Beckhoff KL3311 Documentation

Type
Documentation

This manual is also suitable for

Documentation
KL3311, KL3312, KL3314 and KL3302
Single, Dual- and Four-Channel Analog Imput Terminals for
Thermocouples
4.2
2019-10-08
Version:
Date:
Table of contents
KL3311, KL3312, KL3314 and KL3302 3Version: 4.2
Table of contents
1 Foreword ....................................................................................................................................................5
1.1 Notes on the documentation..............................................................................................................5
1.2 Safety instructions .............................................................................................................................6
1.3 Documentation issue status ..............................................................................................................7
1.4 Beckhoff Identification Code (BIC) ....................................................................................................7
2 Product overview.....................................................................................................................................10
2.1 Introduction......................................................................................................................................10
2.2 Technical Data.................................................................................................................................11
2.3 Basic function principles ..................................................................................................................11
3 Mounting and wiring................................................................................................................................15
3.1 Instructions for ESD protection........................................................................................................15
3.2 Installation on mounting rails ...........................................................................................................15
3.3 Installation instructions for enhanced mechanical load capacity .....................................................19
3.4 Connection ......................................................................................................................................19
3.4.1 Connection system .......................................................................................................... 19
3.4.2 Wiring............................................................................................................................... 22
3.4.3 Shielding .......................................................................................................................... 23
3.5 KL3311 - Connection and LED description .....................................................................................24
3.6 KL3312, KL3302 - Connection and LED Description ......................................................................25
3.7 KL3314 - Connection and LED description .....................................................................................26
3.8 Connection of ground, shield und earthing......................................................................................27
3.9 ATEX - Special conditions (standard temperature range) ...............................................................28
3.10 ATEX Documentation ......................................................................................................................29
4 KS2000 Configuration Software.............................................................................................................30
4.1 KS2000 - Introduction......................................................................................................................30
4.2 Sample program for KL register communication via EtherCAT on KL3314 exemplary...................31
5 Access from the user program ..............................................................................................................34
5.1 KL331x, KL3302 - Terminal Configuration ......................................................................................34
5.2 Mapping in the Bus Coupler ............................................................................................................35
5.2.1 KL3311 - Default Mapping ............................................................................................... 36
5.2.2 KL3312 (KL3302) - Default Mapping ............................................................................... 37
5.2.3 KL3314 - Default Mapping ............................................................................................... 38
5.3 Register overview ............................................................................................................................39
5.4 Register description.........................................................................................................................39
5.5 Control and status byte....................................................................................................................43
5.5.1 Register communication .................................................................................................. 45
5.6 Examples of Register Communication ............................................................................................46
5.6.1 Example 1: reading the firmware version from Register 9............................................... 46
5.6.2 Example 2: Writing to an user register............................................................................. 47
6 Appendix ..................................................................................................................................................50
6.1 Support and Service ........................................................................................................................50
Table of contents
KL3311, KL3312, KL3314 and KL33024 Version: 4.2
Foreword
KL3311, KL3312, KL3314 and KL3302 5Version: 4.2
1 Foreword
1.1 Notes on the documentation
Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under
development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff
®
, TwinCAT
®
, EtherCAT
®
, EtherCATG
®
, EtherCATG10
®
, EtherCATP
®
, SafetyoverEtherCAT
®
,
TwinSAFE
®
, XFC
®
, XTS
®
and XPlanar
®
are registered trademarks of and licensed by Beckhoff Automation
GmbH. Other designations used in this publication may be trademarks whose use by third parties for their
own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 with corresponding
applications or registrations in various other countries.
EtherCAT
®
is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.
Copyright
© Beckhoff Automation GmbH & Co. KG, Germany.
The reproduction, distribution and utilization of this document as well as the communication of its contents to
others without express authorization are prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a
patent, utility model or design.
Foreword
KL3311, KL3312, KL3314 and KL33026 Version: 4.2
1.2 Safety instructions
Safety regulations
Please note the following safety instructions and explanations!
Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.
Description of instructions
In this documentation the following instructions are used.
These instructions must be read carefully and followed without fail!
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Tip or pointer
This symbol indicates information that contributes to better understanding.
Foreword
KL3311, KL3312, KL3314 and KL3302 7Version: 4.2
1.3 Documentation issue status
Version Comment
4.2 Update chapter “Instructions for ESD protection”
Chapter “Beckhoff Identification Code (BIC)” added
4.1 Supported sensor types corrected
4.0 Migration
Update Technical data
Sample program added to the chapter KS2000 Configuration Software
Structural update
Chapters KS2000 configuration software and Access from the user program added
Firmware (FW) and hardware (HW) versions
Documen-
tation,
Version
KL3311 KL3302* KL3312 KL3314
FW HW FW HW FW HW FW HW
4.1 3G 08 3B 04 3H 07 3D 04
4.0 3G 08 3B 04 3H 07 3D 04
*) KL3302 is no longer available and was replaced with KL3312.
The firmware and hardware versions (delivery state) of the terminal can be found in the serial number printed
on the side.
Syntax of the serial number
Structure of the serial number: WWYYFFHH
WW - week of production (calendar week)
YY - year of production
FF - firmware version
HH - hardware version
Example with ser. no.: 35 04 1B 01:
35 - week of production 35
04 - year of production 2004
1B - firmware version 1B
01 - hardware version 01
1.4 Beckhoff Identification Code (BIC)
The Beckhoff Identification Code (BIC) is increasingly being applied to Beckhoff products to uniquely identify
the product. The BIC is represented as a Data Matrix Code (DMC, code scheme ECC200), the content is
based on the ANSI standard MH10.8.2-2016.
Foreword
KL3311, KL3312, KL3314 and KL33028 Version: 4.2
Fig.1: BIC as data matrix code (DMC, code scheme ECC200)
The BIC will be introduced step by step across all product groups.
Depending on the product, it can be found in the following places:
on the packaging unit
directly on the product (if space suffices)
on the packaging unit and the product
The BIC is machine-readable and contains information that can also be used by the customer for handling
and product management.
Each piece of information can be uniquely identified using the so-called data identifier
(ANSIMH10.8.2-2016). The data identifier is followed by a character string. Both together have a maximum
length according to the table below. If the information is shorter, spaces are added to it. The data under
positions 1 to 4 are always available.
The following information is contained:
Item
no.
Type of
information
Explanation Data
identifier
Number of digits
incl. data identifier
Example
1 Beckhoff order
number
Beckhoff order number 1P 8 1P072222
2 Beckhoff Traceability
Number (BTN)
Unique serial number,
see note below
S 12 SBTNk4p562d7
3 Article description Beckhoff article
description, e.g.
EL1008
1K 32 1KEL1809
4 Quantity Quantity in packaging
unit, e.g. 1, 10, etc.
Q 6 Q1
5 Batch number Optional: Year and week
of production
2P 14 2P401503180016
6 ID/serial number Optional: Present-day
serial number system,
e.g. with safety products
51S 12 51S678294104
7 Variant number Optional: Product variant
number on the basis of
standard products
30P 32 30PF971, 2*K183
...
Foreword
KL3311, KL3312, KL3314 and KL3302 9Version: 4.2
Further types of information and data identifiers are used by Beckhoff and serve internal processes.
Structure of the BIC
Example of composite information from item 1 to 4 and 6. The data identifiers are marked in red for better
display:
BTN
An important component of the BIC is the Beckhoff Traceability Number (BTN, item no.2). The BTN is a
unique serial number consisting of eight characters that will replace all other serial number systems at
Beckhoff in the long term (e.g. batch designations on IO components, previous serial number range for
safety products, etc.). The BTN will also be introduced step by step, so it may happen that the BTN is not yet
coded in the BIC.
NOTE
This information has been carefully prepared. However, the procedure described is constantly being further
developed. We reserve the right to revise and change procedures and documentation at any time and with-
out prior notice. No claims for changes can be made from the information, illustrations and descriptions in
this information.
Product overview
KL3311, KL3312, KL3314 and KL330210 Version: 4.2
2 Product overview
2.1 Introduction
Fig.2: KL3311, KL3312 and KL3314
The KL331x analog input terminals allow the direct connection of thermocouples. The circuit of the Bus
Terminals can operate thermocouples using 2-wire technique. Linearization over the full temperature range
is realized with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs
indicates a broken wire. Compensation for the cold junction is made through an internal temperature
measurement at the terminals. mV measurement is also possible with the KL331x terminals.
KL3302 is no longer available and was replaced with KL3312.
Product overview
KL3311, KL3312, KL3314 and KL3302 11Version: 4.2
2.2 Technical Data
Technical data KL3311 KL3302* KL3312 KL3314
Number of inputs 1 2 4
Power supply for the electronics via the K-bus
Thermocouple sensor type Types B, E, J, K, L, N, R, S, T, U, mV measurement (default setting is type K)
Connection technology 2-wire
Temperature range In each case within the defined range of the sensor
(preset: type K, -100°C to 1370°C)
Resolution 0.1℃ per digit
Open-circuit recognition yes no yes yes
Conversion time ~200ms ~250ms
Measuring error (total measuring
range)
<±0.5% of the full scale value
Electrical isolation 500V (K-bus / signal voltage)
Current consumption K-bus typically 65mA
Bit width in the K-bus I/O Input: 1 x 16bits of
data (1 x 8bits con-
trol/status optional)
Input: 2 x 16bits of data (2 x 8bits control/sta-
tus optional)
Input: 4 x 16bits of
data (4 x 8bits con-
trol/status optional)
Configuration No address or configuration settings
Weight approx.70g
Dimensions (WxHxD) approx. 15mmx100mmx70mm (width aligned: 12mm)
Mounting [}15]
on 35mm mounting rail according to EN60715
Permissible ambient temperature range
during operation
0°C ... + 55°C
Permissible ambient temperature range
during storage
-25°C ... + 85°C
Permissible relative air humidity 95%, no condensation
Vibration/shock resistance
conforms to EN60068-2-6/ EN60068-2-27, see also Installation instructions for enhanced
mechanical load capacity [}19]
EMC immunity/emission conforms to EN61000-6-2/ EN61000-6-4
Protection class IP20
Installation position variable
Approval
CE, cULus, ATEX
[}28]
-
CE, cULus, ATEX
[}28]
CE, cULus, ATEX
[}28],GL
*) KL3302 is no longer available and was replaced with KL3312.
2.3 Basic function principles
The thermocouple terminals can evaluate thermocouples of the types B, E, J, K, L, N, R, S, T and U. The
characteristic curves are linearized and the reference temperature determined directly within the terminal.
Temperatures are output in 1/10°C, for example (device-dependent). The terminal is fully configurable via
the Bus Coupler or the control system. Different output formats may be selected or own scaling activated. In
addition, linearization of the characteristic curve and determination and calculation of the reference
temperature (temperature at the terminal connection contacts) can be switched off.
Measuring principle of the thermocouple
Thermocouples can be classified as active transducers. They exploit the thermo-electric effect (Seebeck,
Peltier, Thomson). A voltage referred to as thermovoltage occurs over the length of a cable with different
temperatures at both ends. It is an unambiguous function of the temperature and the material. In a “TC
element” this effect is utilized by operating two different conductor materials in parallel (s. fig [}12].)
Product overview
KL3311, KL3312, KL3314 and KL330212 Version: 4.2
Fig.3: Principle of the thermocouple
Example:
In the following example, the voltage U
th
is given which is present at a type-K thermocouple at the
temperature Tm.
U
th
= (k
NiCr
- k
Ni
) x ΔT
with
ΔT = T
m
- T
v
A type-K thermocouple consists of a junction of a nickel-chrome alloy and nickel, where k
NiCr
and k
Ni
represent the thermoelectric coefficients of nickel-chrome and nickel respectively. By adapting the equation
according to T
m
, the sought-after temperature can be calculated from the voltage measured across the
thermocouple. Based on the difference to the cold junction temperature, the temperature at the
measurement point can be determined to an accuracy of better than one tenth of a Kelvin with the aid of the
above thermocouple equation.
Sensor circuit
A modification of the sensor circuit with additional devices such as change over switches or multi-
plexer decreases the measure accuracy. We strongly advise against such modifications.
Product overview
KL3311, KL3312, KL3314 and KL3302 13Version: 4.2
Internal conversion of the thermovoltage and the reference voltage
Since the coefficients are determined at a reference temperature of 0°C, it is necessary to compensate for
the effect of the reference temperature. This is done by converting the reference temperature into a
reference voltage that depends on the type of thermocouple, and adding this to the measured
thermovoltage. The temperature is found from the resulting voltage and the corresponding characteristic
curve.
U
k
= U
m
+ U
r
T
out
= f(U
k
)
The four LEDs indicate the operating state of the associated terminal channels.
green Run LEDs: RUN (not applicable for KL3314)
On: normal operation
Off: Watchdog timer overflow has occurred. If no process data are transmitted by the Bus Coupler
for 100ms, the green LEDs go out.
Red LEDs: ERROR
On: Wire breakage. The resistance is in the invalid range of the characteristic curve of the
respective thermocouple.
Off: The resistance is in the valid range of the characteristic curve.
Process data output format
In the delivery state, the measured value is displayed in increments of 1/10°C in two's complement format
(integer). Other presentation types can be selected via the feature register (R32) (e.g.signed amount
representation, Siemens output format).
Measured value Output
Hexadecimal output Signed integer output
-200.0°C 0xF830 -2000
100.0℃ 0xFC18 -1000
0.1℃ 0xFFFF -1
0.0℃ 0x0000 0
0.1℃ 0x0001 1
100.0℃ 0x03E8 1000
200.0℃ 0x07D0 2000
500.0℃ 0x1388 5000
850.0℃ 0x2134 8500
1,000.0℃ 0x2710 10000
Voltage limits
U
k
>U
kmax
:
Bits1 and 6 (overrange and error bits) in the status byte are set. The linearization of the characteristic
curve is continued with the coefficients of the overrange limit up to the limit stop of the A/D converter or
to the maximum value of 0x7FFF.
U
k
< U
kmin
:
Bits0 and 6 (underrange and error bits) in the status byte are set. The linearization of the characteristic
curve is continued with the coefficients of the underrange limit up to the limit stop of the A/D converter
or to the minimum value of 0x8000.
For overrange or underrange the red error LED is switched on.
Product overview
KL3311, KL3312, KL3314 and KL330214 Version: 4.2
Calculation of process data
The process data that are transferred to the Bus Coupler are calculated using the following equations:
T
ref
= A
00
* X_ref
U
ref
= a
1
* T
ref
2
+ b
1
* T
ref
+ c
1
(1.0)
(1.1)
Voltage value of the cold junction
U
m1
= A_a * X_ X_m + B_a
U
k
= U
ref
+ U
m1
T = a
0
* U
k
2
+ b
0
* U
k
+ c
0
(1.2)
(1.3)
(1.4)
Measured temperature in 1/16°C
Tout = T (1.5) Neither user nor manufacturer scaling is active
T
h
= A_h * T + B_h
Tout = T
h
(1.6) Manufacturer scaling active (factory setting)
T
a
= A_w * T + B_w
Tout = T
a
(1.7) User scaling active
Th = A_h * T + B_h
Ta = A_w * T + B_w
Tout = Ta
(1.7) Manufacturer and user scaling active
Key
Name Name Register
X_ref Output value of the A/D converter
T
ref
Temperature of the cold junction
U
ref
Voltage value of the cold junction
X_m ADC value of the temperature sensor
U
m1
Voltage value of the temperature sensor
A_a Vendor calibration: Gain R17
B_a Vendor calibration: Offset R18
A_h Manufacturer scaling: Gain R20
B_h Manufacturer scaling: Offset R19
A_w User scaling: Gain R34
B_w User scaling: Offset R33
U
k
Sum of U
ref
and U
m1
T Measured temperature in 1/16°C
T
h
Temperature after vendor scaling (1/10°C)
T
a
Temperature after user scaling
Tout Process data to PLC
The equations of the straight line are enabled via register R32
Fig.4: Data Flow
Mounting and wiring
KL3311, KL3312, KL3314 and KL3302 15Version: 4.2
3 Mounting and wiring
3.1 Instructions for ESD protection
NOTE
Destruction of the devices by electrostatic discharge possible!
The devices contain components at risk from electrostatic discharge caused by improper handling.
Please ensure you are electrostatically discharged and avoid touching the contacts of the device directly.
Avoid contact with highly insulating materials (synthetic fibers, plastic film etc.).
Surroundings (working place, packaging and personnel) should by grounded probably, when handling
with the devices.
Each assembly must be terminated at the right hand end with a KL9010 bus end terminal, to ensure the
protection class and ESD protection.
Fig.5: Spring contacts of the Beckhoff I/O components
3.2 Installation on mounting rails
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!
Mounting and wiring
KL3311, KL3312, KL3314 and KL330216 Version: 4.2
Assembly
Fig.6: Attaching on mounting rail
The bus coupler and bus terminals are attached to commercially available 35mm mounting rails (DIN rails
according to EN60715) by applying slight pressure:
1. First attach the fieldbus coupler to the mounting rail.
2. The bus terminals are now attached on the right-hand side of the fieldbus coupler. Join the compo-
nents with tongue and groove and push the terminals against the mounting rail, until the lock clicks
onto the mounting rail.
If the terminals are clipped onto the mounting rail first and then pushed together without tongue and
groove, the connection will not be operational! When correctly assembled, no significant gap should
be visible between the housings.
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the mounting rails with a height of 7.5mm under the terminals
and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
Mounting and wiring
KL3311, KL3312, KL3314 and KL3302 17Version: 4.2
Disassembly
Fig.7: Disassembling of terminal
Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:
1. Pull the terminal by its orange-colored lugs approximately 1cm away from the mounting rail. In doing
so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of
the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved
housing surfaces and pull the terminal out of the bus terminal block.
Connections within a bus terminal block
The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by
joining the components:
The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus
Terminal electronics.
The power contacts deal with the supply for the field electronics and thus represent a supply rail within
the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24V)
or for higher voltages via power feed terminals.
Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Terminals must
be taken account of, since some types (e.g. analog Bus Terminals or digital 4-channel Bus Termi-
nals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx
or EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail.
PE power contact
The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first
when plugging together, and can ground short-circuit currents of up to 125A.
Mounting and wiring
KL3311, KL3312, KL3314 and KL330218 Version: 4.2
Fig.8: Power contact on left side
NOTE
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or-
der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10mm from the group of terminals.
WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!
Mounting and wiring
KL3311, KL3312, KL3314 and KL3302 19Version: 4.2
3.3 Installation instructions for enhanced mechanical load
capacity
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
Additional checks
The terminals have undergone the following additional tests:
Verification Explanation
Vibration 10 frequency runs in 3 axes
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude
60.1Hz<f<500Hz acceleration 5g, constant amplitude
Shocks 1000 shocks in each direction, in 3 axes
25 g, 6 ms
Additional installation instructions
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
The enhanced mechanical load capacity is valid for all permissible installation positions
Use a mounting rail according to EN 60715 TH35-15
Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth
terminal or reinforced end clamp
The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of
the rail
The mounting points of the mounting rail must be set at 5 cm intervals
Use countersunk head screws to fasten the mounting rail
The free length between the strain relief and the wire connection should be kept as short as possible. A
distance of approx. 10 cm should be maintained to the cable duct.
3.4 Connection
3.4.1 Connection system
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!
Overview
The Bus Terminal system offers different connection options for optimum adaptation to the respective
application:
The terminals of ELxxxx and KLxxxx series with standard wiring include electronics and connection
level in a single enclosure.
Mounting and wiring
KL3311, KL3312, KL3314 and KL330220 Version: 4.2
The terminals of ESxxxx and KSxxxx series feature a pluggable connection level and enable steady
wiring while replacing.
The High Density Terminals (HD Terminals) include electronics and connection level in a single
enclosure and have advanced packaging density.
Standard wiring (ELxxxx / KLxxxx)
Fig.9: Standard wiring
The terminals of ELxxxx and KLxxxx series have been tried and tested for years.
They feature integrated screwless spring force technology for fast and simple assembly.
Pluggable wiring (ESxxxx / KSxxxx)
Fig.10: Pluggable wiring
The terminals of ESxxxx and KSxxxx series feature a pluggable connection level.
The assembly and wiring procedure is the same as for the ELxxxx and KLxxxx series.
The pluggable connection level enables the complete wiring to be removed as a plug connector from the top
of the housing for servicing.
The lower section can be removed from the terminal block by pulling the unlocking tab.
Insert the new component and plug in the connector with the wiring. This reduces the installation time and
eliminates the risk of wires being mixed up.
The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3
mm. The maximum height of the terminal remains unchanged.
A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual
connection wires when the connector is removed.
Conductor cross sections between 0.08mm
2
and 2.5mm
2
can continue to be used with the proven spring
force technology.
The overview and nomenclature of the product names for ESxxxx and KSxxxx series has been retained as
known from ELxxxx and KLxxxx series.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51

Beckhoff KL3311 Documentation

Type
Documentation
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI