ELECTRIC HEATERS
INSTALLATION INSTRUCTIONS
Models: ANEH0521A, ANEH1021A, ANEH09B1B, ANEH18B1B
ANEH18B1C, ANEH36B1C, ANEH36B2C
• Please read this instruction sheet completely before installing the product.
• Installation work must be performed in accordance with national wiring standards by authorized
personnel only.
P/No.: 3828A20229E
2
Table 1 Accessory Heaters Electrical Data
Ton
Heater
Model No.
Heater
KW Rating
Control
Stages
Heater
Rated Volts
Standard indoor fan motor
M.C.A M.C.AM.F.S M.F.SM.C.B
M.C.B
Over size indoor motor
Note; Heater KW ratings are at 208/240V for 220V unit.
M.C.A; Minimum Circuit Ampere
M.F.S; Maximum Fuse Size
M.C.B; Maximum Circuit Breaker
* HACR type Circuit Breaker per NEC.
Installation
Figure 1
Figure 2
: Disconnect all electric power
supplies of unit before sevicing and installing.
WARNING
Flange
Duct Flange
(In the filter assy kit)
3, 4, 5RT
ANEH0521A 3.6/5.0 1 240/60/1 27.6/32.2 60/60 60/60 - - -
ANEH1021A 7.2/10.0 1 240/60/1 47.4/55 60/60 60/60 - - -
6.25RT
ANEH09B1B 7.8/9.0 1 240/60/3 30.4/35.1 60/60 60/60 - - -
ANEH18B1B 15.6/18.0 1 240/60/3 50.9/58.7 70/70 70/70 - - -
7.5RT
ANEH09B1B 7.8/9.0 1 240/60/3 30.4/35.1 60/60 60/60 33.0/38.1 60/60 60/60
ANEH18B1B 15.6/18.0 1 240/60/3 50.9/58.7 70/70 70/70 53.3/61.5 70/70 70/70
10, 12.5RT
ANEH09B1B 7.8/9.0 1 240/60/3 35.7/41.2 60/60 60/60 42.0/48.4 60/60 60/60
ANEH18B1B 15.6/18.0 1 240/60/3 56.2/64.8 70/70 70/70 62.4/72.0 80/80 80/80
ANEH18B1C 15.6/18.0 1 240/60/3 56.2/64.8 70/70 70/70 62.4/72.0 80/80 80/80
15, 20RT
ANEH36B1C 31.2/36.0 1 240/60/3 97.1/112.1 125/125 125/125 103.4/119.3 125/125 125/125
ANEH36B2C 31.2/36.0 2 240/60/3 97.1/112.1 125/125 125/125 103.4/119.3 125/125 125/125
1. Remove the flanges on the top-cover.
(In case of 15RT, 20RT)
2. Assemble the electric heater kit on the top-
cover.(See Figure 2.)
• How to assemble Duct Flange on the Electric
Heater.
3~5RT 6~20RT
3
Control Wiring
• Connect control wires(Brown) on terminal
block (and P.C.B) as shown on wiring
diagram attached on control box cover.
Power Wiring
1. Then route wires down through the
opening in the top of control box. Connect
wires to high voltage terminal block. Refer
to wiring diagram supplied with heater.
2. Check to make certain the proper size
fuses are installed per the fuse table for the
exact heater being used.
3. Ground unit at the grounding screw
provided. Make sure all field wiring
complies with all applicable codes and
water tightness.(Figure 3)
CAUTION: Use copper conductors only to
prevent equipment damage. Unit terminals
are not designed to accept any other wiring.
4. Replace control box cover using screws.
To Unit Control Box
Ground
Power Supply
(High Voltage)
Figure 3
4
Dimension
e
f
d
c
Hole for High Voltage
Power Supply
Removable Panel
b
a
ANEH0521A ANEH1021A ANEH09B1B ANEH18B1B ANEH18B1C ANEH36B1C ANEH36B2C
a 295.4 295.4 270.4 270.4 370.4 370.4 370.4
b 381.2 381.2 440 440 534 534 534
c 381.6 381.6 729 729 860.6 860.6 860.6
d 234.6 234.6 524 524 615.6 615.6 615.6
e 325.6 325.6 370 370 454 454 454
f 25.4 25.4 25.4 25.4 25.4 25.4 25.4