and obligation of the customer to have it replaced with a
dedicated, properly grounded three prong electrical outlet.
Do not under any circumstances:
Cut or remove the third (ground) prong from the
power cord.
Use an adapter plug.
Use an extension cord.
Use a power cord that is frayed or damaged.
Use of a ground fault interrupter (GFI) is not
recommended.
DANGER
IMPORTANT: Do not store or use combustible,
flammable or explosive vapors and liquids (such as
gasoline) inside or in the vicinity of this or any other
appliance. Also keep items that could explode, such
as aerosol cans, away from the range or cooktop. Do
not store flammable or explosive materials in adjacent
cabinets or areas.
WARNING
WARNING – TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be
done by qualified person(s) in accordance with
all applicable codes and standards, including
fire-rated construction.
b) Sufficient air is needed for proper combustion
and exhausting of gases through the
flue(chimney) of fuel burning equipment to
prevent back drafting. Follow the heating
equipment manufacturer’s guideline and safety
standards such as those published by the
National Fire Protection Association (NFPA), and
the American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE), and
the local code authorities.
c) When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden
utilities.
d) Ducted fans must always be vented to the
outdoors.
READ AND SAVE THESE INSTRUCTIONS
Three prong
grounding plug
Grounding
type
electrical
outlet
2
Important Safety Instructions
• Do not install or operate a damaged appliance. If you
receive a damaged appliance, contact your dealer or
builder.
• Observe all governing codes and ordinances during
planning and installation. Contact your local building
department for further information.
• The electric outlet for the downdraft vent should be
installed only by a licensed electrician
• For general ventilating use only. Do not use to
exhaust hazardous or explosive materials and vapors.
• Use this downdraft vent only for its intended purpose
as outlined in the use and care manual. This appli-
ance is not intended for commercial use.
• The customer should not install, repair or replace
any part of this unit unless specifically recommended
in the literature accompanying it. A qualified service
technician should perform all other service. Contact
the Dacor Customer Service Team for examination,
repair or adjustment.
• Keep all packaging materials away from children.
Plastic bags can cause suffocation.
• For proper operation, this unit must be installed with a
cabinet, in-line or remote blower. Use only one of the
models specified. Only one blower shall be installed.
• Before installing or servicing the downdraft vent, dis-
connect the power plug from the electrical outlet.
WARNING
General Safety Precautions
To reduce the risk of fire, electric shock, serious injury or death when using your appliance, follow basic safety precau-
tions, including the following:
• The installer must show the customer the location of
the electrical outlet so that the customer knows where
and how to disconnect power.
• Install or locate this appliance only in accordance
with these installation instructions, the Dacor range/
cooktop installation instructions and the blower instal-
lation instructions. Improper installation, adjustment,
alteration, service or maintenance can cause serious
personal injury or property damage.
• Read the use and care manual completely before
operating this appliance.
• Do not tamper with the controls.
• Never allow the filters or vent openings to become
blocked or clogged. Do not allow foreign objects, such
as cigarettes or napkins, to be sucked into the vent
holes.
• Clean the filters and all grease-laden surfaces often
to prevent grease fires and maintain performance.
Clean this appliance only as specified in the use and
care manual.
• Do not leave children or pets alone or unattended in
the area around the range or cooktop when it is in
use. Never allow children to sit or stand on an appli-
ance. Do not let children play with a range, cooktop
or the downdraft vent. Do not store items of interest to
children above or around the appliance.
WARNING
Electrical Specifications
The downdraft vent is supplied with a 28” (71.1 cm) power
cord with a three prong plug. Plug it directly into a three
prong electrical outlet meeting the requirements below. Do
not use an extension cord.
The correct voltage, frequency and amperage must be sup-
plied as specified below. The circuit must be protected by a
properly sized circuit breaker or time-delay fuse.
Electrical Supply Requirements
A three prong electrical outlet connected to a 120 Vac,
60 Hz, 15 Amp. grounded, dedicated, single phase circuit
is required.
• The above specifications are for reference only. If they
do not agree with those listed on the product data label,
use the ratings on the label.
• The customer must supply 3 conductor wiring/conduit
with minimum current carrying capacity of 8 Amps. to
supply power to the blower from the downdraft vent.
See Installation Specifications for further details.
• It is the owner’s responsibility to ensure that the electri-
cal outlet is installed by a licensed electrician. The elec-
trical installation must comply with the latest revision of
the National Electric Code ANSI/NFPA 70* (latest revi-
sion) and local codes and ordinances.
*A copy of this standard may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02269-9101
• Locate the electrical outlet in an accessible location,
so that the power plug can be disconnected for service
without removing the appliances from the cabinet.
Product Specifications
3
Product Dimensions - ERV3015 and ERV3615
Product Specifications
15"
(38.1 cm)
30"
(76.2 cm)
20”
(50.8 cm)
1 1/8”
(2.9 cm)
28" 3 prong
grounded
power cord
Motor
cover
Front of unit
6”
(15.2 cm)
2 9/16”
(6.5 cm)
9/16”
(1.4 cm)
3”
(7.6 cm)
1 15/16
(4.9 cm)
B
A
2 1/8
(5.4 cm)
2 3/16”
(5.6 cm)
3/16”
(5 mm)
5/16” (8 mm)
thick stiffener
across back
Top cap with
vent down
Vent shown
in raised
position
3 3/4”
(9.5 cm)
30 1/4”
(76.8 cm)
to
37 1/4”
(94.6 cm)
Adjustable
anchor legs
Product
data label
Tolerances: ±1/16” (±1.6 mm) unless otherwise stated
Model
Number
A - Top Cap
Width
B - Chassis
Width
ERV3015 30” (76.2 cm) 27 3/8” (69.5 cm)
ERV3615 36” (91.4 cm) 33 3/8” (84.8 cm)
See pages 9 and
10 for exhaust
locations and
dimensions.
** Maximum height of downdraft vent must not exceed maximum specified counter
height for cooking appliance. See installation instructions for cooking appliance.
* Total chassis depth with optional CABP3 blower installed is 10 3/8” (26.3 cm).
*
**
2 1/8" (5.4 cm)
3/8"
(1.0 cm)
2 1/8" (5.4 cm)
ERV top cap - side view
PRV top cap - side view
7/16"
(1.1 cm)
4
Product Specifications
30 1/4"
(76.8 cm)
to
37 1/4"
(94.6 cm)
10"
(25.4 cm)
30"
(76.2 cm)
18 5/8”
(47.3 cm)
5/16” (8 mm)
thick stiffener
across back
3 3/4"
(9.5 cm)
1"
(2.5 cm)
28" 3-prong
grounded
power cord
Vent shown
in raised
position
Product
data label
Motor
cover
Front of unit
6"
(15.2 cm)
2 9/16"
(6.5 cm)
9/16"
(1.4 cm)
2 1/2"
(6.4 cm)
1 15/16"
(4.9 cm)
B
A
Adjustable
anchor legs
2 1/8"
(5.4 cm)
2 3/16"
(5.6 cm)
3/16"
(5 mm)
Top cap with
vent down
Tolerances: ±1/16” (±1.6 mm) unless otherwise stated
Model
Number
A - Top Cap
Width
B - Chassis
Width
ERV48 48” (121.9 cm) 43 3/8” (110.2 cm)
PRV30 30” (76.2 cm) 27 3/8” (69.5 cm)
PRV36 36” (91.4 cm) 33 3/8” (84.8 cm)
PRV46 46” (116.8 cm) 43 3/8” (110.2 cm)
See page 9 for exhaust
locations and dimensions.
* Maximum height of
downdraft vent must
not exceed maximum
specified counter height
for cooking appliance. See
installation instructions for
cooking appliance.
*
2 1/8" (5.4 cm)
3/8"
(1.0 cm)
2 1/8" (5.4 cm)
ERV top cap - side view
PRV top cap - side view
7/16"
(1.1 cm)
Product Dimensions - ERV48 and PRV Series
5
Product Specifications
Product Dimensions - ERV36-ER and ERV48-ER
30 1/4"
(76.8 cm)
to
37 1/4"
(94.6 cm)
10"
(25.4 cm)
30"
(76.2 cm)
18 5/8”
(47.3 cm)
5/16” (8 mm)
thick stiffener
across back
3 3/4"
(9.5 cm)
1"
(2.5 cm)
28" 3 prong
grounded
power cord
Vent shown
in raised
position
Product
data label
Motor
cover
Front of unit
6"
(15.2 cm)
2 9/16"
(6.5 cm)
2 1/2"
(6.4 cm)
1 15/16"
(4.9 cm)
B
A
Adjustable
anchor legs
2 13/16"
(7.1 cm)
1/4"
(6 mm)
Top cap with
vent down
Tolerances: ±1/16”, (±1.6 mm) unless otherwise stated
Model
Number
Top Cap
Width (A)
Chassis
Width (B)
ERV36-ER 36” (91.4 cm) 33 3/8” (84.8 cm)
ERV48-ER 48” (121.9 cm) 43 3/8” (110.2 cm)
See page 9 for
exhaust locations and
dimensions
*
* Maximum height of
downdraft vent must not
exceed maximum speci-
fied counter height for
cooking appliance. See
installation instructions for
cooking appliance.
6
Installation Specifications
Planning the Installation
General System Layout
The vent system consists of the downdraft vent itself and a
single Dacor approved cabinet blower (models ERV3015 and
ERV3615), remote blower or in-line blower (see facing page
for examples).
WARNING
• Failure to install an approved blower or proper duct
work will result in a back draft and/or the insufficient
venting of smoke and fumes.
• To reduce the risk of personal injury caused by reach-
ing over a hot appliance, cabinet storage space
located directly above the range/cooktop should be
avoided.
• Follow the instructions and diagrams for minimum safe
clearances and installation location in these instruc-
tions, the appliance installation instructions and the
blower installation instructions. Failure to do so may
result in a fire or safety hazard.
• Plan the installation so that all minimum dimensions
are met or exceeded. All contact surfaces between the
downdraft vent and any cabinets or walls must be solid
and at right angles.
• The downdraft vent is equipped with adjustable anchor
legs to accommodate various cabinet heights.
• Install the downdraft vent and range/cooktop so that
they can be removed if service is required.
• When installing the downdraft vent with a cooktop,
access from the front of the cabinet to the chassis and
the electrical/gas supplies of both appliances must
be provided for inspection and service. Any drawers
or shelves must be easy to remove for access to the
cooktop, downdraft vent and utilities.
• There are 7/8” access holes in the bottom and side of
the downdraft vent for connecting the blower wiring and
strain relief. Wire the blower to turn on when the down-
draft vent is turned on. When installing a remote or in-
line blower, run the blower wiring/conduit parallel to the
duct work, connecting it to the downdraft vent on one
end and the blower on the other.
• Allow room for the exhaust duct coming out of the unit.
See Planning the Duct Work for further details.
• The maximum allowable duct run must be taken
into consideration when determining the layout. See
Planning the Duct Work for further details.
• Refer to the range/cooktop installation instructions for
the minimum cutout dimensions specific to the particu-
lar downdraft vent model being installed.
Vertical
non-combustible
surface rear wall
Notches for self-rimming
style installations, see range
installation instructions
Notches required for some downdraft vent
installations, see range
installation instructions
Backsplash
Countertop
overhang
See the range installation
instructions for exact countertop
and cabinet dimensions
Vertical
non-combustible
surface rear wall
Notches required for some downdraft vent
installations, see cooktop
installation instructions
Backsplash
Countertop
overhang
See the cooktop installation
instructions for exact countertop
and cabinet dimensions
Flush with back side
of cabinet front
Range Cabinet/Countertop Cutout - Top View
Cooktop Cabinet/Countertop Cutout - Top View
7
Installation Specifications
Example of Layout with Range
and Bottom Exhaust
Example of Layout with Cabinet
Blower Configuration, Exhaust Through Wall
Example of Layout with Cooktop
and Rear Exhaust
REMP series
remote blower
3 ¼ x 10 to
round transition
and 45°
adjustable elbow
Duct work between
downdraft and
remote blower
Wall board
Cooktop
Backsplash
Downdraft vent
Downdraft vent
configured for
rear exhaust
Floor
Wiring/conduit
from downdraft
to remote blower
Cabinet blower,
option on
ERV3015 and
ERV3615
only
Cooktop
Floor
12” min.
(30.5 cm)
3 1/4 x 10
90° elbow
Wall
Downdraft vent
Wall cap
Backsplash
ILHSF series
in-line blower
3 ¼ x 10 to
round transition
Duct work Duct work
Outside wall
Range
Wall cap on
outside wall
Downdraft vent
Downdraft vent
configured for
bottom exhaust
Floor
Wiring/conduit
from downdraft to
in-line blower
Cabinet back
Front of unit
Cabinet blower -
option on ERV3015,
and ERV3615 only
Connection to
cabinet blower
Blower wiring
access hole
Blower wiring
access hole
Connection to
remote/in-line
blower
Electrical Layout
8
Installation Specifications
Installations with ILHSF and REMP series blowers:
With ILHSF and REMP blowers, the downdraft vent can
be configured to exhaust through the back, the bottom or
either side by removing the appropriate exhaust knock-out
shown on the facing page.
• When connecting the duct work to the back of the unit,
the customer must supply a 3 ¼ x 10 rectangular tran-
sition to make the connection.
• For side and bottom exhaust connections, use the sup-
plied transition to connect the duct work to the unit. It
transitions between the 1
5
/8 x 16 exhaust outlet on the
unit and a 3 ¼ x 10 rectangular duct connection. On
bottom exhaust installations cut a hole in the floor to
allow the transition and/or duct work to pass through
the floor (see page 13).
• On side exhaust installations, allow five inches of space
on the side for the 2 x 16 to 3 ¼ x 10 transition plus
additional space for the duct attached to it (X).
Planning the Duct Work
WARNING
• To reduce the risk of fire and to properly exhaust air,
be sure to duct air outside the house or building. Do
not vent exhaust air into spaces within walls or ceil-
ings or into attics, crawl spaces or garages.
• TO REDUCE THE RISK OF FIRE, USE ONLY METAL
DUCT WORK.
• DO NOT install more than one blower to increase the
length of the duct run. Even small differences between
blower air flow rates can greatly reduce the air draw
by the downdraft vent.
Local building codes may require the use of makeup air
systems with ventilation systems that move air greater than
the specified movement rate (CFM). The specified rate var-
ies based on locale. Consult a qualified HVAC specialist
when designing the system for the requirements in your
area and to assure optimal performance.
You must install one of the Dacor blower models listed
below for the downdraft vent to operate properly. See the
blower installation instructions for directions. For model
CABP3, see the instructions later in this manual.
APPROVED DACOR BLOWERS FOR USE WITH
MODEL ERV-PRV SERIES DOWNDRAFT VENTS
Dacor Blower
Model Number
Rating
Compatible with
Vent Models
CABP3
1
600 CFM
2
ERV3015
3
ERV3615
3
ILHSF8 600 CFM
4
ALL
ILHSF10 1100 CFM
4
ALL
REMP3 600 CFM
4
ALL
REMP16 1000 CFM
4
ALL
1
IMPORTANT: Due to a lack of clearance, do not use a
CABP3 blower if a range or wall oven is to be installed in
front of the downdraft vent.
2
Nominal rating at zero inches static pressure, see the
CABP3 blower ratings on page 17 for actual rating.
3
Revision B and later units only.
4
Nominal rating at zero inches static pressure. See blower
installation instructions for actual ratings.
For installations with CABP3 blowers:
• Installation with a CABP3 blower requires Dacor adapt-
er kit # AERVCAB.
• The blower assembly is mounted to the front of the
downdraft vent with the exhaust pointing in the desired
direction. See page 10.
• The CABP3 blower output connects directly to 3 ¼ x 10
rectangular duct.
1
5
/
8
x 16 duct
transistion
5”
X
3 ¼ x 10 to duct work
2 x 16, connects to
side or bottom exhaust
on downdraft
1"
(2.5 cm)
5"
(12.7 cm)
1
5
/
8
x 16 Duct Transition
9
Duct installation requirements for all blowers:
• All duct work materials (including screws and duct tape)
must be purchased separately by the customer.
• When planning new duct work, always look for the
shortest, most direct route to the outside. See page
7 for examples.
• You can increase the duct size over the duct run if
desired. To prevent a back draft, never decrease the
duct size over the run.
• Do not rely on duct tape alone to seal duct joints.
Fasten all connections with sheet metal screws and
tape all joints with certified silver tape or duct tape.
Installation Specifications
Rear Exhaust Knock Out (3 ¼ x 10)
3”
Vertical center line of rear exhaust knock out lines up with vertical
center line of chassis
On 46” and 48” wide models, the vertical center line of bottom knock-
out lines up with vertical center line of chassis
On 30” and 36” wide models, the vertical center line of bottom knock-
out is offset 3”
Side Exhaust Knock Outs (1
5
/
8
x 16)
Bottom Exhaust Knock Out (1
5
/
8
x 16)
Motor
cover
Front of unit
26" (66.0 cm)
6 1/4"
(15.9 cm)
1 1/8"
(2.9 cm)
C
L
C
L
C
L
Exhaust Knock-out Locations for Use with
REMP and ILHSF Series Blowers
• Use sheet metal screws as required to support the duct
weight.
• To prevent back-drafts, a damper at the duct outlet may
also be required.
• Make sure duct work does not interfere with floor joists
or wall studs.
• With concrete slab construction, “box-in” the duct work
and blower wiring to prevent collapsing or other dam-
age when the wet concrete is poured.
• Cross-drafts or air currents from adjacent open win-
dows or doors, heating/air conditioning outlets, ceiling
fans and recessed ceiling lights reduce vent efficiency.
• System exhaust location (see page 8) must take
into account accumulated snowfall, where applicable.
10
Installation Specifications
Model A B C
ERV3015
12 1/8”
(30.7 cm)
5 5/8”
(14.4 cm)
1 3/4”
(4.4 cm)
ERV3615
9 3/4”
(24.8 cm)
8”
(20.3 cm)
4 1/4”
(10.8 cm)
ERV
ADAPTER
8 7/8" (22.5 cm)
from back of ERV
cutout to center
line of CABP3
exhaust in any
orientation
Bottom exhaust
configuration shown
DUCT
C
L
CABP3
Cooktop
29 1/4”
(74.3 cm)
Duct connection
center line
C
Downdraft vent
center line
Countertop
3
1
/4 x 10
duct connection
Duct connection
center line
B
Downdraft vent
center line
Countertop
3
1
/4 x 10
duct
connection
15 3/8”
(39.1 cm)
Duct connection
center line
A
Downdraft vent
center line
Countertop
3
1
/4 x 10
duct
connection
26 1/4”
(66.7 cm)
Exhaust Locations and Side Dimensions
for CABP3 Cabinet blower
Exhaust Locations and Dimensions
for CABP3 Cabinet Blower Installations
(ERV3015, ERV3615 only)
Front Exhaust Dimensions
CABP3 Blower - Bottom Exhaust
Front Exhaust Dimensions
CABP3 Blower - Right Exhaust
Front Exhaust Dimensions
CABP3 Blower - Left Exhaust
11
Installation Specifications
Calculating the Maximum Duct Run Length
• For optimal performance, consult a qualified HVAC
specialist when designing the duct system.
• Do not use duct work that is smaller in cross-sectional
area than the required duct sizes in the tables below.
• Keep the duct run as short as possible for best perfor-
mance and never exceed the maximums stated in the
table below right.
• The maximum duct length for the downdraft vent sys-
tem depends on the blower model used and the num-
ber of elbows and transitions. The Equivalent Number
of Feet for each elbow and transition (see table below)
must be subtracted from the maximum straight length
to compensate for wind resistance. To determine the
maximum allowable length of the duct work, subtract all
of the equivalent lengths of the elbows and transitions
listed below from the Blower Maximum Duct Straight
Length (see table right).
For example, for a downdraft vent system using 3 ¼ x 10
rectangular duct, two (2) 3 ¼ x 10 90° elbows, a 3 ¼ x 10
rectangular to 10” round transition, and a REMP16 remote
blower:
• From the Blower Maximum Duct Straight Length
table below, the maximum length without transitions
and elbows is 60 feet.
• The equivalent length of each 90° elbow is 15 feet.
• The equivalent length of 45° elbow is 2 feet.
• The equivalent length of the transition is 4 feet.
• The total equivalent length of the above components is:
15 feet + 15 feet + 4 feet + 2 feet = 36 feet.
• The maximum amount of straight duct that can be used
with a REMP16 and the above components is: 60 feet -
34 feet = 24 feet.
Equivalent Number of Feet (Nominal) -
Duct Elbows and Transitions
45° elbow
8 inch
3 feet
3 ¼ x 10
45° elbow
7 feet
45° elbow
10 inch
2 feet
3 ¼ x 10
90° elbow
15 feet
90° elbow
8 inch
7 feet
3 ¼ x 10
90° flat elbow
20 feet
90° elbow
10 inch
5 feet
3 ¼ x 10
to 8” round
transition
4 feet
90° 3 ¼ x 10
to 8” round
transition
25 feet
3 ¼ x 10
to 10” round
transition
4 feet
Roof cap * Wall cap** *
* The equivalent lengths of roof and wall caps vary with
model and configuration. For equivalent length, contact the
manufacturer or a qualified HVAC specialist.
** Not applicable for REMP series blowers.
Duct Work Design Tips
• Wherever possible, reduce the number of transitions
and turns to as few sharp angles as possible. Two
staggered 45° angles are better than one 90°. Keep
turns as far away from the hood exhaust as possible,
with as much space between each bend as possible.
• For best performance, use round duct instead of rect-
angular when possible, especially when elbows are
required.
• If multiple elbows are used, try to keep a minimum of
24” of straight duct between them. Avoid “S” or “back to
back” configurations of adjacent elbows.
• Do not use flexible metal duct.
Blower
Used
Blower Maximum Duct Straight Length
8 Inch Duct 10 Inch Duct
3 ¼ x 10
Duct
CABP3
40 feet
(12.2 m)
30 feet
(9.2 m)
30 feet
(9.2 m)
ILHSF8
50 feet
(15.2 m)
40 feet
(12.2 m)
40 feet
(12.2 m)
ILHSF10
60 feet
(18.3 m)
70 feet
(21.3 m)
60 feet
(18.3 m)
REMP3
50 feet
(15.2 m)
40 feet
(12.2 m)
40 feet
(12.2 m)
REMP16
60 feet
(18.3 m)
70 feet
(21.3 m)
60 feet
(18.3 m)
12
Installation Preparation
Verify Package Contents
1. Unpack the unit and verify that all required parts have
been provided. If any item is missing or damaged,
please contact your dealer immediately. Do not install a
damaged or incomplete appliance. The customer must
report cosmetic issues within 30 days of installation.
Parts List
• Product literature
• Anchoring legs (left - PN 36861, right - PN 36862)
• 2 wood screws, #14 x 2 1/2 (PN 83047)
• 3 wire nuts
• 1
5
/8 x 16 to 3 ¼ x 10 duct transition (PN 13768)
• 2 sheet metal screws, #10 x 1/2 (PN 83022)
• 2 keps nuts, 1/4-20 (PN 83049)
• 2 flat washers, 1/4-20 (PN 83203)
• Insulation foam (tape)
Installation with CABP3 blower requires Dacor adapter kit
# AERVCAB. Kit includes adapter, wiring diagram label
(PN 106770), 3 wing nuts (PN 83035), 3 flat washers (PN
83008) and 6 lock washers (PN83340).
WARNING
• If the electrical service (electrical outlet) does not meet
the Electrical Specifications on page 2, do not
proceed with the installation. Call a licensed electrician
and have an electrical outlet installed that meets the
specifications.
• Install the vent only in a vertical orientation. Do not
mount the vent on a slant or angle.
• Do not enlarge or modify the exhaust knock-outs or
cut an exhaust hole in a location on the chassis other
than those shown. Doing so may cause an increase in
noise and decrease performance.
NOTE: The downdraft vent installs in the back of the cut-
out, separate from the range or cooktop. Install the down-
draft vent before installing the range or cooktop.
2. Start by loosely attaching the anchoring legs to the
studs on the left and right sides of the downdraft vent
using the provided Keps nuts and washers.
Installation Preparation for Downdraft Vent
with ILHSF or REMP Series Blower:
NOTE: For units using the CABP3 cabinet blower, skip to
Installation Preparation for Downdraft Vent with CABP3
Cabinet Blower, on facing page.
1. Remove the appropriate side, back or bottom exhaust
knockout, depending on the desired exhaust configu-
ration, from the downdraft vent chassis by cutting the
metal cross overs and removing the insert (see below).
2. Cut and remove the foil material inside the knock-out
hole. If you fail to remove the foil, the vent will not work.
• If the unit will vent through the bottom or side,
install the suppled 1
5
/8 x 16 to 3 ¼ x 10 transition
to the exhaust location. Before installing, peel the
protective backing off the foam tape and apply it to
the transition flanges. Attach the transition with the
provided sheet metal screws (see below).
• If the unit will exhaust air from the back, attach a
3 ¼ x 10 duct to the vent hole created by removing
the knock-out on the back of the unit.
3. Skip to Installing the Downdraft Vent in the Cutout
on page 13.
Installation Instructions
Back of unit
Side
knock-out
Side
knock-out
Bottom knock-out
Rear knock-out with
metal cross overs
shown
Put nuts/
washers on
studs
Front of unit
Anchor leg
Transition side
installation
Transition bottom
installation
Attach sealing
foam
13
Installing the Downdraft Vent in
the Cutout
1. Cut a hole in the cabinet to allow the duct work to pass
through to the floor or wall for the planned duct system
layout. Use the dimensions on pages 9 and 10 to
determine the hole center line locations. If using the 2” x
16” to 3 1/4” x 10” transition (REMP and ILHSF blower
installations), the hole may need to be enlarged slightly.
2. Gently slide the vent into the rear of the countertop cut-
out with the electrical access panel toward the front.
3. Adjust the anchoring leg height so that the top of the
downdraft vent rests on the counter, then tighten the
hex nuts. Secure the anchoring legs to the cabinet floor
with the provided wood screws.
Adapter Installation for CABP3 Blower:
(optional, ERV3015 and ERV3615 only)
1. Remove the front cover so that the AERVCAB cabinet
blower adapter can be installed. To do so, remove and
retain the three (3) wing nuts and three (3) flat washers
on the front of the unit. Discard the three (3) lock wash-
ers (they will be replaced). Tilt the cover out and pull
up. to remove it.
2. Peel the backing off of some of the foam tape included
with the adapter. Attach it to the right and left flanges.
3. Hold the adapter in front of the opening on the front
of the unit with the adapter’s studs on top and all the
flanges closest to the downdraft vent chassis.
4. Slide the bottom flange on the adapter into the bottom
retainer bracket on the downdraft vent at an angle.
Attach the adapter using the three (3) wing nuts and
Installation Instructions
Cover
Front of unit
Rear corner of cutout
(back of downdraft vent)
plumbed down
Exhaust: size and location
varies with installation type
Front of unit
Floor
Top of vent resting
on countertop
Electrical access
panel
Anchor leg
Adapter
Front of unit
Studs
Bottom retainer bracket
Insert bottom
flange into
bottom retainer
bracket
Attach foam
to right/left
flanges
flat washers removed in
step 1 and three (3) of
the lock washers from the
adapter kit.
14
Installation Instructions
Cabinet Blower Installation:
(optional, ERV3015 and ERV3615 only)
1. Locate the wiring diagram label included with the
adapter kit. Peel the protective backing off and place it
over the existing label on the CABP3 blower as shown.
2. Locate the foam tape supplied with the downdraft vent.
Place the blower on the floor in the orientation it will be
mounted on the front of the downdraft vent. Peel the
backing off the included foam tape and attach it to the
right and left flanges of the blower base plate.
3. With the exhaust in the desired orientation, slide the
bottom flange of the CABP3 blower base plate behind
the tab on the bottom of the adapter mounted to the
front of the downdraft vent.
4. Cover the opening on the adapter by pushing the
blower against it. Make sure that the foam tape cre-
ates a good seal on the right and left side of the open-
ing. Center the blower base plate horizontally over the
opening on the front of the adapter.
5. Install the adapter top retainer bracket over the blower
base plate flange. Secure it in place with the three (3)
wing nuts, lock washers and flat washers included with
the adapter.
CABP3
Top retainer
bracket
Insert bottom flange into
tab at bottom of adapter
Attach foam
to right/left
flanges
Adapter
New label
Existing
label
ILHSF or REMP Series Blower Installation
If using a ILHSF or REMP series blower, install it according
to the blower installation instructions.
Duct Work Installation
WARNING
Tape all duct joints securely to prevent combustion
by-products, smoke or odors from entering the home.
Doing so will also improve system efficiency.
Install the duct work according to the Installation
Specifications section. Use sheet metal screws and duct
tape to connect and seal all of the pieces. Support the duct
weight as necessary to ensure sealed joints.
Electrical Installation
WARNING
• ELECTRIC SHOCK HAZARD - Do not connect the
downdraft vent power plug to the electrical outlet until
installation is complete.
• Failure to complete electrical connections properly
may result in an electric shock hazard or a damaged
or non-functional system. Follow the wiring diagrams
carefully to ensure a proper installation. Do not
change the factory wired terminal connections inside
the electrical access panel for the downdraft vent or
the blower.
• To avoid an electric shock hazard and to prevent dam-
age route all wiring away from hot surfaces.
1. For ILHSF and REMP blower installations, run the wir-
ing/conduit line used to supply power from the down-
draft vent to the blower parallel to the duct work.
2. Remove the cover from the downdraft vent electrical
access panel.
3. Connect the wiring/conduit to the blower as shown in
the wiring diagrams below and the facing page accord-
ing to local codes and ordinances. Make sure all ter-
minal connections, including the factory wired connec-
tions, are tight. Replace the electrical access panel.
Range/Cooktop Installation
Install the range or cooktop according to its installation
instructions.
15
Installation Instructions
Floor
Example of Electrical Installation
with ILHSF or REMP Series Blower
(Side View)
REMP16
remote blower
Connect wires/conduit
according to remote
blower installation
instructions
Downdraft vent
Range
Wiring/conduit from
downdraft vent to remote
(or in-line) blower
See Downdraft Vent
Electrical Access
Panel, above
Electrical Installation - CABP3 Cabinet Blower
Downdraft Vent Electrical Access Panel
Front of unit
Wire Colors : Black = Line (L), White = Neutral (N),
Green = Ground (Gnd)
Electrical connection
from downdraft vent,
match Wire Colors
CABP3 cabinet
blower
Downdraft vent
blower wiring
access hole
Ground
Power
Input
Blower
Output
Blower power wiring/conduit.
Connect other end of wires
to blower terminal block.
Wires to power plug.
Pre-wired at factory.
Do not modify.
Attach ground wire
as shown
Match wire colors to
terminals as shown.
BLACK
WHITE
GREEN
Electrical access
panel
16
Installation Instructions
Verifying Proper Operation
WARNING
• Read the downdraft vent use and care manual com-
pletely before operation.
• Install all of the front filters prior to operating the
downdraft vent. Refer to the use and care manual for
filter installation instructions.
CAUTION
To prevent damage to the downdraft vent power cord,
route it away from the surfaces of the range or cooktop
before connecting it.
1. Make sure the power switch on the top of the downdraft
vent is in the up position.
2. Plug the downdraft vent power plug into the electrical
outlet.
3. Press the power switch once to raise the vent to its
operating position.
4. Once in the up position the vent should begin to draw
air. Turn the variable speed control switch in both direc-
tions to verify that the system is operating correctly.
5. Press the top cap up/down switch once to lower the
vent.
6. Make sure that the top cap on the downdraft vent
intake does not catch on the back edge of the cooktop
or range when the intake is lowered. If interference
occurs, adjust the position of the cooktop or range.
Failure to eliminate any interference may result in per-
manent damage to the vent.
If the downdraft vent is not operational after installa-
tion:
• Make sure that power is being supplied to the unit.
• Make sure that power is being supplied to the blower
from the downdraft vent.
• If the vent will not raise properly or makes a scraping
sound check for obstructions interfering with the raising
of the unit.
If the downdraft vent still does not function after perform-
ing the above checks, do not attempt to repair it yourself.
Contact Dacor Distinctive Service at 793-0093 ex. 2822. Be
sure to have all model and serial numbers from the product
data labels for the downdraft vent and the blower available
when you call.
Dacor is not responsible for the cost of correcting problems
caused by a faulty installation.
Installation Checklist
Are the anchor legs extended down to make contact
with the floor and tightened into place? Are the anchor
legs fastened to the floor? Is the unit level?
Is the duct work completely installed? Are all joints
attached with sheet metal screws and wrapped with
duct tape?
Are both ends of the blower power cable connected (to
the downdraft vent and to the blower itself)?
Are the vent filters installed according to the use and
care manual instructions?
Is the power cord routed away from the hot surfaces of
the range or cooktop.
Is the unit connected to an electrical outlet that meets
the electrical specifications in these instructions?
Has proper operation been verified?
Has the warranty been activated on-line or the warranty
card been filled out completely and mailed?
17
Technical Data
STUD
CHASSIS
GROUND
GROUNDPOWER
INPUT
BLOWER
OUTPUT
GNDL2 N1L1N2 GND
COM
COM
NO
NO
UP
LIMIT SWITCH
DOWN
LIMIT SWITCH
COM NCNO
NC
NC
REMOTE POT
SNORKEL SWITCH
COM
N
NO
RELAY
SPEED CONTROL
RED
RED
BLUE
BLUE
RED
BLK
ORNG
ORNG
BLK
YEL
YEL
WHT
L
BLK
WHT
WHT
Wiring Diagram - All Models
CABP3 Cabinet Blower Ratings
CABP3 Cabinet blower Airflow*
Nominal 600 CFM
Actual 585.6 CFM
* At zero inches static pressure. Performance varies based
on duct system configuration.
Electrical Rating: 4 Amps. @ 120 Vac, 60 Hz.
For ILHSF or REMP series blower ratings, see the blower
installation instructions.
Airflow CFM (Cubic feet/minute)
Static pressure - inches of water
0
1.0
2.0
3.0
4.0
5.0
100 200 300 400 500 600
CABP3 Blower Performance
Dacor●14425ClarkAvenue,CityofIndustry,CA91745●Phone:(800)793-0093●Fax:(626)403-3130●www.dacor.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Dacor MRV48ERS Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI