ETN24-SUPER-PROG
C
W1
TG
Date:
Title:
No.Revision Date File name: etn24-super-prog (eu prog-celsius).vsd
Print name: ETN24/PROG Drawn: P.Rechtman
Checked: S.Lukin
Approved: E.Roy
ETN24-SUPER-PROG
(EU Program – Celsius)
11.11.09
Y2 T W2Y1 RH
Internal / External sensor
DIP switch configuration:
B/O RC
1
2
3
4
5
6
Internal* External
Heat-Cool / Heat Pump
HC* HP
ON*
OFF*
ON*
OFF
ON
OFF
x
x
x
x
x
x
ONOFF*
xx
xx
xx
xx
xx
Heater type (HC only)
Oil/Gas heatElectric heat*
ONOFF*
xx
xx
xx
xx
xx
ON
1 2 3 4 5 6
Heat Pump conf. (HP only)
HP in heatHP in cool*
ONOFF*
xx
xx
xx
xx
xx
3 Minutes compressor delay
Without delayWith delay*
ON**OFF*
xx
xx
xx
xx
xx
* Default
** Without delay – for test only.
Default DIP Switch position
Set
o
C
SelectOn/Off Prog
Switch
Software: ESEUPV14
Checksum: B5A7
ON
1 2 3 4 5 6
A B JMP2
JMP2JMP1
For complete reset of the unit, move JMP1 to “B” position,
wait 30 seconds and move it back to “A” position.
Not in use (always short)
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620
1 Original 11.11.09
Technician Settings
Adjust the set point temperature to 10°C. Wait until display
stops flashing.
Press and hold the [Select] button (5 sec.) to enter
technician settings.
Use the [Select] button to switch between different
configurable parameters.
Use the [+] and [-] buttons to make adjustments or switch
between options.
Set point temperature limit for cooling
Indication: “Cool” and the set point Temperature limit for
cooling. Range: 10...30°C, default 10°C.
Set point temperature limit for heating
Indication: “Heat” and the set point temperature limit for
heating. Range: 10...30°C, default 30°C.
Offset for calibration of the measured temperature
Indication: “Offs” and a number between (-6) and (+6).
Range: -6...+6°C, default 0°C.
Wait until display returns to normal mode