Prolon PL-T1000 Quick start guide

Type
Quick start guide

This manual is also suitable for

Below you will find brief information for PL-RS, PL-T200, PL-T500, PL-T1000, PL-C1000-VAV, PL-VC2000. This document provides information on Prolon VAV controllers and wall sensors. It covers the dimensions and wiring of analog and digital sensors, including the PL-RS, PL-T200, PL-T500, and PL-T1000 models. It also details installation of PL-T1000, auxiliary analog input, operation, changing setpoint and schedule override. The guide includes information about the VAV zone controllers PL-C1000-VAV and PL-VC2000. It mentions compliance and technical specification.

Below you will find brief information for PL-RS, PL-T200, PL-T500, PL-T1000, PL-C1000-VAV, PL-VC2000. This document provides information on Prolon VAV controllers and wall sensors. It covers the dimensions and wiring of analog and digital sensors, including the PL-RS, PL-T200, PL-T500, and PL-T1000 models. It also details installation of PL-T1000, auxiliary analog input, operation, changing setpoint and schedule override. The guide includes information about the VAV zone controllers PL-C1000-VAV and PL-VC2000. It mentions compliance and technical specification.

QUICK START GUIDE
VAV CONTROLLERS & WALL SENSORS
www.proloncontrols.com | info@proloncontrols.com
17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9
REV 1.0
PL-QCK-WSENSOR/VC2000-EN
© Copyright 2018 Prolon. All rights reserved.
No part of this document may be photocopied or reproduced by any means, or translated to
another language without prior written consent of Prolon. All specications are nominal and
may change as design improvements are introduced. Prolon shall not be liable for damages
resulting from misapplication or misuse of its products. All trademarks are the property of their
respective owners.
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 3
Analog Sensor (PL-RS) .................................................................................................4
Dimensions and Wiring .....................................................................................4
Digital Sensor (PL-T200) ...............................................................................................6
Dimensions and Wiring .....................................................................................6
Digital Sensor (PL-T500) ...............................................................................................8
Dimensions and Wiring .....................................................................................8
Digital Sensor (PL-T1000) ........................................................................................... 10
Installation .......................................................................................................... 10
Auxiliary Analog Input .................................................................................... 12
Operation ............................................................................................................ 12
Changing the Setpoint ................................................................................... 13
Schedule Override ........................................................................................... 13
VAV Zone Controller (PL-C1000-VAV) ....................................................................... 14
VAV Zone Controller (PL-VC2000) ............................................................................ 16
Compliance............................................................................................................... 18
Technical Specications ....................................................................................... 18
Table of Contents
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN4
Analog Sensor (PL-RS)
COM
THERM
COM
POT
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Schedule override
Room temperature
Setpoint (10K)
Dimensions and Wiring
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 5
COM
THERM
COM
POT
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Schedule override
Room temperature
Setpoint (10K)
Temperature table (thermistor: 10K Type 3)
Fahrenheit 41 50 59 68 77 86 95 104
Celsius 5 10 15 20 25 30 35 40
Ohms 25395 19903 15714 12493 10000 8056 6530 5324
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN6
Digital Sensor (PL-T200)
Dimensions and Wiring
INT A (+)
INT B (-)
24VAC
COM
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Schedule override
(hold for 3 second)
Communication (RS485)
Power (2 VA max)
RJ45 connection
(to C1000)
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 7
INT A (+)
INT B (-)
24VAC
COM
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Schedule override
(hold for 3 second)
Communication (RS485)
Power (2 VA max)
RJ45 connection
(to C1000)
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN8
Digital Sensor (PL-T500)
Dimensions and Wiring
INT A (+)
INT B (-)
24VAC
COM
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Communication (RS485)
Power (2 VA max)
RJ45 connection
(to C1000)
Schedule override:
Hold 3 seconds
Change unit °F/°C:
Double-click
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 9
INT A (+)
INT B (-)
24VAC
COM
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Communication (RS485)
Power (2 VA max)
RJ45 connection
(to C1000)
Schedule override:
Hold 3 seconds
Change unit °F/°C:
Double-click
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN10
Digital Sensor (PL-T1000)
Installation
1. Open casing to remove back cover by pushing on the tab located
underneath the thermostat. (See Figure 1)
2. Pull wire(s) throught central hole of back cover.
3. Screw in the back cover to the wall.
4. Connect wires:
If using twisted pair wires:
- Pull out screw terminal block.
- Remove 1 cm insulation from each wire.
- Connect the wires to the terminal blocks and reconnect
the terminal blocks. (See Figure 2)
If using CAT5 cable:
- Plug the cable into the RJ45 jack of the T1000 (if CAT5 cable
is opened at the controller, refer to Figure 3 for pinout of the
T1000’s RJ45 jack).
5. Reconnect top cover.
IMPORTANT! Do not install the thermostat under the following
conditions:
Any location exposed to direct sunlight.
On an outside wall.
Near an air dischatge grill.
In a location where vertical sir circulation is retricted.
Near a dimmer switch.
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 11
Figure 1
Figure 2
Figure 3
INT A
INT B
24 VAC
COM
24V
RJ45 (Female)
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN12
Digital Sensor (PL-T1000)
Auxiliary Analog Input
The T1000 has auxiliary analog input which can be used to connect
another thermistor. The T1000 can be congured to use this alternate
temperature reading for a variety of functions, including temperature
averaging or radiant oor slab temperature. The alternate thermistor
(10KΩ type 3) can be connected to the auxiliary input using the AUX
IN“ and “COM“ pins. (See gure below)
Analog Input
Operation
The T1000 is controlled using the circular touch pad on the bottom half
of the thermostat. The touch pad uses capacitive sensing technology
to detect nger proximity. There are no moving parts to push or rotate.
The T1000 is controlled using simple scrolling, tapping or holding
motions, performed around the circle of the touch pad. The center of
the circle is unused.
Scroll clockwise or
counterclockwise
to adjust or navigate
Tap here to
ENTER
Tap here to
go BACK
5
6
7
8
9
10
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 13
Changing the Setpoint
Schedule Override
The First, go to the Setpoint screen.
Scroll or tap
(any direction)
Heat SP
Cool SP
Adjust your setpoint
by scrolling clockwise
or counterckwise
View current zone
temperature
Home Screen Setpoint Screen
Tap anywhere
(or simply wait)
return to
Home Screen
The sun icon is
displayed when
overridden
OVERRIDE ACTIVE
(Occupied mode)
The moon icon
indicates
unoccupied mode
Scroll clockwise
to override
67.5
79.5
67.5
79.5
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN14
VAV Zone Controller (PL-C1000-VAV)
INT Port: Incoming Modbus RS485 communication from digital
sensor -OR- Remote computer with Prolon Focus software
Digital Input for night setback / Standby mode
Multi-function analog input
Common for all the inputs
Temperature setpoint (0-10K potentiometer)
Room temperature sensor (10K thermistor)
Output 5 (analog 0-10VDC) (Max Current: 40 mA)
Output 4 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 3 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 2 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 1 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Power source of the controller (24 VAC - Class 2)
NET Port: Incoming Modbus RS485 communication
- OR - BACnet MS/TP
32-122 °F (0-50 °C) Non-condensing
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 15
INT Port: Incoming Modbus RS485 communication from digital
sensor -OR- Remote computer with Prolon Focus software
Digital Input for night setback / Standby mode
Multi-function analog input
Common for all the inputs
Temperature setpoint (0-10K potentiometer)
Room temperature sensor (10K thermistor)
Output 5 (analog 0-10VDC) (Max Current: 40 mA)
Output 4 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 3 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 2 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 1 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Power source of the controller (24 VAC - Class 2)
NET Port: Incoming Modbus RS485 communication
- OR - BACnet MS/TP
cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN16
VAV Zone Controller (PL-VC2000)
32-122 °F (0-50 °C) Non-condensing
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN 17
Service pin
General purpose analog input
(0-5 VDC, 4-20mA, 10K thermistor)
Supply / Radiant / Zone / Occupancy / Discharge
Digital sensor (T1000, T500 or T200) /
Remote computer with Focus
Analog output (0-10 VDC) (max current: 40 mA)
Network communication
Digital output - Isolated Triac
Dry contact (24 VAC) (max current: 750 mA)
Power source of the controller
(24 VAC - Class 2)
Airflow Sensor (PL-VC2000-PI)
Airflow sensors are only included in the PL-VC2000-PI
models only. Adding an airflow sensor to the Prolon VC2000
lets it regulate the airflow as well as temperature in a zone,
independently of the static pressure variations of the system.
The default flow sensor has a range of 0 to 2 in H20
(0 to 500 Pa). Depending on the flow cross used, this
translates to roughly 0-3500 ft/min.
cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN18
Compliance
Technical Specications
Digital Sensor (PL-T1000)
FCC Compliant to CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B) / NMB-3(B)
RoHS Directive (2002/95/EC)
VAV Zone Controller (PL-C1000-VAV / PL-VC2000)
cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1
CAN/CSA-C22.2 No. 2015-12, Signal Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class B
Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B)/NMB-3(B)
RoHS Directive (2002/95/EC)
FCC User Information
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that
may cause undesired operation.
Industry Canada
This Class (B) digital apparatus meets all the requirements of the Canadian
Interference-Causing Equipment regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du
Réglement sur le matériel brouilleur du Canada.
PL-RS / PL-T200
Supply: 24 VAC ±10%, 50/60 Hz
Consumption: 2 VA max
PL-T500 / PL-T1000
Supply: 24 VAC ±10%, 50/60 Hz
Consumption: 5 VA max
PL-C1000-VAV
Supply: 24 VAC ±10%, 50/60 Hz
Consumption: 2 VA (Typ), 32 VA (Input)
PL-VC2000
Supply: 24 VAC ±10%, 50/60 Hz, Class 2
Consumption: 3 VA (Typ), 5 VA (Max),
24 VA (Input)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Prolon PL-T1000 Quick start guide

Type
Quick start guide
This manual is also suitable for

Below you will find brief information for PL-RS, PL-T200, PL-T500, PL-T1000, PL-C1000-VAV, PL-VC2000. This document provides information on Prolon VAV controllers and wall sensors. It covers the dimensions and wiring of analog and digital sensors, including the PL-RS, PL-T200, PL-T500, and PL-T1000 models. It also details installation of PL-T1000, auxiliary analog input, operation, changing setpoint and schedule override. The guide includes information about the VAV zone controllers PL-C1000-VAV and PL-VC2000. It mentions compliance and technical specification.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI