LG LCN246HV Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
Cassette-Type Air Conditioner
SVC MANUAL(Exploded View)
MODEL : ATNH243PLAE[LCN246HV]
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
- 2 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Specification
Power Supply Ø/V/Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal running current A
Fan Motor Type
Fan Type
Motor Output x Number of Unit
Air Flow Rate(H/M/L) CMM
cfm
External Static Pressure mmAq
Capacitor μF/Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(WxHxD) Decorative Panel mm(inch)
Weight Body kg(lbs)
Decorative Panel kg(lbs)
Air Filter
Sound Level (H/M/L) dB(A)+3
Piping Liquid mm(inch)
Connections Gas mm(inch)
Drain(OD/ID) mm(inch)
Dehumidification Rate l/h
Safety devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable outdoor unit
Power and transmission interunit cable No. x AWG
Model
Decoration panel
ATNH243PLAE[LCN246HV]
PT-UMC
Indoor unit type Ceilling Cassette - 4way
1 / 208-230 / 60
6.74
23,000
7.33
25,000
10.4
BLDC
Turbo Fan
60 x 1
18 / 16 / 14
636/565/494
-
220 / 450
Direct Drive
2R x 8C x 19
840 x 204 x 840 (33 x 8 x 33)
950 x 37 x 950(37 3/8 x 1 15/32 x 37 3/8)
21(46.3)
5(11.02)
Long life filter
39 / 37 / 34
9.52 (3/8)
15.88 (5/8)
32/25
2.1
Fuse, Thermal protector for fan motor
Thermistor
R410A
EEV(Outdoor Unit)
LUU246HV
4 x 18
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m(24.6ft)
- Level Difference of Zero.
2. Without optional accessories(i.e. Plasma kit, elevation grille etc.) and with maximum airvolume (Cassette type is using PQRCUS0)
3. Wiring cable size must comply with the applicable local and national code.
Conversion Formula
Btuh = kW × 3,412
cfm = CMM × 35.3
- 3 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
2. Piping Diagrams
Indoor Unit
Th2
Th3
Th2
Th1
Heat Exchanger
: Cooling
: Heating
Turbo Fan
LOC. Description PCB Connector
Th1 Thermistor for inlet air temperature CN_ROOM
Th2 Thermistor for EVA. in temperature CN_PIPE/IN
Th3 Thermistor for EVA. out temperature CN_PIPE/OUT
Model Gas Liquid
ATNH243PLAE[LCN246HV] 15.88(5/8) 9.52(3/8)
[Unit:mm(inch)]
- 4 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
3. Wiring Diagrams
CN_POWER
CN_D/PUMP
CN_MOTOR
CN_VANE2 CN_VANE1
CN_FLOAT CN_DISPLAY
CN_OPTION
CN_REMO
CN_ROOM
CN_PIPE/IN
CN_PIPE/OUT
SW01
- 5 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Indoor Unit
4. Exploded View
130411
131410
354211
148000
W49810
346810
W48310
W48300B
249310
352150
130911A
131400B
263230B
359012
W4056
267110
W6640
249951
W3110
268711B
W0FZZ
135500
268711D
268711E
352118
130911C
131400D
552111
148000
158591
263230C
330871A
330871B
349480
W50060
567480A
* 268711D is LGELAP only
Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)
- 6 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
146811
147581
145200
135500
159830
135800
135303
Front Panel
P/NO : MFL62129309
MAY, 2010
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

LG LCN246HV Owner's manual

Category
Split-system air conditioners
Type
Owner's manual

Ask a question and I''ll find the answer in the document