Robur GA ACF HT Installation, Use And Maintenance Manual

Type
Installation, Use And Maintenance Manual

This manual is also suitable for

Installation, use and maintenance manual
gas powered
absorption chiller
GA ACF
This Installation, use and maintenance manual has been drawn up and printed by Robur S.p.A.; whole or partial
reproduction of this Installation, use and maintenance manual is prohibited.
The original is led at Robur S.p.A.
Any use of this Installation, use and maintenance manual other than for personal consultation must be previously
authorised by Robur S.p.A.
The rights of those who have legitimately led the registered trademarks contained within this publication are not
aected.
With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the
data and contents of this Installation, use and maintenance manual without prior notice.
Revision: U
Code: D-LBR357
DISPOSAL
The appliance and all its accessories must be disposed of separately in accordance with the regulations in force.
Use of the WEEE symbol (Waste Electrical and Electronic Equipment) indicates that this product cannot be disposed of as household waste.
Proper disposal of this product helps to prevent potential negative consequences for the environment and human health.
Installation, use and maintenance manual – GA ACF
3
INDEX OF CONTENTS
I Introduction .............................................................................
p.4
Recipients ..........................................................................
p.4
Control device ..................................................................
p.4
II Symbols and denitions ...............................................
p.4
II.1 Key to symbols .................................................................
p.4
II.2 Terms and denitions ....................................................
p.4
III Warnings......................................................................................
p.4
III.1 General and safety warnings ......................................
p.4
III.2 Conformity ........................................................................
p.5
III.3 Exclusions of liability and warranty ..........................
p.6
1 Features and technical data ......................................
p.7
1.1 Features ..............................................................................
p.7
1.2 Dimensions .......................................................................
p.8
1.3 Components ...................................................................
p.10
1.4 Electrical wiring diagram ...........................................
p.13
1.5 Electronic boards ..........................................................
p.14
1.6 Controls ............................................................................
p.15
1.7 Technical data ................................................................
p.16
2 Transport and positioning ........................................
p.17
2.1 Warnings ..........................................................................
p.17
2.2 Handling ...........................................................................
p.17
2.3 Appliance positioning .................................................
p.18
2.4 Minimum clearance distances..................................
p.18
2.5 Mounting base ...............................................................
p.18
3 Heating engineer ...............................................................
p.18
3.1 Warnings ..........................................................................
p.18
3.2 Hydraulic system ...........................................................
p.19
3.3 Hydraulic connections ................................................
p.19
3.4 Water circulation pump ..............................................
p.20
3.5 Antifreeze function .......................................................
p.20
3.6 Antifreeze liquid ............................................................
p.20
3.7 System water quality ...................................................
p.21
3.8 System lling ..................................................................
p.21
3.9 Fuel gas supply ..............................................................
p.21
4 Electrical installer ..............................................................
p.22
4.1 Warnings ..........................................................................
p.22
4.2 Electrical systems ..........................................................
p.22
4.3 Electrical power supply ...............................................
p.23
4.4 Adjustment and control .............................................
p.23
4.5 Water circulation pump ..............................................
p.26
5 First start-up ..........................................................................
p.27
5.1 Preliminary checks ........................................................
p.27
5.2 Electronic adjustment on the machine – Menus
and parameters of the S61 board ...........................
p.28
5.3 Modifying settings ........................................................
p.29
6 Normal operation ..............................................................
p.29
6.1 Warnings ..........................................................................
p.29
6.2 Switch on and o ..........................................................
p.29
6.3 Modifying settings ........................................................
p.29
6.4 Eciency ..........................................................................
p.29
7 Maintenance ..........................................................................
p.30
7.1 Warnings ..........................................................................
p.30
7.2 Pre-emptive maintenance .........................................
p.30
7.3 Scheduled routine maintenance .............................
p.30
7.4 Messages on the display ............................................
p.31
7.5 Restarting a locked-out unit .....................................
p.31
7.6 Periods of inactivity ......................................................
p.31
8 Diagnostics ..............................................................................
p.32
8.1 Operative codes.............................................................
p.32
Introduction
4
I
I INTRODUCTION
Installation, use and maintenance manual
This Manual is an integral part of the GA ACF unit and
must be handed to the end user together with the
appliance.
RECIPIENTS
This Manual is intended for:
End user, for appropriate and safe use of the appliance.
Qualied installer, for correct appliance installation.
Planner, for specic information on the appliance.
CONTROL DEVICE
In order to be able to work, the GA ACF unit needs a control de-
vice (DDC or external request), which must be connected by the
installer.
II SYMBOLS AND DEFINITIONS
II.1 KEY TO SYMBOLS
DANGER
WARNING
NOTE
PROCEDURE
REFERENCE (to other document)
II.2 TERMS AND DEFINITIONS
GA Appliance/Unit = equivalent terms, both used to designate
the GA Gas Absorption chiller.
TAC = Technical Assistance Centre authorised by Robur.
External request = generic control device (e.g. thermostat, tim-
er or any other system) equipped with a voltage-free NO contact
and used as control to start/stop the GA unit.
DDC Control (Direct Digital Controller) = optional Robur adjust-
ment device to control one or more Robur appliances (GAHP
heat pumps, GA chillers and AY00-120 boilers) in ON/OFF mode.
RB100/RB200 Devices (Robur Box) = optional interface devices
complementary to DDC, which may be used to broaden its func-
tions (heating/cooling/DHW production service demands, and
control of system components such as third party generators,
adjustment valves, circulators, probes).
GUE (Gas Utilization Eciency) = eciency index of gas chiller,
equal to the ratio between the chilling energy produced and the
energy of the fuel used (relative to NCV, net caloric value).
First start-up = appliance commissioning operation which may
only and exclusively be carried out by a TAC.
S61 Board = electronic board on the GA unit, to control all func-
tions and to provide interface with other devices and with the
user.
III WARNINGS
III.1 GENERAL AND SAFETY WARNINGS
Installer's qualications
Installation must exclusively be performed by a qualied
rm and by qualied personnel, with specic knowledge
on heating, cooling, electrical systems and gas applianc-
es, in compliance with the laws in force in the Country of
installation.
Declaration of conformity
Upon completing installation, the installing rm shall
issue to the owner/client the appliance's workmanlike
conformity declaration, according to national/local reg-
ulations in force and the manufacturer's instructions/
provisions.
Misuse
The appliance must only be used for the purposes for
which it has been designed. Any other use is deemed
hazardous. Incorrect use may aect operation, duration
and safety of the appliance. Adhere to the manufactur-
er's instructions.
Hazardous situations
Do not start the appliance in hazardous conditions, such
as: gas smell, problems with the plumbing/electrical/gas
system, parts of the appliance under water or damaged,
malfunctioning, disabling or bypassing control and safe-
ty devices.
In case of danger, request intervention by qualied per-
sonnel.
In case of danger, switch o the electrical power and gas
supplies only if this can be done in total safety.
Do not entrust children, persons with physical, sensory
or mental disabilities or persons with poor knowledge
and experience with use of the appliance.
Gas component tightness
Before performing any operation on gas ducting compo-
nents, close the gas valve.
Upon completing any procedure, perform the tightness
test according to regulations in force.
Warnings
Installation, use and maintenance manual – GA ACF
5
III
Gas smell
If you smell gas:
Do not use electrical devices such as telephones, mul-
timeters or other equipment that may cause sparks next
to the appliance.
Shut o the gas supply by turning the valve o.
Switch o the power supply via the external disconnect
switch in the power supply electrical panel.
Use a telephone away from the appliance to ask for inter-
vention from qualied personnel.
Moving parts
The appliance contains moving parts.
Do not remove guards during operation, and in any case
prior to disconnecting the power supply.
Burn hazard
The appliance contains very hot parts.
Do not open the appliance and do not touch internal
components before the appliance has cooled down.
Pressure vessels
The appliance has a sealed circuit classied as pres-
sure vessel, the tightness of which is tested by the
manufacturer.
Do not carry out any intervention on the sealed circuit or
on the appliance's valves.
Water-ammonia solution
The GA unit uses the ammonia-water absorption cycle.
The water-ammonia solution is contained in the sealed
circuit. The solution is harmful for health if it is ingested,
inhaled or comes in contact with the skin.
In the event of coolant leak keep away and disconnect
the power and gas supply (only if it is possible to do so
with no danger).
Ask for TAC intervention.
Electrocution hazard
Disconnect the electrical power supply before any oper-
ation on appliance components.
For electrical connections exclusively use compliant
components and according to the specications provid-
ed by the manufacturer.
Ensure the appliance cannot be accidentally switched
back on.
Earthing
Electrical safety depends on eective earthing system,
correctly connected to the appliance and installed ac-
cording to the regulations in force.
Distance from combustible or ammable materials
Do not deposit ammable materials (paper, diluents,
paints, etc.) near the appliance.
Limescale and corrosion
Depending on the chemical/physical properties of the
system water, limescale or corrosion may damage the
appliance (Paragraph 3.7
p.21
).
Check system sealing.
Avoid frequent top-ups.
Chloride concentration
The concentration of chlorides or free chlorine in the
system water must not exceed the values in Table
3.2
p.21
.
Aggressive substances in the air
Halogenated hydrocarbons containing chlorine and u-
orine compounds cause corrosion. The air of the installa-
tion site must be free from aggressive substances.
Switching the appliance o
Disconnecting the power supply while the appliance
is running may cause permanent damage to internal
components.
Except in the case of danger, do not disconnect the pow-
er supply to switch o the appliance, but always and ex-
clusively act through the provided control device (DDC
or external request).
In the event of failure
Operations on internal components and repairs may
exclusively be carried out by a TAC, using only original
parts.
In the event of failure of the appliance and/or breakage
of any component, do not attempt to repair and/or re-
store and immediately contact the TAC.
Routine maintenance
Proper maintenance assures the eciency and good op-
eration of the appliance over time.
Maintenance must be performed according to the man-
ufacturer's instructions (see Chapter 7
p. 30
) and in
compliance with current regulations.
Appliance maintenance and repairs may only be entrust-
ed to rms legally authorised to work on gas appliances
and systems.
Enter into a maintenance contract with an authorised
specialised rm for routine maintenance and for servic-
ing in case of need.
Use only original parts.
Decommissioning and disposal
If the appliance is to be disposed of, contact the manu-
facturer for its disposal.
Keep the Manual
This Installation, use and maintenance manual must al-
ways accompany the appliance and must be handed to
the new owner or installer in the event of sale or removal.
III.2 CONFORMITY
EU directives and standards
GA series absorption chillers are certied as conforming to
standard EN 12309 and comply with the essential requirements
Warnings
6
III
of the following Directives:
2016/426/EU "Gas Appliances Regulation" as amended and
added.
2014/30/EC "Electromagnetic Compatibility Directive" as
amended and added.
2014/35/EC "Low Voltage Directive" as amended and added.
2006/42/EC "Machine Directive" as amended and added.
2014/68/EU "Pressure Equipment Directive" as amended
and added.
Furthermore, they comply with the requirements of the follow-
ing standards:
EN 378 Refrigerating systems and heat pumps.
Other applicable provisions and standards
The design, installation, operation and maintenance of the sys-
tems shall be carried out in compliance with current applicable
regulations, depending on the Country and location, and in ac-
cordance with the manufacturer's instructions. In particular, reg-
ulations regarding the following shall be complied with:
Gas systems and equipment.
Electrical systems and equipment.
Heating and air conditioning systems, heat pumps and chill-
ers.
Fire safety and prevention.
Any other applicable law, standard and regulation.
III.3 EXCLUSIONS OF LIABILITY AND
WARRANTY
Any contractual or extra-contractual liability of the man-
ufacturer for any damage caused by incorrect installa-
tion and/or improper use and/or failure to comply with
regulations and with the manufacturer's directions/in-
structions shall be disclaimed.
In particular, the warranty on the appliance may be ren-
dered void by the following conditions:
Incorrect installation.
Misuse.
Failure to comply with the manufacturer's indications on
installation, use and maintenance.
Alteration or modication of the product or any part
thereof.
Extreme operational conditions or however outside of
the operational ranges set forth by the manufacturer.
Damages caused by external agents such as salts, chlo-
rine, sulphur or other chemical substances contained in
the installation water or present in the air of the instal-
lation site.
Abnormal actions transmitted to the appliance by the
plant or installation (mechanical stresses, pressure, vi-
brations, thermal expansion, electrical surges...).
Accidental damages or due to force majeure.
Features and technical data
Installation, use and maintenance manual – GA ACF
7
1
1 FEATURES AND TECHNICAL DATA
1.1 FEATURES
Operation
Based on the thermodynamic water-ammonia absorption cycle
(H
2
0–NH
3
), the appliance produces chilled water using natural
gas (or LPG) as primary energy and dissipating heat directly to
the outside air.
The thermodynamic cycle takes place within a hermetically
sealed circuit, in welded construction, perfectly tight, facto-
ry-tested, which does not require any maintenance or coolant
top-ups.
Mechanical and thermo-hydraulic components
Steel sealed circuit, externally treated with epoxy paint.
Multigas premix burner equipped with ignition and ame
detection managed by an electronic control unit.
Titanium stainless steel shell-and-tube water exchanger
(evaporator), externally insulated.
Air exchanger (condenser) with nned coil, with steel pipe
and aluminium ns.
Variable-ow microprocessor-controlled helicoidal mo-
tor-fan.
Control and safety devices
S61 electronic board with microprocessor, LCD display and
knob.
Circuit water ow switch.
Generator limit thermostat, with manual reset.
Automatically resettable ue gas thermostat.
Dierential air pressure switch on the combustion circuit.
Sealed circuit safety relief valve.
Bypass valve, between high and low-pressure circuits.
Ionization ame control box.
Double shutter electric gas valve.
Antifreeze functions for hydraulic circuit.
Heat recovery exchanger circulation pump relay (HR version
only).
Versions
The GA ACF unit is available in the following versions:
ACF standard, for residential/retail/industrial cooling sys-
tems with chilled water down to +3 °C.
HR with heat recovery exchanger, for residential/retail/in-
dustrial cooling systems with chilled water down to +3 °C,
plus recovery exchanger hot water up to +80 °C (e.g. DHW
production).
TK for heavy duty use, for process systems and applications
with chilled water down to +3 °C, in continuous operation
year round.
HT for very hot climates, for residential/retail/industrial cool-
ing systems with chilled water down to +5 °C, with outside
air up to 50 °C.
LB for negative temperatures, for cooling systems with
chilled water down to -10 °C (glycol indispensable).
Models ACF, TK, LB and HT have 2 chilled water inlet/outlet t-
tings, model HR has 4 chilled water and heat recovery exchanger
hot water inlet/outlet ttings.
1.1.1 Standard or silenced fan
According to the type of fan, all the GA ACF units are available
in two versions:
Standard fan, for applications that do not require a special
degree of noiselessness.
Silenced fan, for applications that require a high degree of
noiselessness.
Features and technical data
8
1
1.2 DIMENSIONS
Figure1.1 ACF standard version dimensions
A Position of holes for xing of anti-vibration joints
Figure1.2 ACF silenced version dimensions
A Position of holes for xing of anti-vibration joints
Features and technical data
Installation, use and maintenance manual – GA ACF
9
1
Figure1.3 ACF Service plate with plumbing and gas connections
A Water outlet connection Ø 1 1/4" F
B Water inlet connection Ø 1 1/4" F
G Gas connection Ø 3/4" F
Figure1.4 ACF-HR Service plate with plumbing and gas connections
G Gas connection Ø 3/4" F
Chiller - CHILLED WATER
D Outlet water tting Ø 1 1/4" F
C Water inlet connection Ø 1 1/4" F
Recovery exchanger - HOT WATER
A Water outlet connection Ø 1 1/4" F
B Water inlet connection Ø 1 1/4" F
Features and technical data
10
1
1.3 COMPONENTS
Figure1.5 Internal components - front view
1 Combustion air intake
2 Combustion blower
3 Gas valve
4 Electrical panel
5 Oil pump
6 Water inlet connection Ø 1 1/4" F
7 Water outlet connection Ø 1 1/4" F
8 Gas connection Ø 3/4" F
9 Room temperature probe
10 Fan






Features and technical data
Installation, use and maintenance manual – GA ACF
11
1
Figure1.6 Internal components - left side view
1 Ignition transformer 2 Flue thermostat 3 Ignitor and ame detectors


Features and technical data
12
1
Figure1.7 Internal components - right side view
1 Safety valve
2 Return temperature probe
3 TG generator temperature probe
4 Limit thermostat
5 Flow temperature probe
6 Flow switch
7 TCN probe
1
2
5
6
7
3
4
Features and technical data
Installation, use and maintenance manual – GA ACF
13
1
1.4 ELECTRICAL WIRING DIAGRAM
Figure1.8 GA-ACF, ACF-TK, ACF-LB, ACF-HT Unit wiring diagram
TER Power supply terminal block 230 Vac
SCH1 Electronic board (S61)
GV Gas solenoid valve
LS Gas ow warning lamp
PSW Air pressure switch
THMF Outlet water temperature probe
THRF Inlet water temperature probe
TCN Condenser outlet temperature probe
TA Ambient air temperature probe
TG Generator temperature sensor
SRT1 Oil pump rotation sensor
TF Flue gas thermostat
TL Generator limit thermostat (manual reset)
FL Water ow switch
BLW Blower motor
C Blower condenser
FAN Fan motor
C2 Fan condenser
PMP Oil hydraulic pump motor
PWRTR Tansformer 230/24 Vac
CNTBOX Flame controller
IGN Ignition electrodes
IGNTR Ignition transformer
FLS Detection electrode
C2
Features and technical data
14
1
Figure1.9 ACF-HR Unit wiring diagram
TER Power supply terminal block 230 Vac
SCH1 Electronic board (S61)
GV Gas solenoid valve
LS Gas ow warning lamp
PSW Air pressure switch
THMF Outlet water temperature probe
THRF Inlet water temperature probe
TCN Condenser outlet temperature probe
TA Ambient air temperature probe
TG Generator temperature sensor
SRT1 Oil pump rotation sensor
TF Flue gas thermostat
TL Generator limit thermostat (manual reset)
FL Water ow switch
BLW Blower motor
C Blower condenser
FAN Fan motor
C2 Fan condenser
PMP Oil hydraulic pump motor
PWRTR Tansformer 230/24 Vac
CNTBOX Flame controller
IGN Ignition electrodes
IGNTR Ignition transformer
FLS Detection electrode
KP Installation water circulating pump relay
(recovery circuit)
C2
1.5 ELECTRONIC BOARDS
The appliance's electrical panel contains:
Electronic board S61 (Figure 1.10
p. 15
), with microproces-
sor, it controls the appliance and displays data, messages and
operative codes. The appliance is monitored and programmed
by interacting with the display and the knob.
Features and technical data
Installation, use and maintenance manual – GA ACF
15
1
Figure1.10 Electronic board S61
SCH Electronic board S61
THMF Water delivery temperature probe input
THRF Water return temperature probe input
TCN Condenser outlet temperature probe input
TA Ambient air temperature probe input
TG Generator temperature probe input
TA1 Not used
TA2 Not used
SRT1 Oil pump rotation sensor input
SRT2 Not used
JP12 Not used
SPI Not used
P8 (GND, L, H) CAN BUS connector
J1 CAN bus Jumper
A1, A2 Auxiliary inputs (not used)
TF Flue gas thermostat input
TL Generator limit thermostat input
FL Water ow switch input
FS5 Board supply input 24 Vac
P7 (R, W, Y, O) operation request inputs
IGN.BOX (L, N) ame controller supply input 230 Vac
MAIN board supply input 230 Vac
PUMP 230V (L, N) oil hydraulic pump supply
output
N.O. Contact Circuit water circulation pump
controller terminals
J10 Circuit water circulation pump controller
jumper
FAN (BK, WH, BR) Fan output
JTAG S61 board programming connector
ENC Knob
JP10 6-pole ame controller connector
F1 T 2A fuse
F2 T 10A fuse
F3 T 2A fuse
F4 T 3,15A fuse
1.6 CONTROLS
Control device
The appliance may only work if it is connected to a control de-
vice, selected from:
DDC controller
external request
1.6.1 Control system (1) with DDC (GAHP unit ON/
OFF)
The DDC controller is able to control appliances, a single GA unit,
or even several Robur GAHP/GA/AY units in cascade, only in ON/
OFF mode (non modulating). For more details refer to the DDC,
RB100, RB200 Manuals and the Design Manual.
DDC Controller
The main functions are:
Setup and control of one (or more) Robur units of the
absorption line (GAHP, GA, AY).
Data display and parameters setting.
Hourly programming.
Climatic curve control.
Diagnostics.
Errors reset.
Possibility to interface with a BMS.
DDC functionality may be extended with auxiliary Robur devices
RB100 and RB200 (e.g. service requests, DHW production, Third
Party generator control, probe control, system valves or circula-
tion pumps, ...).
1.6.2 Control system (2) with external request for
heating or cooling (GAHP unit ON/OFF)
The appliance may also be controlled via generic enable devic-
es (e.g. thermostat, timer, switch, contactor...) tted with volt-
age-free NO contact. This system only provides elementary con-
trol (on/o, with xed setpoint temperature), hence without the
important functions of system (1). It is advisable to possibly limit
Features and technical data
16
1
its use to simple applications only and with a single appliance. For connection of the selected device to the appliance's
electronic board please refer to Paragraph 4.4
p.23
.
1.7 TECHNICAL DATA
Table1.1 GA ACF technical data
ACF 60-00
ACF 60-00
HR
ACF 60-00
TK
ACF 60-00
HT
ACF 60-00
LB
Operation in cooling mode
Unitary cooling power
Outdoor temperature/Delivery
temperature
A35W7 kW 17,7 17,1 -
A35W-5 kW - 13,3
Heat input
nominal (1013 mbar - 15 °C) kW 25,3
real kW 25,0
Cold water temperature (outlet)
minimum °C 3 (1) 5 -10
nominal °C 7 -5
Cold water temperature (inlet)
maximum °C 45
minimum °C 8 -7
Water ow rate
maximum l/h 3500 2900
nominal l/h 2770 2675 2600
minimum l/h 2500 2300
Internal pressure drop at nominal water ow bar 0,29 (2) 0,42 (2)
External air temperature
nominal °C 35
maximum °C 45 50 45
minimum °C 0 -12 0
Operating recovery circuit
Recovery unit heat output
Outdoor temperature/Inlet
temperature/1000 l/h water
ow
A35W40 kW - 21,0 -
Hot water temperature (inlet) nominal °C - 40 -
Hot water temperature (outlet) nominal °C - 58 -
Water ow rate
maximum l/h - 2500 -
minimum l/h - 0 -
nominal l/h - 1000 -
Total GUE (40°C inlet temperature)
Outdoor temperature/Inlet
temperature/1000 l/h water
ow
A35W7 % - 155 -
Electrical specications
Power supply
voltage V 230
type - single-phase
frequency Hz 50
Electrical power absorption
nominal kW 0,82 (3)
nominal silenced kW 0,87 (3)
Degree of protection IP - X5D
Installation data
Gas consumption
G20 natural gas (nominal) m³/h 2,68 (4)
LPG G30/G31 (nominal) kg/h 1,97 (5) 1,94 (5)
sound power L
w
(max) dB(A) 79,6 (6)
sound power L
w
(max) silenced dB(A) 75,0 (6)
sound pressure L
p
at 5 metres (max) dB(A) 57,6 (7)
sound pressure L
p
at 5 m (maximum) silenced dB(A) 53,0 (7)
maximum water pressure in operation bar 4,0
Water content inside the apparatus
hot side l - 3 -
cold side l 3
Water tting
type - F
thread 1 1/4
Gas connection
type - F
thread 3/4
Dimensions
width mm 850
depth mm 1230
height mm 1445
silenced height mm 1540
Weight in operation kg 360 390 380
(1) To be set (on demand) during the rst startup. Default Minimum Temperature = 4,5 °C.
(2) For ows other than nominal see Design Manual, Pressure losses Paragraph.
(3) ±10% according to the power supply voltage and tolerance on electrical motors consumption. Measured at outdoor temperature of 30 °C.
(4) PCI (G20) 34,02 MJ/m³ (15 °C - 1013 mbar).
(5) PCI (G30/G31) 46,34 MJ/kg (15 °C - 1013 mbar).
(6) Sound power values detected in compliance with the intensity measurement methodology set forth by standard EN ISO 9614.
(7) Maximum sound pressure levels in free eld, with directionality factor 2, obtained from the sound power level in compliance with standard EN ISO 9614.
Transport and positioning
Installation, use and maintenance manual – GA ACF
17
2
ACF 60-00
ACF 60-00
HR
ACF 60-00
TK
ACF 60-00
HT
ACF 60-00
LB
General information
Cooling uid
ammonia R717 kg 6,8 7,2 7,9 7,1 7,2
water H
2
O kg 10,0 10,3 10,0 10,5
(1) To be set (on demand) during the rst startup. Default Minimum Temperature = 4,5 °C.
(2) For ows other than nominal see Design Manual, Pressure losses Paragraph.
(3) ±10% according to the power supply voltage and tolerance on electrical motors consumption. Measured at outdoor temperature of 30 °C.
(4) PCI (G20) 34,02 MJ/m³ (15 °C - 1013 mbar).
(5) PCI (G30/G31) 46,34 MJ/kg (15 °C - 1013 mbar).
(6) Sound power values detected in compliance with the intensity measurement methodology set forth by standard EN ISO 9614.
(7) Maximum sound pressure levels in free eld, with directionality factor 2, obtained from the sound power level in compliance with standard EN ISO 9614.
Table1.2 PED data
ACF 60-00 ACF 60-00 HR ACF 60-00 TK ACF 60-00 HT ACF 60-00 LB
PED data
Components under pression
generator l 18,6
leveling chamber l 11,5
evaporator l 3,7
cooling volume transformer l - 4,5
cooling absorber solution l 6,3
solution pump l 3,3
test pressure (in air) bar g 55
maximum pressure of the cooling circuit bar g 32
lling ratio kg of NH
3
/l 0,157 0,166 0,165 0,148 0,150
uid group -
2 TRANSPORT AND POSITIONING
2.1 WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage dur-
ing appliance transport and installation.
On-site inspection
Upon arrival at the site, ensure there is no transport dam-
age on packing, metal panels or nned coil.
After removing the packing materials, ensure the appli-
ance is intact and complete.
Packing
Only remove the packing after placing the appliance on
site.
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are po-
tentially dangerous.
Weight
The crane and lifting equipment must be suitable for the
load.
Do not stand under suspended loads.
2.2 HANDLING
Handling and lifting
Always handle the appliance in its packing, as delivered by
the factory.
To lift the appliance use straps or slings inserted in the holes
of the base (Figure 2.1
p.17
).
Use lifting beams to avoid damaging the outer panels and
nned coil (Figure 2.1
p.17
).
Comply with safety regulations at the installation site.
Figure2.1 Instruction for lifting
In the event of handling with forklift or pallet truck,
comply with the handling instructions shown on the
packing.
Heating engineer
18
3
2.3 APPLIANCE POSITIONING
Do not install inside a room
The appliance is type-approved for external installation.
Do not install inside a room, not even if it has openings.
In no event start the appliance inside a room.
GA Unit ventilation
The aerothermic appliance requires a large space, venti-
lated and free from obstacles, to enable smooth ow of
air to the nned coil and free air outlet above the mouth
of the fan, with no air recirculation.
Incorrect ventilation may aect eciency and cause
damage to the appliance.
The manufacturer shall not be liable for any incorrect
choices of the place and setting of installation.
Where to install the appliance
The appliance may be installed at ground level, on a terrace
or on a roof, compatibly with its dimensions and weight.
It must be installed outside buildings, in an area of natural air
circulation, outside the dripping path of drainpipes or simi-
lar. It does not require protection from weathering.
No obstruction or overhanging structure (e.g. protruding
roofs, canopies, balconies, ledges, trees) shall interfere either
with the air owing from the top of the appliance or with the
exhaust ue gas.
Do not install near the exhaust of ues, chimneys or hot
polluted air. In order to work correctly, the appliance needs
clean air.
Acoustic issues
Pre-emptively assess the appliance's sound eect in connec-
tion to the site, taking into account that building corners, en-
closed courtyards, restricted spaces may amplify the acous-
tic impact due to the reverberation phenomenon.
2.4 MINIMUM CLEARANCE DISTANCES
Distances from combustible or ammable materials
Keep the appliance away from combustible or ammable
materials or components, in compliance with applicable
regulations.
Clearances around the appliance
The minimum clearance distances shown in Figure 2.2
p. 18
(bar any stricter regulations) are required for safety, operation
and maintenance.
Figure2.2 Clearances
2.5 MOUNTING BASE
Mounting base constructive features
Place the appliance on a level at surface made of reproof
material and able to withstand its weight.
(1) - installation at ground level
Failing a horizontal supporting base, make a at and level
concrete base, at least 100-150 mm larger than the appli-
ance size per side.
(2) - installation on terrace or roof
The structure of the building must support the total weight
of the appliance and the supporting base.
If necessary, provide a maintenance walkway around the ap-
pliance.
Anti vibration mountings
Although the appliance's vibrations are minimal, resonance
phenomena might occur in roof or terrace installations.
Use anti-vibration mountings.
Also provide anti-vibration joints between the appliance
and water and gas pipes.
3 HEATING ENGINEER
3.1 WARNINGS
General warnings
Read the warnings in Chapter III.1
p. 4
, providing im-
portant information on regulations and on safety.
Compliance with installation standards
Installation must comply with applicable regulations
in force, based on the installation Country and site, in
matters of safety, design, implementation and mainte-
nance of:
heating systems
cooling systems
gas systems
Installation must also comply with the manufacturer's
provisions.
Heating engineer
Installation, use and maintenance manual – GA ACF
19
3
3.2 HYDRAULIC SYSTEM
Primary and secondary circuit
In many cases it is advisable to divide the hydraulic system
into two parts, primary and secondary circuit, uncoupled by
a hydraulic separator, or possibly by a tank that also acts as
inertial tank/buer.
Water ow rate
The GA unit works with constant, water ow and ON/OFF oper-
ative mode.
System and components must be designed and installed
consistently.
Minimum water content
High thermal inertia is conducive to ecient appliance opera-
tion. Very short ON/OFF cycles are to be avoided.
For each GA unit provide a minimum water content in the
installation of at least 70 litres.
If necessary, provide for an inertial volume, to be suitably
sized (see design manual).
Buer tank
If using a buer tank, it can be with 2 or 4 hydraulic connections,
as shown in the following two diagrams (Figure 3.1
p. 19
,
3.2
p.19
).
Figure3.1 2-pipe tank diagram
1 Anti-vibration connection
2 Pressure gauge
3 Flow regulator valve
4 Water lter
5 Shut-o valves
6 Water pump (primary circuit)
7 Safety valve (3 bar)
8 Expansion tank
9 Hydraulic separator
10 Water pump (secondary circuit)
11 2-connection inertial buer tank
Figure3.2 4-pipe tank diagram
1 Anti-vibration connection
2 Pressure gauge
3 Flow regulator valve
4 Water lter
5 Shut-o valves
6 Water pump (primary circuit)
7 Safety valve (3 bar)
8 Expansion tank
9 4-connection inertial buer tank
10 Water pump (secondary circuit)
3.3 HYDRAULIC CONNECTIONS
Plumbing ttings
on the right, at the bottom, connection plate
Versions ACF/TK/LB/HT (Figure 1.3
p.9
).
A (= out) 1 1/4" F - chilled WATER OUTLET (m = outlet to the
system)
B (= in) 1 1/4" F - chilled WATER INPUT (r = inlet from the sys-
tem)
HR Version with heat recovery exchanger (Figure 1.4
p.9
).
A (= out) 1 1/4" F - hot WATER OUTLET (m = outlet to the
system)
B (= in) 1 1/4" F - hot WATER INPUT (r = inlet from the system)
D (= out) 1 1/41" F - chilled WATER OUTLET (m = outlet to
the system)
C (= in) 1 1/4" F - chilled WATER INPUT (r = inlet from the sys-
tem)
Hydraulic pipes, materials and features
Use pipes for heating/cooling installations, protected from
weathering, insulated for thermal losses, with vapour barrier
to prevent condensation.
Pipe cleaning
Before connecting the appliance,accurately wash the
water and gas piping and any other system component,
removing any residue.
Minimum components of primary plumbing circuit
Always provide, near the appliance:
on water piping, both output and input
2 antivibration joints on water ttings
2 pressure gauges
2 isolation ball valves
on the inlet water piping
1 separator lter
Heating engineer
20
3
1 ow regulation valve, if the circulation pump is with
constant ow
1 water circulation pump, towards the appliance
on the output water piping
1 safety valve (3 bar)
1 expansion tank of the individual unit
Figure3.3 Hydraulic plan
1 Anti-vibration connection
2 Pressure gauge
3 Flow regulator valve
4 Water lter
5 Shut-o valves
6 Water pump (primary circuit)
7 Safety valve (3 bar)
8 Expansion tank
9 Hydraulic separator / inertial tank with 4
ttings
10 Water pump (secondary circuit)
3.4 WATER CIRCULATION PUMP
The circulation pump (ow and head) must be selected and
installed based on pressure losses of plumbing/primary circuit
(piping + components + exchange terminals + appliance).
For the appliance pressure losses refer to Table 1.1
p.16
and
Design Manual.
Constant ow circulation pump
The primary circulation pump must be obligatorily controlled
by the appliance's electronic board (S61) (see Paragraph
1.5
p.14
).
3.5 ANTIFREEZE FUNCTION
Antifreeze self-protection
The appliance is equipped with an active antifreeze self-protec-
tion system to prevent freezing. The antifreeze function (deac-
tivated by default) automatically starts the primary circulation
pump when the outside temperature approaches zero.
Electrical continuity
The active antifreeze self-protection is only eective if
the power supply is assured. Otherwise, antifreeze liquid
might be required.
3.6 ANTIFREEZE LIQUID
Precautions with glycol
The manufacturer disclaims any liability for any damage
caused by improper glycol use.
Always check product suitability and its expiry date with
the glycol supplier. Periodically check the product's pres-
ervation state.
Do not use car-grade antifreeze liquid (without inhibi-
tors), nor zinc-coated piping and ttings (incompatible
with glycol).
Glycol modies the physical properties of water (densi-
ty, viscosity, specic heat...). Size the piping, circulation
pump and thermal generators accordingly.
With automatic system water lling, a periodic check of
the glycol content is required.
Operation with outside temperatures < 10 °C
If the outside air temperature is expected to be lower
than +10 °C add glycol to prevent a greater icing risk.
Type of antifreeze glycol
Inhibited type glycol is recommended to prevent oxidation
phenomena.
Glycol eects
The Table 3.1
p.20
shows, indicatively, the eects of using a
glycol depending on its %.
Table3.1 Technical data for lling the hydraulic circuit
Glycol %
Water-glycol mixture freezing temper-
ature
Percentage of increase in pressure drops Loss of eciency of unit
10 -3 °C - -
15 -5 °C 6,0% 0,5%
20 -8 °C 8,0% 1,0%
25 -12 °C 10,0% 2,0%
30 -15 °C 12,0% 2,5%
35 -20 °C 14,0% 3,0%
40 -25 °C 16,0% 4,0%
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36