Symmons TempControl HTA-100 Installation And Service Instructions

Type
Installation And Service Instructions

Symmons TempControl HTA-100 is a high-temperature audio-visual alarm system designed to monitor and control warm or hot water temperature, alerting you when it exceeds a preset limit. It features:

  • Temperature monitoring: The system monitors water temperature using a temperature probe, alerting you when it approaches or exceeds a set caution or alarm temperature.
  • Audio-visual alarms: When the caution set point is reached, the system emits a brief audible signal and blinks an amber LED. If the alarm set point is reached, it triggers a continuous audible signal, blinks a red LED, and turns off a green LED indicating normal operation.

Symmons TempControl HTA-100 is a high-temperature audio-visual alarm system designed to monitor and control warm or hot water temperature, alerting you when it exceeds a preset limit. It features:

  • Temperature monitoring: The system monitors water temperature using a temperature probe, alerting you when it approaches or exceeds a set caution or alarm temperature.
  • Audio-visual alarms: When the caution set point is reached, the system emits a brief audible signal and blinks an amber LED. If the alarm set point is reached, it triggers a continuous audible signal, blinks a red LED, and turns off a green LED indicating normal operation.
Connect 120 VAC line voltage to the primary side of the
transformer as displayed in Figure 1.
12V
6V
T
coil
connections
Relay 12 VDC @ <80mA
(customer supplied option)
Remote monitoring
system connections
Temperature probe and
1/4" NPT male tting
Water hammer
arrestor (optional)
Tee tting
(required, see
options)
Alarm
control
module
Water ow
Transformer
12 VAC/15 VA
Solenoid valve (optional)
12 VDC, 10 Watts max
120 VAC Power
25'probe cable
(optional lengths)
Connect the 12 VAC secondary side of the transformer to
the 12 VAC power input terminals on the back of the alarm
control module as identied in Figure 2 below. Note that
there is no polarity required for the input terminals.
ON
OFF
Fuses #229
1.5A / 250VP
12 VAC
power input
12 VDC valve
power output
(optional)
Temperature
input probe
DIP Switches
Rear view of Alarm Control Module
12 VDC relay
power output
(optional)
Temperature Probe - Plug probe into the connector on
the backside of the control module as identied in Figure2
above. Note that the connectors are keyed and will only mate
in one direction. (optional cable lengths are available)
Solenoid Valve (optional) -
Connect coil wires between the
solenoid valve and the valve power output terminals on the
back of the control module as identied in Figure 2 above.
Note that there is no polarity required between connections.
High Temperature Audio Visual Alarm System, HTA-100
Installation and Service Instructions
TempControl
®
General Information
Alarm System - TempControl High Temperature Audio
Visual Alarm System will monitor, alert and alarm when
water temperature exceeds preset limit. It best ts
applications where there is a critical need to accurately
monitor and control warm or hot water temperature.
Solenoid Valve (optional) - When alarmed, the valve is
de-energized and closes to provide complete shutdown of
the water ow.
Relay (customer supplied option) - Installed relay enables
remote monitoring of alarm control module.
Caution Set Point - is the lower of the two set point
temperatures that alerts when the output water is
approaching an undesirable temperature limit.
Alarm Set Point - Once the output temperature reaches the
alarm set point, the system goes into full alarm mode.
Installation
Important: All piping should be thoroughly
ushed prior to installation to prevent debris from
interfering with the solenoid operation. Do not run
solenoid power and temperature probe through
same conduit.
Piping
Tee Fitting - Required; appropriate size tting for
application purchased seperately (see options).
Temperature Probe - Locate probe as far downstream from
mixing valve as is reasonably possible.
a. Slide connector nut and ferrule piece over the probe.
b. Slide probe 1/2” to 2/3” into the tee tting.
c. Slide the ferrule and connector nut down the probe sha
and tighten in place.
Solenoid Valve (optional, 12 VDC, 10 Watts, normally
closed) - Install valve directly before the temperature probe in
any orientation. Make note of the correct direction of the water
ow as marked on the valve.
Electrical
Mount the 4" x 4" supplied mounting box in a dry location
within wiring reach of the temperature probe and solenoid
valve if used.
Mount supplied transformer.
(120 VAC – 12 VAC/15 VA UL listed, CSA certified class 2)
Figure 1
Figure 2
For California Residents
WARNING: is product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
It may be necessary to move the opposite set point to
achieve the desired setting. Once the desired temperatures
are selected, return the key to the RUN position.
Alarm Lockout
e alarm control module can be locked to prevent changes to
the set points, even with the access key.
Once caution set point and alarm set point has been set,
remove the screws from upper right and lower le corners of
front plate. Remove the control module from the 4" x 4" box.
Enable set point lockout
Enable
- DIP Switch 2 = ON
Disable - DIP Switch 2 = OFF
Reinstall the control module into
the 4" x 4" box.
When the key is placed in the SET
position, the display will alternate
between a set point temperature
and the characters LOC.
Set point temperatures can be viewed but unable to change.
Alarm Operation
Normal Mode:
Green Valve (normal) LED LED is lit to indicate
normal operation; that water temperature is below set
point temperature
and can ow. If optional solenoid valve
is installed, it is in the open position.
Flashing Red Dot
A ashing red dot (Heart Beat)
in the lower right corner of the display indicates that the
systems processor is running.
Caution Mode:
Amber Caution LED LED will blink and the audible
signal will sound briey every 60 seconds when the
temperature reaches the caution set point indicating
attention should be paid to the system.
Green Valve (normal) LED LED will remain lit
indicating normal operation.
Alarm Mode:
Red Alarm LED
LED will blink and the Amber
Caution LED
will go out if the output temperature
reaches the alarm set point. A continuous pulsing audible
signal will also be heard.
Green Valve (normal) LED LED will go out indicating
no water can ow. (If solenoid is installed, valve will close)
Signals mean immediate attention should be given to the system.
Alarm Hysteresis:
Amber Caution LED LED will light if the temperature
decreases below the alarm set point indicating that the
temperature is lower than the alarm set point but still
greater than the caution set point.
Alarm condition/mode will still be in eect. e system
will only reset when the temperature decreases below the
caution set point.
Relay (customer supplied option) -
Connect relay coil wires
between the relay and the valve power output terminals on
the back of the control module as identied in Figure 2. Note
that there is no polarity required between connections.
Fahrenheit / Celsius Temperature Display Setting
Select either Fahrenheit or Celsius
display units by setting Dip Switch
on control module circuit board.
Fahrenheit
DIP Switch 1 = OFF
Celsius
DIP Switch 1 = ON
Electrical Enclosure Box
Secure control module in electrical box using the two (2)
screws provided with box. Screws should be inserted into the
upper right and lower le corners of the control module.
Do not remove upper le and lower right screws securing the
control module together.
Temperature Set Point Adjustments
NOTE: The following settings were set at the factory:
Caution Alert Temperature = 114˚F (45.6˚C)
High Limit Alarm Temperature = 120˚F (48.9˚C)
Reset temperature
settings
- Reset the above
factory temperature
settings as required by
the application to prevent
erratic temperature
readings that can
prematurely activate the
alarm.
SET key position - Turn
key from the RUN position
to the SET position.
Identify caution set
point temperature (A)
Press SELECT keypad
button until A appears in the rst eld of the LED display.
e three (3) digits immediately following the A identies the
current caution set point temperature.
Set caution set point temperature - Pressup
down
keypad arrow buttons located below the display to increase
or decrease temperature setting.
Identify alarm set point temperature (H) - Press SELECT
keypad button until H appears in the rst eld of the LED
display. e three (3) digits immediately following the H
identies the current alarm set point temperature.
Set alarm set point temperature - Press up
down
keypad arrow buttons located below the display to increase
or decrease temperature setting.
NOTE: Caution set point temperature cannot be set higher
than alarm set point temperature and alarm set point
cannot be set lower than caution set point temperature.
Page 2
Figure 4
Figure 5
Figure 3
T
PARALLEL
CONNECTION TO
SOLENOID VALVE
(total current @ <833 mA )
(valve current @ <750 mA)
(relay coil current @ <80 mA)
12V-DC RELAY
(CUSTOMER SUPPLIED)
BUILDING
MONITORING
SYSTEM
CONNECTIONS
HIGH TEMPERATURE ALARM - SYSTEM OPERATING CONDITIONS:
System OFF no current to valve or relay valve closed/relay open no alarm
System ON/SET – current to valve and relay – valve open/relay closed – no alarm
System ON/TRIPPED no current to valve or relay valve closed/relay open alarm
NOTES:
1-All current values are maximums not to exceed
2-The above system design does not transmit “analog or digital” data to the building monitoring system
3-The above system design only provides for a “binary or on/off” signal to the building monitoring system
4-Building monitoring system connections and/or signals are defined per the customer application
Alarm Control Module
Page 3
Problem Cause
Memory problem with circuit board
“Up arrow” button shorted or stuck on power up
“Down arrow” button shorted or stuck on
power up
Key switch in “set” position on power up
Key switch in “override” position on power up
Calibration error
Power up without probe attached or with
probe wire broken
Set point lockout enabled
Solution (Follow service instructions)
Contact factory technical service
Ensure button is not depressed; if this does
not correct problem contact factory technical
assistance
Ensure button is not depressed; if this does
not correct problem contact factory technical
assistance
Turn key to run position; if this does not
correct problem contact factory technical
assistance
Turn key to run position; if this does not
correct problem contact factory technical
assistance
Contact factory technical service
Reconnect probe; if this does not correct
problem contact factory technical assistance
Set DIP switch 2 to the off position
Front Panel Display: ERR1
Front Panel Display: ERR2
Front Panel Display: ERR3
Front Panel Display: ERR4
Front Panel Display: ERR5
Front Panel Display: CAL
Front Panel Display: PRB1
Front Panel Display ashes: LOC
Set point cannot be adjusted
No power, no display or
erratic behavior
One or both fuses are blown
Check and replace 1.5A fuses located
on circuit board
TROUBLE SHOOTING CHART
Symmons Industries, Inc.
31 Brooks Drive
Braintree, MA 02184
Phone: (800) 796-6667
Fax: (800) 961-9621
Copyright © 2016 Symmons Industries, Inc.
www.symmons.com
ZV-3004 REV A
012116
Override Key
Alarm Set Point - once alarm set point temperature has been
reached, only personnel with the override key can initiate water
flowing in the system.
Override Position - Insert the key into the control module
front panel and turn the key switch to the override position.
e solenoid valve is held open allowing water to ow.
All users should be clear of the water ow due to
excessive temperature owing until the system is
corrected.
SILENCE Keypad Button - e audible signal may be
silenced by depressing the SILENCE keypad button located
on the panel. e audible signal will only be silenced for 60
seconds and will resume at the completion of the cycle.
Key Removal - e key cannot be removed in the override
position
preventing the solenoid from being held open and
le unattended.
Alarm Hysteresis - As the system output temperature is
corrected, the above Alarm Hysteresis conditions will occur.
Green Valve (normal) LED
LED will blink and an
audible signal will be heard regardless of the current mode
when the key switch is in the override position and the
silence period has expired.
Options
Solenoid Valves 12 VDC/10 Watts max (normally closed)
SV-102 ..................... 1/2" NPT
SV-200 ..................... 3/4" NPT
SV-400 ..................... 1" NPT
SV-500 ..................... 1-1/4" NPT
SV-700/900 .............1-1/2" NPT
SV-1000 ................... 2" NPT
Water Hammer Arrestor
WHA-1 .....................1" NPT water hammer arrestor
Tee Fittings
TF-102 ..................... 1/2" x 1/2" x 1/4" NPT
TF-200 ..................... 3/4" x 3/4" x 1/4" NPT
TF-400 ..................... 1" x 1" x 1/4" NPT
TF-500 ..................... 1-1/4" x 1-1/4" x 1/4" NPT
TF-700/900..............1-1/2" x 1-1/2" x 1/4" NPT
TF-1000 ................... 2" x 2" x 1/4" NPT
Temperature Probe Cables - additional lengths
TPC-50 ....................50' probe cable
TPC-100 ..................100' probe cable
Relay (customer supplied option)
HTA-100 Alarm System Kit - includes the following:
Programmable alarm control module with two system
operation keys and stainless steel front panel
Electrical mounting enclosure box; 4" x 4"
Transformer; 120 VAC, 12 VAC/15 VA, UL listed/
CSA certified class 2
Solid state temperature probe with 25' cable and 1/4"
male compression fitting for attaching probe
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Symmons TempControl HTA-100 Installation And Service Instructions

Type
Installation And Service Instructions

Symmons TempControl HTA-100 is a high-temperature audio-visual alarm system designed to monitor and control warm or hot water temperature, alerting you when it exceeds a preset limit. It features:

  • Temperature monitoring: The system monitors water temperature using a temperature probe, alerting you when it approaches or exceeds a set caution or alarm temperature.
  • Audio-visual alarms: When the caution set point is reached, the system emits a brief audible signal and blinks an amber LED. If the alarm set point is reached, it triggers a continuous audible signal, blinks a red LED, and turns off a green LED indicating normal operation.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI