It may be necessary to move the opposite set point to
achieve the desired setting. Once the desired temperatures
are selected, return the key to the RUN position.
Alarm Lockout
e alarm control module can be locked to prevent changes to
the set points, even with the access key.
■ Once caution set point and alarm set point has been set,
remove the screws from upper right and lower le corners of
front plate. Remove the control module from the 4" x 4" box.
■ Enable set point lockout
Enable
- DIP Switch 2 = ON
Disable - DIP Switch 2 = OFF
■ Reinstall the control module into
the 4" x 4" box.
■ When the key is placed in the SET
position, the display will alternate
between a set point temperature
and the characters LOC.
■ Set point temperatures can be viewed but unable to change.
Alarm Operation
Normal Mode:
■ Green Valve (normal) LED LED is lit to indicate
normal operation; that water temperature is below set
point temperature
and can ow. If optional solenoid valve
is installed, it is in the open position.
■ Flashing Red Dot
A ashing red dot (Heart Beat)
in the lower right corner of the display indicates that the
systems processor is running.
Caution Mode:
■ Amber Caution LED LED will blink and the audible
signal will sound briey every 60 seconds when the
temperature reaches the caution set point indicating
attention should be paid to the system.
■ Green Valve (normal) LED LED will remain lit
indicating normal operation.
Alarm Mode:
■ Red Alarm LED
LED will blink and the Amber
Caution LED
will go out if the output temperature
reaches the alarm set point. A continuous pulsing audible
signal will also be heard.
■ Green Valve (normal) LED LED will go out indicating
no water can ow. (If solenoid is installed, valve will close)
Signals mean immediate attention should be given to the system.
Alarm Hysteresis:
■ Amber Caution LED LED will light if the temperature
decreases below the alarm set point indicating that the
temperature is lower than the alarm set point but still
greater than the caution set point.
Alarm condition/mode will still be in eect. e system
will only reset when the temperature decreases below the
caution set point.
■ Relay (customer supplied option) -
Connect relay coil wires
between the relay and the valve power output terminals on
the back of the control module as identied in Figure 2. Note
that there is no polarity required between connections.
Fahrenheit / Celsius Temperature Display Setting
■ Select either Fahrenheit or Celsius
display units by setting Dip Switch
on control module circuit board.
Fahrenheit
DIP Switch 1 = OFF
Celsius
DIP Switch 1 = ON
Electrical Enclosure Box
■ Secure control module in electrical box using the two (2)
screws provided with box. Screws should be inserted into the
upper right and lower le corners of the control module.
■ Do not remove upper le and lower right screws securing the
control module together.
Temperature Set Point Adjustments
NOTE: The following settings were set at the factory:
Caution Alert Temperature = 114˚F (45.6˚C)
High Limit Alarm Temperature = 120˚F (48.9˚C)
■ Reset temperature
settings
- Reset the above
factory temperature
settings as required by
the application to prevent
erratic temperature
readings that can
prematurely activate the
alarm.
■ SET key position - Turn
key from the RUN position
to the SET position.
■ Identify caution set
point temperature (A)
Press SELECT keypad
button until A appears in the rst eld of the LED display.
e three (3) digits immediately following the A identies the
current caution set point temperature.
■ Set caution set point temperature - Pressup
down
keypad arrow buttons located below the display to increase
or decrease temperature setting.
■ Identify alarm set point temperature (H) - Press SELECT
keypad button until H appears in the rst eld of the LED
display. e three (3) digits immediately following the H
identies the current alarm set point temperature.
■ Set alarm set point temperature - Press up
down
keypad arrow buttons located below the display to increase
or decrease temperature setting.
NOTE: Caution set point temperature cannot be set higher
than alarm set point temperature and alarm set point
cannot be set lower than caution set point temperature.
Page 2
Figure 4
Figure 5
Figure 3