MULTISPAN FA-11 Owner's manual

Type
Owner's manual
OPERATING MANUAL
Fault Annunciator : Technical Datasheet
FA-11
www.multispanindia.com
Page - 1FA-11
1) Model : FA-11 (96x96x50mm)
2) Display: LCD 16*2
3) Input : NC or NO CONTACT
4) LED : INDICATION
1) AUDIO ALARM
2) VISUAL ALARM
3) M/C OUTPUT
5) Output:
1) AUDIO ALARM RELAY
2) VISUAL ALARM RELAY
3) M/C OUTPUT RELAY
6) Power Supply: 100 To 270V AC,50/60Hz
Approx 6VA
7) Protection Level:
Technical Specification:
Description of the fault Annunciator :
1) When plant starts initially, instrument will start sensing fault after the
5 Second delay. Delay is required to allow all fault signals to get
in to set mode.
2) The instrument will constantly monitor all the faults that are preset during the
plant operation.
3) Fault logic is selectable by OPEN signal or CLOSE signal by user.
In Case of HARD Fault, which indicates higher risk :
1) The Plant will trip immediately.
2) Fault message will be display on LCD panel.
3) Generate audio-alarm and visual alarm (Tower Light flashing).
1) The Plant will not trip immediately.
2) Fault message will be display on LCD panel.
3) Generate audio-alarm and visual alarm (Tower Light flashing).
In Case the Fault is Solved in 5 Minutes or less :
1) Display will show NORMAL message.
2) Visual alarm signal will be OFF.
In Case the Fault is Not Solved in 5 Minutes or less :
1) Plant will Trip
2) Generate audio-alarm and visual alarm (Tower Light flashing).
3) Facility for operator only to stop Audio alarm.
4) After the fault is solved, Press key & key to Restart the plant
Facility for operator only to stop audio alarm.
4)
In Case of SOFT Fault
*
*
5) After the fault is solved, Press key & key to Restart the plant
ACCEPT
ACCEPT
RESET
RESET
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
IP-65(Front side) AS per
IS/IEC 60529:2001
FAULT INPUTS
1. D.P.S (P.S.)
(NORMAL) OUTPUTS
NO CNC
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
M/C
WORKING:
HARD FAULT
Normal Condition:
Action
No Action 1.D.P.S.
(P.S.)
Flashing
ON Relay ON
(Plant OFF)
Inputs-1
Open
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
Page - 2FA-11 www.multispanindia.com
To define healthy condition
either NO or NC by front key
To define no. of fault input
Press key
SET Press key
SET
PASSWORD 25 PASSWORD 50
FAULT TYPE - NO FAULT NO: 01
Fault type can be
change by key
User can select no.of fault
input wants to use up to 10.
To save the number of fault selection,
Power off the instrument.
Enter password
“25” by & key
Enter password
“50” by & key
Action
No Action NORMAL
OFFOFF Relay OFF
(Plant ON)
All Inputs
Shorted
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
Fault in Input-1
INPUTS (FAULT IN CH-1) OUTPUTS
NO CNC
M/C
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
5. T.S. (HT SNK)
6. T.S. (C BSBR)
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
Acknowledge (ACCEPT) the Fault
Fault Clear
INPUTS
INPUTS
1 LOW VOLTAGE
(FAULT ACCEPT)
(FAULT ACCEPT)
OUTPUTS
2 HIGH VOLTAGE
3 OVER CURRENT
4 MOTOR TEMP HIGH
- - - - - - - - - - - - - - -
N OVER TRAVEL
Action
Press
Accept ON
OFF Relay ON
(Plant OFF)
Inputs-1
Open
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
switch
Action
No Action RESET THE
FA-11
ONOFF Relay ON
(Plant OFF)
All Inputs
Shorted
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
NO
NO
C
C
NC
NC
M/C
M/C
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
Page - 3FA-11 www.multispanindia.com
1.D.P.S.
(P.S.)
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
RESET THE ANNUNCIATOR:
SOFT FAULT:
INPUTS
INPUTS
FAULT IN INPUT-3
(FAULT ACCEPT)
(FAULT ACCEPT)
M/C
OUTPUTS
OUTPUTS
Action
Press
Reset NORMAL
OFF
OFF Relay OFF
(Plant ON)
All Inputs
Shorted
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
switch
M/C
Action
No Action 3. T.S.
(SP MAN)
Flashing
OFF Relay OFF
(Plant ON)
Inputs-3
Open
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
NO
NO
C
C
NC
NC
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
Page - 4FA-11 www.multispanindia.com
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
NO CNC
M/C
IF FAULT RECOVERED BEFORE 5 MINUTES:
IF FAULT IS NOT RECOVERED IN 5 MINUTES:
Action
No Action NORMAL
OFF
OFF Relay OFF
(Plant ON)
All Inputs
Shorted
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
FAULT INPUTS(NORMAL) OUTPUTS
OUTPUTS
Action
No Action ON Relay ON
(Plant OFF)
Inputs-3
Open
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
(FAULT IN CH-1)
Flashing
NO CNC
M/C
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
Page - 5FA-11 www.multispanindia.com
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
3. T.S.
(SP MAN)
ACKNOWLEDGE ( ACCEPT) THE FAULT
INPUTS
FAULT IN INPUT-3
OUTPUTS
Action
PRESS
ACCEPT
SWITCH
ON
OFF
NOTE : Accept is also available at back Terminal
Relay ON
(Plant OFF)
Inputs-3
Open
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
(FAULT IN CH-1)
Fault Clear
INPUTS (FAULT ACCEPT)
Action
No Action RESET THE
FA-11
ON
OFF Relay ON
(Plant OFF)
All Inputs
Shorted
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
NO CNC
M/C
NO CNC
M/C
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
Page - 6
FA-11 www.multispanindia.com
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
3. T.S.
(SP MAN)
ALL FAULT CLEAR
MULTISPAN
PRESS ENTER KEY
INSTRUMENT
ENT
Press key
(Normal Display)
RESET THE ANNUNCIATOR:
Fault Report:
For Example :
For Example :
Note :
Note :
Note :
INPUTS (FAULT ACCEPT)
Press + Key for 4 sec. to go to fault REPORT MODE.
Display will show Number of Fault & Number of Time that fault occurs.
OUTPUTS
Action
Press
Reset NORMAL
OFF
OFF Relay OFF
(Plant ON)
All inputs
shorted
Message
on LCD
Display
Audio
Output
Visual
Output
Machine
Output
Fault
Input
switch
NO CNC
M/C
NOTE : Reset is also available at back Terminal
RESET
ENT
SET
MULTISPAN
INSTRUMENTS
ENT
No. Of Fault : 03
No. Of Time : 04
DT-19 : 03 F-04
TM: 14:14:46
Press Key to change No. of Fault.
DATE (DT)- 19:03(DD:MM).
TIME (TM)- 14:14:46(HR : MIN : SEC).
Press Key for Display DATE & TIME of fault History for particular
fault Number.
NUMBER of Times Fault occur (F-04):it will be auto shifted
For Clear all Fault
To Clear all Faults Press key and Then Power on the instrument.
Press key + Power On
SET
SET
Page - 7FA-11 www.multispanindia.com
1. D.P.S (P.S.)
2. D.P.S. (COIL)
3. T.S. (SP MAN)
4. T.S. (RT MAN)
5. T.S. (HT SNK)
6. T.S. (C BSBR)
Massage (maximum 12 Character include space)
Example: for Display in Normal Condition
Rear Panel:
Example for Defining Hard Fault
Wire connectors are provided for the wiring purpose for power input,
alarms, machine output and 10 number of faults.
In Normal Condition, Default message on Display is “Normal” you can
change this message by using RS-232
All 10 Faults can be programmable as hard fault and Soft fault at site
by using RS-232 Communication.
For Defining Fault as hard fault and soft fault terminal software used .
Fault Number in two digit
Fault Number in two digit
Massage (maximum 12 Character include space)
Massage (maximum 12 Character include space)
Example for Defining soft Fault
Connection Diagram:
Product improvement and upgrade is a constant procedure. So for more updated operating information and support,
Please contact our helpline : +91-9978991474/76/82 or Email at mark[email protected] Ver:1707
Page - 8
FA-11 www.multispanindia.com
14
30
13
29
12
28
11
27
10
26
17 18 19 20 21 22 23 24 25
12345 6 7 8 9 15
31
16
32
AUX. SUPPLY
100 To
250V AC
~
100
250V AC
~
50/60 HZ
4VA
AUX. SUPPLY
100 To
250V AC
~
~
50/60 Hz
6VA
100
270V AC
LN
R1 R2 R3
NC NC NC CCC NONONO
Fault-1 Fault-2 Fault-3 Fault-4 Fault-5 Fault-6
ACCEPTRST
GND
TXD
RS-232
Made in India
www.multispanindia.com
1. D.P.S (P.S.)
3. T.S. (SP MAN)
5. T.S. (HT SNK)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

MULTISPAN FA-11 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI