ADTRAN 6-Amp Power Installation guide

Category
Power supply units
Type
Installation guide

This manual is also suitable for

ADTRAN 6-Amp Power is a versatile power solution that offers reliable and efficient performance for a wide range of applications. Its advanced features and robust design make it an ideal choice for powering critical equipment in various industries and environments.

With its high power output of 6 amps, this power supply can support demanding loads, ensuring uninterrupted operation of connected devices. The built-in battery charger allows for seamless transition to backup power in the event of a primary power outage, providing peace of mind and uninterrupted operation.

The ADTRAN 6-Amp Power features multiple alarm relays that provide real-time status updates, enabling proactive monitoring and timely response to potential issues. This advanced monitoring capability is crucial for maintaining system uptime and preventing costly downtime.

ADTRAN 6-Amp Power is a versatile power solution that offers reliable and efficient performance for a wide range of applications. Its advanced features and robust design make it an ideal choice for powering critical equipment in various industries and environments.

With its high power output of 6 amps, this power supply can support demanding loads, ensuring uninterrupted operation of connected devices. The built-in battery charger allows for seamless transition to backup power in the event of a primary power outage, providing peace of mind and uninterrupted operation.

The ADTRAN 6-Amp Power features multiple alarm relays that provide real-time status updates, enabling proactive monitoring and timely response to potential issues. This advanced monitoring capability is crucial for maintaining system uptime and preventing costly downtime.

installation guide
Total Access
Rackmount 6-Amp PS/BC
Installation and Maintenance Guide
Document Number: 61180043L2-5E
CLEI: VAPUKTOC_ _
June 2010
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
ii 61180043L2-5E
Front Matt er
Trademarks
Anybrandnamesandproductnamesincludedinthisdocumentaretrademarks,registered
trademarks,ortradenamesoftheirrespectiveholders.
To the Holder of this Document
Thecontentsofthisdocumentarecurrentasofthedateofpublication.ADTRAN
®
reserves
therighttochangethecontentswithoutpriornotice.
InnoeventwillADTRANbeliableforanyspecial,incidental,orconsequentialdamagesor
forcommerciallossesevenifADTRANhasbeenadvisedthereofasaresultofissueofthis
document.
About this Document
ThisdocumentprovidesinstructionsfortheinstallationandmaintenanceoftheRackmount6
AmpPS/BC.Theintendedaudienceforthisinformationisthecraftpersonresponsibleforthe
installationandmaintenanceoftheequipment.Theseins truct ionsassumefamiliaritywiththe
intendeduseoftheequipment,basicrequiredinstallationskills,andknowledgeof
localand
acceptedsafetypractices.
901ExplorerBoulevard
P.O. Box140000
Huntsville,AL358144000
UnitedStates
(256)9638000
©2010ADTRAN,Inc.
AllRightsReserved.
®
61180043L2-5E iii
Revision History
Revision Functional Description
ThisdocumentupdatestheAlternateMountinginstructions(see“A l t e r n a t e Mounting”on
page 17)toreflecttheadditionofrackmountingusinganADTRANsuppliedkit.
Conventions
Thefollowingtypographicalconventionsareusedinthisdocument:
Thisfontindicatesacrossreferencelink.
This fontindicatesscreenmenus,fields,andparameters.
T
HIS FONTindicateskeyboardkeys(ENTER,ESC,ALT).Keysthataretobepressedsimulta
neouslyareshownwithaplussign(A
LT+X indicatesthattheALT keyandX keyshouldbe
pressedatthesametime).
Thisfontindicatesreferencestootherdocumentationandisalsousedforemphasis.
Thisfontindicatesonscreenmessagesandprompts.
Thisfontindicatestexttobetypedexactlyasshown.
This fontindicatessilkscreenlabelsorothersystemlabelitems.
Thisfontis
usedforstrongemphasis.
Revision Date Description
DJune2005
RevisetoremoveDualPS/BCJumperCable.
EJune2010 ReviseAlternateMountinginstructions.
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
iv 61180043L2-5E
Hazard Classifications
Thefollowinghazardclassificationsareusedinthisdocument:
DANGER
!
DANGERind ica tesahazardwithahigh levelofriskwhich,ifnot avoided,
willresultindeathorseriousinjury.
WARNING
!
WARNINGindicatesahazardwithamediumlevelofri skwhich,ifnot
avoided,couldresultindeathorseriousinjury.
CAUTION
!
CAUTIONindicatesahazardwithalowlevelofriskwhich,ifnotavoided,
couldresultinminorormoderateinjury.CAUTIONcanalsobeusedtoalert
againstunsafepracticesassociatedwitheventsthatcouldleadtopersonal
injury.
NOTICE
Noticecalloutsindicateapotentiallyhazardoussituationnotrelatedto
personalinjury,suchasmessagesrelatedtopropertydamageonly.
NOTE
Notesinformtheuserofadditional,butessential,informationorfeatures.
61180043L2-5E v
Icons
ThefollowingiconsareusedthroughouttheADTRANdocumentsuite:
Training
ADTRANofferstrainingcoursesonourproducts.Thesecoursesincludeoverviewson
productfeaturesandfunctionswhilecoveringapplicationsofADTRANproductlines.
ADTRANprovidesavarietyoftrainingoptions,includingcustomizedtrainingandcourses
taughtatourfacilitiesoratcustomersites.
Forinquiriesconcerningtraining,contactADTRAN:
TrainingPhone:
8006151176,ext.6303
TrainingFax:2569636217
TrainingEmail:[email protected]
deployment guide
installation guide
jobAid
reference guide
diagnostic guide
safety and regulatory
engineering guide
application guide
release notes
upgrade guide
user guide
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
vi 61180043L2-5E
61180043L2-5E vii
Contents
Scope of this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
In this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Single or Dual Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PS/BC Mounting Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Battery Disconnect Protection Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
DC Over Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Alarm Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Shipping Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting the PS/BC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Alternate Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Provisioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
120 VAC Power Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DC Power Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
PS/BC to Battery Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Battery Charge/Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Alarm Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
viii 61180043L2-5E
Appendix A
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Warranty and Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
ADTRAN Sales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
ADTRAN Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
ADTRAN Repair/CAPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Repair and Return Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Figures
61180043L2-5E ix
Figures
Figure 1.Total Access PS/BC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2.PS/BC Mounted On Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 3.Wiring Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
x 61180043L2-5E
Tables
Table 1.LED Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2.Power Factor and Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 3.PS/BC Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
61180043L2-5E 1
Total Access
6-Amp Rackmount PS/BC
Scope of this Guide
Thisguidecontainsimportantpreinstal lationandinstallationinstructionsforinstallingthe
ADTRANTotalAccessRackmount6AmpPowerSupplyBatteryCharger(PS/BC,P/N
1180043L2).Craftpersonnelshouldreviewthisentireguideaspartofinstallationplanning.
In this Guide
ThisguidecontainsthetopicslistedinTable1.
Table 1. Topic List
Topic See Page
Introduction 3
Description 3
Installation 5
WiringDescriptions 8
Operation 11
Maintenance 12
Specifications 13
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
2 61180043L2-5E
Introduction
ThePS/BCrectifierispartoftheTotalAccessRackmountACPowerSupply/BackupBattery
System(APS/BBS).ItisdesignedtoworkinconjunctionwithoneortwoADTRANbackup
batterypacks(P/N1175044L1).
Figure1illustratesthePS/BC(P/N1180043L2)rightand leftsidepanels.
Figure 1. Total Access PS/BC
Features
TheTotalAccess PS/BCfeaturesincludethefollowing:
–54VDCat6ampsoutputformultipleuse
•Modularconnectionsfortwobackupbatterypacks
•Modularpoweroutputconnection
•LEDstatusforVAC,VDC,andbatterycharging
•Fullbatteryrechargeinlessthaneighthours
•TwoPS/BCconf igurationoptionsavailable
•Fuseprotection
•Positiveground
•BatteryPack
mountinghardwareincluded
•Completelyautoma ticoperation
•Multipleprotectionfeatures
Uninterruptedpoweroutputifbackupbatteryconnected
MeetsNEBSLevel3(allrequirementsofGR63COREandGR1089CORE)
•FCCandUL60950compliant
F
U
S
E
F
U
S
E
Description
61180043L2-5E 3
Description
OriginallydesignedfortheTotalAccess1500system,thePS/BCcanbeusedinanyappli
cationusing120VACinput,andrequiringupto–54VDC,6ampsoutput.
IntheTotalAccess1500configuration,therectifierperformsACtoDCconversionand,when
usedwiththedualbattery,provides
uptoeighthoursofbackuppowerforafullypopulated
TotalAccess1500bank(96FXScircuits)withupto50percentoffhookcircuitsatanyone
time.
Forgeneraluse,therectifierreceivesACpowerfromastandard120VACwalloutletand
convertsthisto–54VDC,
6ampoutputtothedesignatedloadplusrechargingthesingleor
dualbattery,ormaintainingbatteryatpeakcharge.Eachbatteryhasfourseriesconnected12
voltrechargeablecells.
Single or Dual Battery
Eachbatterystringisratedfor3ampsofcurrentand7amp hoursofcapacity.Dualbatteries
arerequirediftheloadexceedstheseratingsduringACpowerfailure(backupbatterymode).
PS/BC Mounting Location
ThePS/BCnormallymountstotheassociatedbatterypack.Theunitcanalsomounttoa
specialbracketwithinacabinet,ormountexternaltoacabinetagainstawall.
Battery Disconnect Protection Circuit
Duringbatteryoperationaprotectioncircuitdisconnectsbatteryfromthemainoutputwhen
batteryvoltagedropsbelow39VDC,preventingoverdischarge.WhenACreturns,themain
outputprovidesregulated–54VDC,batteriesrecharge,andthesystemreturnstonormal.
Referto“LEDStatusIndicators”onpage 4.
Aftertheprotectioncircuit
initiates,theLEDsremainon(red),continuingtoslowlydrainthe
battery.Whenbatteryvoltagedropsto35VDC,allloadisremovedfromthebattery.IfAC
powerwillnotbeavailableforanextendedperiod(severaldays),disconnectthebatteryto
preventunnecessarydischarge.
DC Over Voltage Protection
ThePS/BChasaprotectioncircuitthatdisablestherectifiertoprotecttheloadfromahigh
outputvoltagecausedbyrectifierfailure.ThebackupbatteryorredundantPS/BCsupports
theloadinthisinstance.TheovervoltageeventcanpermanentlydisablethePS/BC.Confirm
thisbyperformingthefollowingprocedure:
1.DisconnectthePS/BCfromtheACsource.
2. Wait30minutesminimum.
3. After30minutesplugbackintotheACsource.
4. Iftheunithasrecovered,the
AC FAIL/UNIT FAIL/OVERLOADLEDwillturnongreenand
theunitreturnstoservice.IftheLEDdoesnotturnongreen,replacethePS/BC.
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
4 61180043L2-5E
Alarm Relays
TherearetwouncommittedalarmrelaysassociatedwithPS/BCoperation,asfollows:
•ACFail(ACF):AlarmsifACfails,therectifieroverloads,ortherectifierfails
•BatteryLowVoltage(BV):Alarmsifeitherorbothbatteryvoltagedropsbelow42VDC
Fuse
Astandard5×20mm5ampfuseadjacenttotheACpowercordprotectsACpowe rfeed
overloadincaseofrectifierfailure.
LED Status Indicators
AsetofthreePS/BCmulti colorLEDsprovidestatusforAC, DC,andbatterychargecondi
tions.SeeTable2forLEDdescriptions.DescriptionsarealsolabeledonthePS/BC.
Note:Descriptionsarethesameforasinglebattery.
Safety and Regulatory Compliance
ThisdevicecomplieswithPart15oftheFCCrules.Operationissubjecttothefollowingtwo
conditions:
1.Thisdevicemaynotcauseharmfulinterference.
2. Thisdevicemust accep tanyinterferencereceived,includinginterferencethatmaycause
undesiredoperation.
ChangesormodificationsnotexpresslyapprovedbyADTRANcouldvoidtheusers
authority
tooperatethisequipment.
Table 2. LED Descriptions
LED Status Description
AC FAIL/UNIT FAIL/OVERLOAD
z
z
Green
Red
Normal120VACoperation
ACfailorrectifieroverloadorfail
BATTERY VOLTAGE
z
z
z
Green
Yellow
Red
Battery1andBattery2greaterthan42VDC
Battery1orBattery2lessthan42VDC
Battery1andBattery2lessthan40VDC
CHARGING STATUS
z
z
z
Green
Yellow
Red
Battery1andBattery2chargedorrecharging
Battery1orBattery2discharging
Battery1andBattery2fullydischarged
All LEDs
{ Off AClost,Batterylessthan35VDC
Installation
61180043L2-5E 5
Installation
CAUTION
!
Electrostaticdischarge(ESD)candamageelectronicmodules.Whenhandling
modules,we ar anan tistaticdischargewriststraptopreventdamageto
electroniccomponents.Placemodulesinantistaticpackingmaterial when
transportingorstoring.Whenworkingonmodules, alwaysplacethemonan
approvedantistaticmatthatiselectricallygrounded.
AfterunpackingtheTotalAccessPS/BC,inspectitfordamage.Ifdamagehasoccurred,filea
claimwiththecarrier,thencontactADTRANCustomerService.RefertoAppendixA,
Warrantyforfurtherinformation.Ifpossible,keeptheoriginalshippingcontainerfor
returningthePS/BC
forrepairorforverificationofshippingdamage.
Shipping Contents
Thecontentsincludethefollowingitems:
•Rackmount6AmpPowerSupplyBatteryCharger
TotalAccess
Rackmount6AmpPS/BC InstallationandMaintenanceGuide
(P/N61180043L25)
Appropriatewiring:
–PS/BCtoACsource(hardwired)
–PS/BCtoload
–PS/BCalarmoutput
•BatteryPackmountinghardware
SeparatelypurchasedRackMountingKitsforthePS/BCareavailableforthefollowingracks:
•19inch(P/N1175050L1)
•23inch(P/N1175051L1)
C A U T I O N C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
6 61180043L2-5E
Mounting the PS/BC
ThePS/BChousingoccupiesanominalarea15.35inches(withmountingtabs)wideby3.45
incheshighandisdesignedsothefourmountingtabscrewholesaligntothreadedscrew
holesontheADTRANbatterypackhousing.Thisprocedureassumesthatthebatterypackis
mountedinthedesignated19
inchor23inchrack.HardwareformountingthePS/BCtothe
batterypackisincluded.
Tomountthe PS/BC,completethe followingsteps:
1.Ensurea120 VACwalloutletiswithinreachofthePS/BC10footpowe rcord.
2. DeterminethemostconvenientdirectiontoviewthestatusLEDsandposition
thePS/BC
accordingly.
3. Alignthemountingtabstothethreadedmountingholesonthebatterypack.
4. Usingtheincluded“sems”screwswithstarwasher,mountthePS/BCtothebatterypack.
Tightenfastenersfirmly.
SeeFigure2forarepresentativeexampleofthe PS/BCmountedtothebattery.
Figure 2. PS/BC Mounted On Battery Pack
1175044L1
BATTERY
BAC
KU
P
W
AR
NING
:
SCREW LENGTHS EXCEEDING 3/8"
MAY PUNCTURE BATTRIES.
1175044L1
BATTERY BACKUP
W
AR
NING
:
SCREW LENGTHS EXCEEDING 3/8"
MAY
PUNCTURE BATTRIES.
1180043L2
CAUTION:
FOR CONTINUED PROTECTION AGAINST
RISK OF FIRE, REPLACE ONLY WITH THE
SAME TYPE AND RATING OF FUSE
.
FUSE: 12A/125V
F
U
S
E
F
U
S
E
Installation
61180043L2-5E 7
Alternate Mounting
Therearetwoalternatemountingmethods,asfollows:
1.Mountingdirectlytoawallusingcustomersuppliedwoodscrews
2. Rackmounting(bracket),usingonofthefollowingkits:
•19InchRackMountKit,P/N1175050L1
•23InchRackMountKit,P/N1175051L1
Rack Mounting
RackmountingkitscanbepurchasedseparatelyfromADTRAN.
Therackmountingbracketmountlocationisnormallyatthebatterypositionwhenbatteries
aremounted externaltothecabinet.Thebrackethasthreadedmountingholesthataligntothe
PS/BCmountingtabs.ThePS/BCcanbemountedtoeithersideof
thebracket,ortwoPS/BCs
canbemounted,oneoneachside.Openingsinthebracketallowforwiremanagement.
NOTE
Whendeterminingthealternatemountinglocation,ensuresuppliedcabling
reachesthedesignatedterminationpoint,includ ingdressingandlacing.
Provisioning
AsidefromvariousPS/BCandbatterymountingandwiringconfigurations,therearenoend
usercontrols,adjustments,oroptionsassociatedwiththePS/BC.
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
8 61180043L2-5E
Wiring Descriptions
ThewiringrequiredforthesinglePS/BCanddualbatteryconfigurationisincluded.
CAUTION
!
Allgroundsmustterminateataknowngroundlocation.Checkmetalto
metalcontactonallgroundconnections.Donotstackorcombine ground s.
Ensuregroundcircuitcontinuity.
Ground
AgroundpostadjacenttothePS/BCfuseisavailableforframeground.
WARNING
!
Do not connectAC poweror make batteryconnectionsuntil allother
connectionshavebeenmadeforthedesignatedinstallationandprotective
coversandshieldshavebeeninstalled.
120 VAC Power Input
ACinputisthrougha10footwirewithathreepronggroundedplugontheend.Thelineis
hardwiredtothePS/BC.
NOTE
IntheoptionaltwoPS/BCconfiguration,af ully redundantsyste mrequires
thateachPS/BChaveanindependentACsource.
DC Power Output
The4footlong,threeconductorPS/BCpoweroutputwireoriginatesatthe–54V 6A OUTPUT
modularconnectorandterminatesatthree#6ringlugsforcustomerdesignatedconnection.
Wirecolorcodeisasfollows:
•Red=–54VDC
•Black=Return
•Green=Ground
PS/BC to Battery Configurations
ThebasicdesignconfigurationconsistsofonePS/BCwithtwobatteries.Avarietyofother
configurationsarepossiblewithmore(orless)redundantcapability,seeFigure3forstandard
configurationsIandII.
Wiring Descriptions
61180043L2-5E 9
Figure 3. Wiring Block Diagrams
ThesewouldincludeoneortwoPS/BCs,none,one,ortwobatteries,orsomecombinationof
PS/BCandbattery.ThemostreliableconfigurationwouldbetwoPS/BCswithtwobatteries
eachandwithindependentACsources.ThetwoPS/BCoutputswouldterminateatasingle
loadthathasprimaryandsecondary
powersharingterminals.
Battery Charge/Discharge
CAUTION
!
Topreventbatterydischargepriortosystemoperation,donotconnectthe
batterytothePS/BCuntiltheACpowerisconnectedorimminent.
Eachbatteryhasahardwired6footbatterycharge/dischargewirethatoriginatesatthe
batteryhousingandterminatesatamodularconnector.ThePS/BChastwomatingconnector
portseachlabeled
–48V 3A INPUT.Itdoesnotmatterwhichbatteryconnectstowhichport.
Load
A
B
Load
A
B
PS/BC
A
PS/BC
A
Batt
Batt
Batt
Batt
Batt
Batt
I
Ia
Ib
Configuration I, Ia, Ib
I. PS/BC, no battery.
Ia. PS/BC + 1 battery string.
Ib. PS/BC + 2 battery strings.
PS/BC
B
II
II
IIa
IIb
IIc
IId
Configuration II, IIa, IIb, IIc, IId
II. 2 PS/BC, no battery.
IIa. 2 PS/BC + 1 battery string.
IIb. 2 PS/BC + 2 battery strings.
IIc. 2 PS/BC + 3 battery strings.
IId. 2 PS/BC + 4 battery strings.
This configuration shows adding battery
strings alternately to PS/BC A and B.
Other wiring configurations are optional.
Total Access Rackmount 6-Amp PS/BC Installation and Maintenance Guide
10 61180043L2-5E
Topreventheatbuildupthebatterychargecurrentislimitedto1ampperbattery.Thiselimi
natestheneedfortemperaturecompensation.
Alarm Wiring
Thealarmrelayoutputoriginates atamodularconnectorwitha6footwirestub.Wiring
terminationoftheoutputiscustomerdesignated.Thealarmoutputs:ACFail,BatteryLow
Voltage,areassignedthefollowingwirecolorcodes:
•ACF=orange,orange/white
•BV=blue,blue/white
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

ADTRAN 6-Amp Power Installation guide

Category
Power supply units
Type
Installation guide
This manual is also suitable for

ADTRAN 6-Amp Power is a versatile power solution that offers reliable and efficient performance for a wide range of applications. Its advanced features and robust design make it an ideal choice for powering critical equipment in various industries and environments.

With its high power output of 6 amps, this power supply can support demanding loads, ensuring uninterrupted operation of connected devices. The built-in battery charger allows for seamless transition to backup power in the event of a primary power outage, providing peace of mind and uninterrupted operation.

The ADTRAN 6-Amp Power features multiple alarm relays that provide real-time status updates, enabling proactive monitoring and timely response to potential issues. This advanced monitoring capability is crucial for maintaining system uptime and preventing costly downtime.