Original instructions
Keep this manual for future reference.
This product must only be installed or serviced by qualified personnel.
Please read this manual carefully before installation.This appliance is filled with R32.
INSTALLATION MANUAL
Original Instructions
MULTI-SPLIT AIR CONDITIONER
3U55S2PR1FA
4U71S2PR1FA
4U80S2PR1FA
5U125S2PN1FA
0150558811
Move and scrap the air conditioning
Contents
Safety Precautions
Read Before Installation
Accessories
Procedure for Selecting the location
Installation drawings of indoor and
outdoor units
Precautions on Installation
Limitations on the installation
Refrigerant piping work
Pump Down Operation
Wiring work
Dred function
Test running
Trouble shooting
23
19
English
30
Outdoor Unit Installation
5U125S2PN1FA
5U100S2PS1FA
Your air conditioning product is marked with this
symbol.This means that electrical and electronic
products shall not be mixed with unsorted
household waste.Do not try to dismantle the
system yourself:the dismantling of the air
conditioning system,treatment of the refrigerant,of oil and of
other part must be done by a qualified installer in accordance
with relevant local and national legislation.Air conditioners
must be treated at a specialized treatment facility for reuse,
recycling and recovery.By ensuring this product is disposed
of correctly,you will help to prevent potential negative cons-
equences for the environment and human health.Please
contact the installer or local authority for more information.
Battery must be removed from the remote controller and dis-
posed of separately in accordance with relevant local and
national legislation.
The products are fulfilled with the requirements in the
directive 2011/65/EU of the European parliament and of
council on the Restriction of the use of Certain Hazardous
Substances in Electrical and Electronic Equipment(EU
RoHS Directive)
WEEE
In accordance with the directive 2012/19/EU of the European
parliament,herewith we inform the consumer about the dis-
posal requirements of the electrical and electronic products.
DISPOSAL REQUIREMENTS:
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
This product contains fluorinated greenhouse gases covered
by the Kyoto Protocol.Do not vent into the atmosphere.
Refrigerant type:R32
GWP*value:675
GWP=global warming potential
Please fill in with indelible ink,
1 the factory refrigerant charge of the product
2 the additional refrigerant amount charged in the field
and
1+2 the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the
product charging port(e.g.onto the inside of the stop value
cover).
A contains fluorinated greenhouse gases covered by the
Kyoto Protocol
B factory refrigerant charge of the product:see unit name
plate
C additional refrigerant amount charged in the field
D total refrigerant charge
E outdoor unit
F refrigerant cylinder and manifold for charging
Air conditioner working temperature: cooling -10~46 degree, heating -15~24 degree.
The single indoor unit will reduce in heating efficiency if the ambient temperature is under 0 degree.
WARNING
IMPORTANT INFORMATION REGA-
RDING THE REFRIGERANT USED
1
A
B
C
D
kg
kg
kg
R32
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazard.
This appliance is not intended for use by persons (including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
This appliance can be used by children aged from 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge if they have been given supervision
or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children
without supervision.
The appliances are not intended to be operated by means of an external timer or separate remote-
control system.
Keep the appliance and its cord out of reach of children less than 8 years.
The A-weighted sound pressure level is below 70 dB.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms,
or for commercial use by lay persons.
Disconnect the appliance from its power source during maintenance service and when replacing parts.
After reading this handbook, hand it over to those who will be using the unit.
The user of the unit should keep this mamual at hand and make it available to those who will be
performing repairs or relocating the unit. Also, make it available to the new user when the user changes
hands.
WARNING
CAUTION:
2
Ask your dealer or qualified personnel to carry out installation work.Do not attempt to install the air
conditioner yourself. Improper Installation may result in water leakage, electric shocks, fire or explosion.
All the cables shall have got the European authentication certificate. During installation, when the
connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.
If refrigerant gas leaks during installation, ventilate the area immediately.oxic gas may be produced.if the
refrigerant comes into contact with fire,and explosion may be happen.
Make sure ground connection is correct and reliable.Do not earth the unit to a utility pipe, lightning
conductor or telephone earth lead. Imperfect earthing may result in electric shocks.
The breaker of the air conditioner should be all-pole switch and explosion-proof. The distance between
its two contacts should not be no less than 3mm. Such means for disconnection must be incorporated in
the wiring.
The air conditioning sockets should be placed 1m above from the air conditioner, nor under the air
conditioner. Be sure not to use open flame, high static electrical or high temperature equipments
etc.nearby the air conditioner.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by
the manufacturer.
The appliance must be stored in a room without continuously operating ignition sources, the radius of the
storage area should be no less than 2.5 m (for example:open flames, an operating gas appliance or an
operating electric heater).
Do not pierce or burn.
Be aware that refrigerants may not contain an odour.
The appliance must be installed, operated and stored in a room with a floor area larger than the Minimum
Room Area specified in the table on the following pages,The room should be well ventilated.
Comply with national gas regulations.
This appliance can be used by children aged 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge if they have been given superivision
or instruction concering use of the appliance in a safe way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and user maintenance shall not be made by children without
supervision.
The air conditioner can not be discarded or scrapped Randomly If you need please contact customer
service personnel of Haier to scrap in order to obtain the correct disposal methods.
Reusable mechanical connectors and flared joints are not allowed indoor.
Read the precautions in this manual
carefully before operating the unit.
This symbol shows that this appliance
uses a flammable refrigerant.
If the refrigerant is leaked and exposed
to an external ignition source, there is a
risk of fire.
Do not install the air conditioner at any place where there is danger of flammable gas leakage.In the event of a gas leakage,
build-up of gas near the air conditioner may cause a fire to break out.
Tighten the flare nut according to the specified method such as with a torque wrench.If the flare nut is too tight, it may crack
after prolonged use, causing refrigerant leakage.
Take adequate steps to prevent the outdoor unit being used as a shelter by small animals.Small animals.making contact with
electrical parts can cause malfunctions, smoke or fire.
Please instruct the customer to keep the area around the unit clean
The temperature of refrigerant circuit will be high, please keep the inter-unit wire away from copper pipes that not thermally
insulated.
Only qualified personnel can handle, fill, purge and dispose of the refrigerant.
Read the operator's manual Service indicator, read technical
manual
Safety Precautions
The installation, maintenance, service and repair operations of this product shall be carried
out by professional personnel, who have been trainedand certified by national training
organizations that areaccredited to teach the relevant national competency standards
that may be set in legislation.
Improper installation may cause water leakage, electrical shock, fire, or explosion.
Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire, or explosion.
Be sure to use the supplied or specified installation parts.
Use of other parts may cause the unit to cometo lose, water leakage, electrical shock, fire, or explosion.
Install the air conditioner on a solid base that can support the unit's weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the
national electrical wiring rules or code of practice.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire, or explosion.
Be sure to use a dedicated power circuit. Never use a power supply shared by another
appliance.
For wiring, use a cable long enough to cover the entire distance with no connection.
Do not use an extension cord. Do not put other loads on the power supply, use a dedicated
power circuit.
(Failure to do so may cause abnormal heat, electrical shock, fire, or explosion.)
Use the specified types of wires for electrical connections between the indoor and outdoor
units.
Firmly clamp the interconnectiong wires so their terminals receive no external stresses. Incomplete connections or clamping
may cause terminal overheating, fire, or explosion.
After connectiong interconnecting and supply wiring be sure to shape the cables so that
they do not put undue force on the electrical covers or panels.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, fire, or explosion.
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames, may cause explosion.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames, may cause explosion.)
When installing or relocating the system, be sure to keep the refrigerant circuit free from
substancs other than the specified refrigerant(R32), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture,
resulting in injury.)
During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the compressor
is run, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.
Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone
earth.
Incomplete earth may cause electrical shock, fire, or explosion. A high surge current from lightning or other sources may cause
damage to the air conditioner.
The installation of pipe-work shall be kept to a minimum.
Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is
smaller than the Minimum Room Area specified in the table on the following pages.
Mechanical connections shall be accessible for maintenance purposes.
Information for handling, installation, cleaning, servicing and disposal of refrigerant.
Warning: Keep any required ventilation openings clear of obstruction.
Notice: Servicing shall be performed only as recommended by this manual instruction.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks, fire, or explosion.
WARNING
3
Loading and Unloading/Transporting Management/Storage Requirements
Loading and Unloading Requirements
Installation Precautions
Transporting Management Requirements
Storage Requirements
Installation Instructions
WARNING!
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire or explosion.
Establish drain piping according to the instructions of this manual.
Inadequate piping may cause flooding.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the falre nut may crack after a long time and cause refrigerant leakage.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke fire, or explosion. Please instruct the customer to
keep the area around the unit clean.
CAUTION
4
1) The products shall be carefully handled during loading and unloading.
2) Rude and barbarous handling such as kicking, throwing, dropping, bumping, pulling and rolling is not allowed.
3) The workers engaged in loading and unloading must be subject to necessary trainings on the potential hazards caused by
barbarous handling.
4) Dry powder extinguishers or other suitable fire extinguishing apparatus within the period of validity shall be equipped at the
loading and unloading site.
5) The untrained personnel cannot be engaged in loading and unloading of flammable refrigerants air conditioner.
6) Before loading and unloading, anti-static measures shall be taken, and phones cannot be answered during loading and
unloading.
7) Smoking and open fire are not allowed around the air conditioner.
1) The maximum transporting volume of finished products shall be determined as per local regulations.
2) The vehicles used for transporting shall be operated as per local laws and regulations.
3) Dedicated after-sales vehicles shall be used for maintenance, and exposed transporting of refrigerant
cylinders and the products to be maintained is not allowed.
4) The rain cover or similar shielding material of transporting vehicles shall be provided with certain flame retardancy.
5) Leakage warning device of flammable refrigerant shall be installed inside the closed-type compartment.
6) Anti-static device shall be equipped inside the compartment of transporting vehicles.
7) Dry powder extinguishers or other suitable fire extinguishing apparatus within the period of validity shall be equipped inside
the driver's cab.
8) Orange-white or red-white reflective stripes shall be pasted on the sides and tail of the transporting vehicles, to remind the
vehicles behind of keeping distance.
9) The transporting vehicles shall run at a constant speed, and heavy acceleration/deceleration shall be avoided.
10) Combustibles or the static articles cannot be transported simultaneously.
11) High-temperature area shall be avoided during transporting, and necessary radiating measures shall be taken in case the
temperature inside the compartment is too high.
1) The storage package of equipment used shall be such that no leakage of refrigerant will be caused due to mechanical
damage of the equipment inside.
2) The appliance must be stored in a room without continuously operating ignition sources, the radius of the storage area
should be no less than 2.5 m (for example:open flames, an operating gas appliance or an operating electric heater).
3) Do not pierce or burn.
4) The maximum quantity of the equipment allowed to be stored together shall be determined as per local regulations.
The area of the room in which R32 refrigerant air conditioner is installed cannot be less than the minimum area specified in
the table below, to avoid potential safety problems due to out-of-limit of refrigerant concentration inside the room caused by
leakage of refrigerant from refrigeration system of the indoor unit.
Once the horn mouth of connecting lines is fastened, it may not be used again (the air tightness may be affected).
A whole connector wire shall be used for indoor/outdoor unit as required in the operation specification of installation process
and operation instructions.
Safety Awarenes
Unpacking Inspection
Inspection on Installation Environment
Safety Principles of Installation
No Smoking Cotton clothes Anti-static gloves
BEWARE
ELECTROSTATICS Goggles
Caution, risk of fire
Minimum Room Area
Type
R32 0.306
LFL
kg/m3
h0
m
0.6
1.0
1.8
2.2
Total Mass Charged/kg
Minimum Room Area/m2
1.224 1.836 2.448 3.672 4.896 6.12 7.956
29 51 116 206 321 543
10 19 42 74 116 196
3 6 13 23 36 60
24 9 152440
5
1.Procedures: operation shall be made as per controlled procedures to minimize the probability of risks.
2.Area: area shall be divided and isolated appropriately, and operation in an enclosed space shall be avoided. Before the
refrigeration system is started or before working, ventilation or opening of the area shall be guaranteed.
3.Site inspection: the refrigerant shall be checked.
4.Fire control: the fire extinguisher shall be placed nearby, and fire source or high temperature is not allowed; the sign of "No
smoking"shall be arranged.
1.Indoor unit: nitrogen is sealed during the delivery of indoor units (inside the evaporator), and the red sign at the top of the
green plastic seal cap on the evaporator air pipes of the indoor unit shall be checked first after unpacking. In case the sign is
raised, the nitrogen sealed still exists. Afterwards, the black plastic seal cap at the joint of evaporator liquid pipes of the indoor
unit shall be pressed, to check whether nitrogen still exists. In case no nitrogen is sprayed out, the indoor unit is subject to
leakage, and installation is not allowed.
2.Outdoor unit: the leak detection equipment shall be extended into the packing box of the outdoor unit, to check whether the
refrigerant is leaking. If the refrigerant leakage is identified, installation is not allowed, and the outdoor unit shall be delivered
to the maintenance department.
1.The room area checked cannot be less than the area specified on the warning sign of the indoor unit.
2.Inspection on the surrounding environment of place of installation: the outdoor unit of flammable refrigerants air conditioner
cannot be installed inside an enclosed room reserved.
3.Power supply, switches or other high-temperature articles such as the fire source and oil heater shall be avoided below the
indoor unit.
4.The power supply shall be provided with earthing wire and be reliably earthed.
5.While punching the wall with an electric drill, whether embedded water/electricity/gas pipelines are designed at the hole preset
by the user shall be verified in advance. It is recommended that the through-wall holes reserved shall be used as much as
possible
1. Favorable ventilation shall be maintained at the place of installation (doors and windows are opened).
2. Open fire or high-temperature heat source (including welding, smoking and oven) higher than 548 is not allowed within
the scope of flammable refrigerant.
3. Anti-static measures shall be taken, such as the wearing of cotton clothes and cotton gloves.
4. The place of installation shall be convenient for installation or maintenance. Barriers shall be avoided around the air
inlet/outlet of the indoor/outdoor unit, and the electrical appliance, power switches, sockets, valuables and high-temperature
products within the scope of both sidelines of the indoor unit shall be avoided, and cannot be adjacent to heat source and
flammable and combustible environment.
5. In case of refrigerant leakage of the indoor unit during installation, the valve of the outdoor unit shall be closed immediately,
and windows shall be opened, and all the personnel shall be evacuated. After the leakage of refrigerant is handled, the indoor
environment shall be subject to concentration detection. Further handling is not allowed until the safety level is reached.
6. In case the product is damaged, it must be delivered to the maintenance point. Welding of refrigerant pipelines at the user’s
site is not allowed.
Electrical Safety Requirements
Qualification Requirements of Installer
Indoor Unit Installation
2. Piping layout
3. Nitrogen charging for pressure maintaining and leak detection
Outdoor Unit Installation
6
1.The surrounding conditions (ambient temperature, direct sunlight and rainwater) shall be noticed during electrical wiring,
with effective protective measures being taken.
2.Copper wire cable in line with local standards shall be used as the power line and connector wire.
3.Both the indoor unit and outdoor unit shall be reliably earthed.
4.Wiring for the outdoor unit shall be made first and then the indoor unit. The air conditioner can only be powered on after
wiring and pipe connection.
5.The dedicated branch circuit must be used, and leakage protector with sufficient capacity must be installed.
Relevant qualification certificate must be obtained as per national laws and regulations.
1.Fixing of wall panel and piping layout
In case of left/right water pipe connection for the indoor unit, or in case the evaporator interface of the indoor unit and the horn
mouth of the connecting piping cannot be extended to the outdoor side for installation, the connector pipes shall be connected
to the evaporator piping interface of the indoor unit in the process of horn mouth.
During layout of connecting pipes, drain hose and connector wires, the drain hose and connecting wire shall be placed at the
bottom and top respectively. The power line cannot be twined with the connector wire. The drain pipes (especially inside the
room and machine) must be winded with thermal insulation materials.
After the evaporator of the indoor unit is connected to the connector pipe (after welding), nitrogen more than 4.0MPa
shall be charged inside the evaporator and the piping connected to evaporator with a nitrogen cylinder(adjusted by a reducing
valve). Afterwards, the valve of the nitrogen cylinder shall be closed, for leak detection with soapy water or leak detecting
solution. The pressure shall be maintained for more than 5 minutes, and then whether the system pressure is reduced or not
shall be observed. In case the pressure is reduced, leakage can be identified. After the leak point is handled, the steps above
shall be repeated.
After the evaporator of the indoor unit is connected to connecting piping, nitrogen shall be charged for pressure maintaining
and leak detection. Afterwards, the evaporator shall be connected to the two-way stop valve and three-way stop valve of the
outdoor unit. After the copper cap of the connecting piping is fastened, nitrogen more than 4.0MPa shall be charged at the
access hole of the three-way stop valve with a charging hose. The valve of the nitrogen cylinder shall be closed, for leak
detection with soapy water or leak detecting solution. The pressure shall be maintained for more than 5 minutes, and then
whether the system pressure is reduced or not shall be observed. In case the pressure is reduced, leakage can be identified.
After the leak point is handled, the steps above shall be repeated.
The next step (vacuumizing with a vacuum pump) can only be continued after the installation steps (nitrogen charging for
pressure maintaining and leak detection normal) are completed.
1.Fixing and connection
Note:
a) Fire source shall be avoided within 3m around the place of installation.
b) The leak detection equipment of refrigerant shall be placed at a low position in the
outdoor, and shall be opened.
Vacuumizing
Leak Detection
Post-installation Inspection Items and Test Run
Post-installation Inspection Items
Test Run
Items to Be Checked
Whether the installation is firm or not
Whether the inspection on air leakage is completed
Whether the unit is fully insulated
Whether the drainage is smooth or not
Whether the power voltage is identical to that marked on the
nameplate
Whether the circuit and pipeline are installed correctly
Whether the unit is safely earthed
Whether the type of wire is in line with relevant regulations
Whether barriers are identified at the air inlet/outlet of the
indoor/outdoor unit
Whether the length of refrigerant pipes and the refrigerant
amount charged are recorded
Consequence of Improper Installation
The unit may fall, vibrate or make a noise
The refrigerating capacity (heating capacity) may be insufficient
Condensation or drip may occur
Condensation or drip may occur
Failure may occur or the parts may be burned
Failure may occur or the parts may be burned
Electric leakage may occur
Failure may occur or the parts may be burned
The refrigerating capacity (heating capacity) may be
insufficient
The refrigerant amount charged cannot be confirmed
7
1) Fixing
The support of the outdoor unit shall be fixed onto the wall surface, and then the outdoor unit shall be fixed onto the support
horizontally. In case the outdoor unit is wall-mounted or roof-mounted, the support shall be firmly fixed, to avoid the damage of
strong wind.
2) Installation of connecting pipes
The cone of the connecting pipes shall be aligned with the conical surface of corresponding valve connector. The nut of
connecting pipes shall be installed at a proper position and then be tightened with a spanner. Excessive tightening torque shall
be avoided, or otherwise the nut may be damaged.
A digital vacuum gauge shall be connected for vacuumizing. The duration of vacuumizing shall be at least 15 minutes,
and the pressure of the vacuum gauge shall be below 60Pa.Afterwards, the vacuumizing equipment shall be closed, and
whether the reading of the digital vacuum gauge is increased or not shall be observed after the pressure is maintained for 5
minutes. In case no leakage is identified, the two-way stop valve and three-way stop valve of the outdoor unit may be opened.
Finally, the vacuumizing hose connected to the outdoor unit can be disassembled.
The joint of connecting pipes for the outdoor unit shall be subject to leak detection with soap bubble or dedicated leak
detection equipment.
1. Preparations
(1) Check the power supply.
(2) Check the equipment around, whether there is any combustible source, fire source,or heat source.
(3) Power on is not allowed before all the installation operations are completed and before the leak detection is proven qualified.
(4) The control circuit shall be connected correctly and all the wires shall be firmly connected.
(5) The two-way stop valve and three-way stop valve shall be opened.
(6) All the scattered articles (especially the metal filing and thread residue) shall be removed from the unit body.
2. Methods
(1) Switch on the power supply and press the "ON/OFF" on the remote controller, after which the air conditioner will start
operating.
(2) Press "Mode"to select refrigeration, heating and sweeping wind, and observe whether the air conditioner is under normal
operation.
Relocation Procedures
Safety discharge of refrigerant
Safety discharge of refrigerant
Inspection on operational state Disassembly
Refrigerant recovery by the
system
Cleaning of the indoor unit and
connecting pipes with inert gas
Disassembly
Installation as required in
standards
Inspection on system leakage prior
to disassembly Disassembly
8
For all the faults requiring welding the refrigeration pipelines or components inside the refrigeration system of R32 refrigerant
air conditioners, maintenance at the user's site is never allowed.
For the faults requiring radical disassembly and bending operation of the heat exchanger, such as the replacement of the
outdoor unit chassis and integral disassembly of the condenser, inspection and maintenance at the user's site are never
allowed.
For the faults requiring replacement of the compressor or parts & components of refrigeration system, maintenance at the
user's site is not allowed.
For other faults not involved in the refrigerant container, internal refrigeration pipelines and refrigeration elements, the
maintenance at the user's site is allowed, including the cleaning and dredging of the refrigeration system requiring no
disassembly of refrigeration elements and no welding.
In case replacement of gas/liquid pipes is required during maintenance, the joint of evaporator gas/liquid pipes of the indoor
unit shall be cut off with a cutting knife. Connection is only allowed after re-flaring (the same to the outdoor unit).
Note: in case relocation is required, the joint of evaporator gas/liquid pipes of the indoor unit shall be cut off with a cutting knife.
Connection is only allowed after re-flaring (the same to the outdoor unit).
Maintenance Instructions
Maintenance Precautions
Precautions
Qualification Requirements of Maintenance Personnel
1. All the operators or the maintenance personnel involved in refrigerating circuits shall be provided with the effective certificate
issued by an industry-accepted assessment institute, to ensure that they are qualified for safety disposal of refrigerant as
required in the assessment regulations.
2. The equipment can only be maintained and repaired as per the method recommended by the manufacturer. In case the
assistance from personnel of other disciplines is required, the assistance shall be supervised by the personnel with qualification
certificate involved in flammable refrigerant.
Please call the dealer or the appointed agency.
Follow the following procedures:
Inspection on Maintenance Environment
Maintenance Site Requirements
Leak Detection Methods
Safety Principles
9
Before operation, the refrigerant leaked in the room is not allowed.
The area of the room in which maintenance is made shall be in line with this manual.
Continuous ventilation shall be maintained during maintenance.
Open fire or high-temperature heat source higher than 548 degree which can easily give birth to open fire is not allowed
inside the room within the maintenance area.
During maintenance, the phones and the radioactive electronics of all the operators inside the room must be powered off.
One dry powder or carbon dioxide extinguisher shall be equipped inside the maintenance area, and the extinguisher must
be under available state.
The maintenance site shall be provided with favorable ventilation and must be flat. Arrangement of the maintenance site
inside the basement is not allowed.
Welding zone and non-welding zone shall be divided at the maintenance site, and shall be clearly marked. A certain safety
distance must be guaranteed between the two zones.
Ventilators shall be installed at the maintenance site, and exhaust fans, fans, ceiling fans, floor fans and dedicated exhaust
duct can be arranged, to meet the requirements of ventilation volume and uniform exhaust, and to avoid accumulation of
refrigerant gas.
Leak detection equipment for flammable refrigerant shall be equipped, with relevant management system being established.
Whether the leak detection equipment is under available state shall be confirmed before maintenance.
Sufficient dedicated vacuum pumps of flammable refrigerant and refrigerant charging equipment shall be equipped, with
relevant management system for maintenance equipment being established. It shall be guaranteed that the maintenance
equipment can only be used for vacuumizing and charging of one type of flammable refrigerant, and mixed usage is not
allowed.
The master power switch shall be arranged outside the maintenance site, with protective (anti-explosive) device being
equipped.
Nitrogen cylinders, acetylene cylinders and oxygen cylinders shall be placed separately. The distance between the gas
cylinders above and the working area involved in open fire shall be at least 6m. The anti-backfire valve shall be installed for
the acetylene cylinders. The color of the acetylene cylinders and oxygen cylinders installed shall meet the international
requirements.
The warning sign of " No Fire" ,"No Smoking", or"Anti static"shall be arranged inside the maintenance area.
Fire control device suitable for electric appliance such as the dry powder extinguisher or carbon dioxide extinguisher shall
be equipped, and shall always be under the available state.
The ventilator and other electrical equipment at the maintenance site shall be relatively fixed, with standardized pipe
routing. Temporary wires and sockets at the maintenance site are not allowed.
The environment in which the refrigerant leakage is checked shall be free from potential ignition source. Leak detection with
halogen probes (or any other detector with open fire) shall be avoided.
For the system containing flammable refrigerant, leak detection may be realized with electronic leak detection equipment.
During leak detection, the environment in which the leak detection equipment is calibrated shall be free from refrigerant. It
shall be guaranteed that the leak detection equipment will not become potential ignition source, and is applicable to the
refrigerant to be detected. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed.
The fluid used for leak detection shall be applicable to most of the refrigerant. The use of chlorine-containing solvent shall
be avoided, to avoid chemical reaction between chlorine and refrigerant and corrosion to copper pipelines.
In case leakage is suspected, the open fire at the site shall be evacuated or be put out.
In case welding is required at the leakage position, all the refrigerants shall be recovered, or be isolated at a position far
from the leak point with a stop valve. Before and during welding, the whole system shall be purified with OFN.
The power supply should be cut off before the maintenance.
During product maintenance, favorable ventilation shall be guaranteed at the maintenance site, and the close of all the
doors/windows is not allowed.
Operation with open fire is not allowed, including welding and smoking. The use of phones is also not allowed. The user
shall be informed that cooking with open fire is not allowed.
During maintenance in a dry season, when the relative humidity is less than 40%, anti-static measures shall be taken,
including the wearing of cotton clothes and cotton gloves.
In case the leakage of flammable refrigerant is identified during maintenance, forced ventilation measures shall be taken
immediately, and the source of leak shall be plugged.
In case the product damaged must be maintained by disassembling the refrigeration system, the product must be delivered
to the maintenance point. Welding of refrigerant pipelines at the user's site is not allowed.
During maintenance, in case re-treatment is required due to lack of fittings, the air conditioner shall be reset.
The refrigeration system must be safely earthed in the whole course of maintenance.
For the door-to-door service with refrigerant cylinders, the refrigerant charged inside the cylinder cannot exceed the specified
value. The cylinder placed in vehicles or at the installation/maintenance site shall be fixed perpendicularly and be kept away
from heat sources, ignition source, source of radiation and electric appliance.
Maintenance Items
Maintenance Requirements
Maintenance of Electrical Components
Maintenance of Intrinsically Safe Elements
Removal and Vacuumizing
Welding
10
Before the refrigeration system is operated, the circulating system shall be cleaned with nitrogen. Afterwards, the outdoor
unit shall be vacuumized, the duration of which cannot be less than 30 minutes. Finally, 1.5~2.0MPa OFN shall be used for
nitrogen flushing (30 seconds~1 minute), to confirm the position requiring treatment. Maintenance of the refrigeration system
is only allowed after the residual gas of flammable refrigerant is removed.
During the use of refrigerant charging tools, cross contamination of different refrigerants shall be avoided. The total length
(including the refrigerant pipelines) shall be shortened as much as possible, to reduce the residual of refrigerant inside.
The cylinders of refrigerant shall be kept upright, and be fixed.
Before refrigerant charging, the refrigeration system shall be earthed.
The refrigerant charged shall be of the type and volume specified on the nameplate. Excessive charging is not allowed.
After maintenance of the refrigeration system, the system shall be sealed with a safe manner.
The maintenance in progress shall not damage or lower the original class of safety protection of the system.
Partial of the electrical component under maintenance shall be subject to inspection on refrigerant leakage with dedicated
leak detection equipment.
After the maintenance, the components with safety protection functions cannot be disassembled or removed.
During the maintenance of sealing elements, before opening the seal cover, the air conditioner shall be powered off first.
When power supply is required, continuous leak detection shall be carried out at the most dangerous position, to avoid potential
risks.
During maintenance of electrical components, the replacement of enclosures shall not affect the level of protection.
After maintenance, it shall be guaranteed that the sealing functions will not be damaged or the sealing materials will not
lose the function of preventing the entry of flammable gas due to aging. The substitute components shall meet the recommended
requirements of the air conditioner manufacturer.
The intrinsically safe element refers to the components working continuously inside flammable gas without any risks.
Before any maintenance, leak detection and inspection on earthing reliability of the air conditioner must be carried out, to
ensure no leakage and reliable earthing.
In case the allowable voltage and current limit may be surpassed during the service of the air conditioner, any inductance or
capacitance cannot be added in the circuit.
Only the elements appointed by the air conditioner manufacturer can be used as the parts and components replaced, or
otherwise a fire or explosion may be triggered in case of refrigerant leakage.
For the maintenance not involved in system pipelines, the system pipelines shall be well protected, to ensure that no
leakage will be caused due to maintenance.
After maintenance and before test run, the air conditioner must be subject to leak detection and inspection on earthing
reliability with leak detection equipment or leak detecting solution. It shall be guaranteed that the startup inspection is carried
out without leakage and under reliable earthing.
The maintenance or other operations of the refrigeration circuit shall be made as per conventional procedures. Moreover,
the flammability of refrigerant shall also be mainly considered. The following procedures shall be followed:
Refrigerant cleaning;
Pipeline purification with inert gas;
Vacuumizing;
Pipeline purification again with inert gas;
Pipeline cutting or welding. The refrigerant shall be recovered to a proper cylinder. The system shall be purged with OFN, to
ensure safety. The step above may need to be repeated for several times. Compressed air or oxygen cannot be used for
purging.
In the course of purging, OFN shall be charged inside the refrigeration system under vacuum state, to reach the operating
pressure. Afterwards, the OFN shall be discharged to the atmosphere. Finally, the system shall be vacuumized. The step above
shall be repeated until all the refrigerants in the system are cleared. The OFN charged for the last time shall be discharged to
the atmosphere. Afterwards, the system can be welded. The operation above is necessary in case of pipeline welding.
It shall be guaranteed that no alight fire source is around the outlet of the vacuum pump and the ventilation is favorable.
Favorable ventilation must be guaranteed in the maintenance area. After the maintenance machine is subject to the
vacuumizing above, the system refrigerant can be discharged on the outdoor unit side.
Before the outdoor unit is welded, it must be guaranteed that no refrigerant is inside the outdoor unit and the system
refrigerant has been discharged and cleared.
The refrigeration pipelines cannot be cut with a welding gun under any circumstance. The refrigeration pipelines must be
disassembled with a pipe cutter, and the disassembly must be carried out around a ventilation opening
Refrigerant Charging Procedures
Scrapping and Recovery
Recovery
11
The following requirements are added as the supplementation of conventional procedures:
During the use of refrigerant charging tools, cross contamination of different refrigerants shall be avoided. The total length
(including the refrigerant pipelines) shall be shortened as much as possible, to reduce the residual of refrigerant inside;
The cylinders of refrigerant shall be kept upright;
Before refrigerant charging, the refrigeration system shall be earthed;
A label must be pasted on the refrigeration system after refrigerant charging;
Excessive charging is not allowed; the refrigerant shall be charged slowly;
In case system leakage is identified, refrigerant charging is not allowed unless the leak point is repaired;
During refrigerant charging, the charging amount shall be measured with an electronic scale or a spring scale. The connecting
hose between the refrigerant cylinder and the charging equipment shall be relaxed appropriately, to avoid impact on the
measuring accuracy due to stress.
Requirements on storage site of refrigerant
The cylinder of refrigerant shall be placed in a -10~50 environment with favorable ventilation, and warning labels shall be
pasted;
The maintenance tool in contact with the refrigerant shall be stored and used separately, and the maintenance tool of
different refrigerants cannot be mixed.
Scrapping
Before scrapping, the technician shall be completely familiar with the equipment and all its features. The safe recovery of
refrigerant is recommended. In case the refrigerant recovered needs to be reused, before which the sample of refrigerant and
oil shall be analyzed.
(1) The equipment and operation shall be well known;
(2) Power supply shall be switched off;
(3) The followings shall be guaranteed before scrapping:
The mechanical equipment shall be convenient for operation on the cylinder of refrigerant (if necessary);
All personal protective equipment is available and being used correctly;
The whole course of recovery shall be guided by qualified personnel;
The recovery equipment and cylinders shall be in line with corresponding standards.
(4) The refrigeration system shall be vacuumized if possible;
(5) In case the vacuum state cannot be reached, vacuumizing shall be carried out from numerous positions, to pump the
refrigerant in each part of the system out;
(6) It shall be guaranteed that the capacity of cylinders is sufficient before recovery;
(7) The recovery equipment shall be started and operated as per the operation instructions of the manufacturer;
(8) The cylinder cannot be charged too full. (The refrigerant charged cannot exceed 80% of the capacity of cylinders)
(9) The maximum operating pressure of cylinders cannot be surpassed even only lasting for a short term;
(10) After refrigerant recovery is completed, the cylinder and equipment must be evacuated rapidly, and all the stop valves on
the equipment must be closed;
(11) Before purification and tests, the refrigerant recovered cannot be charged into another refrigeration system.
Note:
The air conditioner shall be marked (with dates and signature) after being scrapped and the refrigerant is discharged.
It shall be guaranteed that the sign on the air conditioner can reflect the flammable refrigerant charged inside.
During maintenance or scrapping, the refrigerant inside the refrigeration system needs to be cleared. It is recommended
that the refrigerant be cleared thoroughly.
The refrigerant can only be charged into a dedicated cylinder, the capacity of which shall match with the refrigerant amount
charged in the whole refrigeration system. All cylinders to be used are designated for the recovered refrigerant and labeled for
that refrigerant (Dedicated Cylinder for Refrigerant Recovery). The cylinders shall be equipped with pressure relief valves and
stop valves under favorable state. The empty cylinder shall be vacuumized before usage and be kept under normal temperature.
The recovery equipment shall always be under favorable working state, and be equipped with operation instructions, to
facilitate information search. The recovery equipment shall be applicable to the recovery of flammable refrigerant. Moreover,
weighing apparatus under available state with measurement certificates shall be equipped. In addition, removable attachment
joints free from leakage shall be used as the hose, and shall always be under favorable state. Whether the recovery equipment
is under favorable state and is properly maintained and whether all the electrical components are sealed shall be checked
before usage, to avoid fire or explosion in case of refrigerant leakage. If you have any question, please consult the manufacturer.
The refrigerant recovered shall be delivered back to the manufacturer in appropriate cylinders, with transporting instructions
being attached. Mixing of refrigerant in recovery equipment (especially the cylinders) is not allowed.
During transporting, the space in which the flammable refrigerant air conditioners are loaded cannot be sealed. Anti-
static measures shall be taken for the transporting vehicles. Meanwhile, during the transporting, loading and unloading of air
conditioners, necessary protective measures shall be taken, to protect the air conditioner from being damaged.
During removal of the compressor or clearing of the compressor oil, it shall be guaranteed that the compressor is
vacuumized to a proper level, to ensure no residual flammable refrigerant is left inside the lubricating oil. The vacuumizing
shall be completed before the compressor is delivered back to the manufacturer. The vacuumizing can only be accelerated by
heating the compressor housing through electrical heating. Safety shall be guaranteed when the oil is discharged from the
system.disassembled with a pipe cutter, and the disassembly must be carried out around a ventilation opening
12
Be sure to conform with the following important Safety Precautions.
If any abnormal phenomena is found
(e. g.smell of firing), please open the
window and well ventilated the room
immediately, then cut off the power supply immediately,
and contact the dealer to find out the handling method.
In such case, to continue using the conditioner will damage
the conditioner, and may cause electrical shock, fire, or
explosion hazard.
Don't dismantle the outlet of the
outdoor unit.
The exposure of fan is very dangerous
which may harm human beings.
After a long time use of air-conditioner,
the base should be checked for any
damages.
If the damaged base is not repaired, the
unit may fall down and cause accidents.
When need maintenance and repairment,
call dealer to handle it.
Incorrect maintenance and repairment
may cause water leak, electrical shock,
fire, and explosion hazard.
Air-conditioner can't be installed in the environment with
inflammable gases because the inflammable gases near
air-conditioner may cause fire and explosion hazard.
Please let the dealer be responsible for installing the
conditioner. Incorrect installation may cause water leak,
electrical shock, fire, and explosion hazard.
Connect earthing wire.
Earthing wire should not be connected to the gas
pipe, water pipe, lightning rod or phone line,
incorrect earthing may cause shock.
Use drain pipe correctly to ensure efficient drainage.
Incorrect pipe use may cause water leaking.
Installed explosion-proof electrical-leaking circuit breaker.
It easily cause electrical shock without circuit breaker.
Call the dealer to take measures to prevent the refrigerant
from leaking.
If conditioner is installed in a small room, be sure to take
every measure in order to prevent suffocation and explosion
accident even in case of refrigerant leakage.
When conditioner is installed or reinstalled, the dealer should
be responsible for them.
Incorrect installation may cause water leaking, electrical
shock, fire, and explosion hazard.
No goods or nobody is permitted to
placed on or stand on outdoor unit.The
falling of goods and people may cause
accidents.
Don't operate the air-conditioner with
damp hands.Otherwise it will be shocked.
Only use correctly-typed fuse.
May not use wire or any other materials
replacing fuse, otherwise it may cause
faults or fire accidents.
Earthing
switch off
WARNING
WARNING
After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the
use and cleaning of the unit according to the Operation Manual.
Carefully read the following information in order to operate the air conditioner correctly.
The following safety symbols are used throughout this manual:
:Indicates an action that must be avoided.
:Indicates that important instructions must be followed.
:Indicates a part which must be grounded.
:Beware of electric shock (This symbol is displayed on the main unit label.)
Below are listed three kinds of Safety Precautions and Suggestions.
Incorrect operations may result in severe consequences of death or serious injuries.
Incorrect operations may result in injuries or machine damages; in some cases may cause serious consequences.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
WARNING
CAUTION
!
Have the unit professionally installed.
Improper installation by an unqualified person may result
in water leak, electric shock, fire, or explosion.
Be sure to carefully follow each step in this handbook when
installing the unit.
Improper installation may result in water leak, electric shock,
smoke or fire.
Have all electrical work performed by a licensed electrician
according to the local regulations and the instructions given
in this manual. Secure a circuit designated exclusively to
the unit.
Improper installation or a lack of circuit capacity may cause
the unit to malfunction or present a risk of electric shock,
smoke,and fire.
Place the unit on a stable, level surface that withstands the
weight of the unit to prevent the unit from tipping over or
falling causing injury as a result.
Only use specified cables for wiring. Securely connect each
cable, and make sure that the cables are not straining the
terminals.
Cables not connected securely and properly may generate
heat and cause fire and explosion.
Take necessary safety measures against typhoons and
earthquakes to prevent the unit from falling over.
Do not make any changes or modifications to the unit. In
case of problems, consult the dealer.
If repairs are not made properly, the unit may leak water
and present a risk of electric shock, or it may produce smoke
or cause fire and explosion.
Securely attach the terminal cover(panel) on the unit.
If installed improperly, dust and/or water may enter the unit
and present a risk of electric shock, smoke, fire, or explosion.
Only use refrigerant R32 as indicated on the unit when
installing or relocating the unit.
The use of any other refrigerant or an introduction of air into
the unit circuit may cause the unit to run an abnormal cycle
and abnormal cycle and cause the unit to burst.
In the event of a refrigerant gas leak, provide adequate
ventilation to the room.
If leaked refrigerant gas is exposed to a heat source, noxious
gases, fire or explosion will be caused.
Do not touch the fins on the heat exchanger with bare hands,
for they are sharp and dangerous.
Do not try to defeat the safety features of the devices, and
do not change the settings.
Defeating the safety features on the unit such as the pressure
switch and temperature switch or using parts other than the
dealer or specialist may result in fire or explosion.
When installing the unit in a small room, safeguard against
hypoxia that results from leaked refrigerant reaching the
threshold level.
Consult the dealer for necessary measures to take.
When relocating the air conditioner, consult the dealer or
a specialist.
Improper installation may result in water leak, electric shock,
or fire.
After completing the service work, check for a refrigerant
gas leak.
If leaked gas refrigerant is exposed to a heat source such
as fan heater,stove,and electric grill, noxious gases may
form.
Only use specified parts.
Have the unit professionally installed. Improper installation
may cause water leak, electric shock,smoke, fire, explosion.
WARNING
WARNING
13
14
Precautions for Handling Units for Use with R32
Do not use the existing refrigerant piping
The old refrigerant and refrigerator oil in the existing piping
contain a large amount of chlorine, which will cause the
refrigerator oil in the new unit to deteriorate.
R32 is a high-pressure refrigerant, and the use of the
existing piping may result in bursting.
Keep the inner and outer surfaces of the pipes clean and
free of contaminants such as sulfur, oxides, dust/dirt shaving
particles,oils,and moisture.
Contaminants inside the refrigerant piping will cause the
refrigerant oil to deteriorate.
Use a vacuum pump with a reverse-flow check valve.
If other types of valves are used, the vacuum pump oil will
flow back into the refrigerant cycle and cause the refrigerator
oil to deteriorate.
Do not use the following tools that have been used with the
conventional refrigerants. Prepare tools that are for exclusive
use with R32.
(Gauge manifold, charging hose, gas leak detector,
reverse-flow check valve, refrigerant charge base,vacuum
gauge, and refrigerant recovery equipment.)
If refrigerant and/or refrigerant oil left on these tools are
mixed in with R32, or if water is mixed with R32, it will
cause the refrigerant to deteriorate.
Since R32 does not contain chlorine, gas-leak detectors
for conventional refrigerators will not work.
Store the piping to be used during installation indoors, and
keep both ends of the piping sealed until immediately before
brazing.(keep elbows and other joints wrapped in plastic.)
If dust, dirt, or water enters the refrigerant cycle, it may
cause the oil in the unit to deteriorate or may cause the
compressor to malfunction.
A large amount of mineral oil will cause the refrigerating
machine oil to deteriorate.
Use a small amount of ester oil, ether oil, or alkylbenzene
to coat flares and flange connections.
Use liquid refrigerant to charge the system.
Charge the unit with gas refrigerant will cause the refrigerant
in the cylinder to change its composition and will lead to
a drop in performance
Do not use a charging cylinder.
The use of charging cylinder will change the composition
of the refrigerant and lead to power loss.
Exercise special care when handling the tools.
An introduction of foreign objects such as dust, dirt or
water into the refrigerant cycle will cause the refrigerating
machine oil to deteriorate.
Only use R32 refrigerant.
The use of refrigerants containing chlorine(i.e. R22) will
cause the refrigerant to deteriorate.
Before Installing the Unit
Do not install the unit in a place where there is a possibility
of flammable gas leak.
Leaked gas accumulated around the unit may start a fire
or explosion.
Do not use the unit to preserve food, animals, plants, artifacts,
or for other special purposes.
The unit is not designed to provide adepuate conditions
to preserve the quality of these items.
Do not use the unit in an unusual environment
The use of the unit in the presence of a large amount of
oil, steam, acid, alkaline solvents or special types of sprays
may lead to a remarkable drop in performance and/or
malfunction and presents a risk of electric shock, smoke,
fire, or explosion.
The presence of organic solvents, corroded gas (such as
ammonia,sulfur compounds,and acid may cause gas or
water leak.)
When installing the unit in a hospital, take necessary measures
against noise.
High-frequency medical equipment may interfere with the
normal operation of the air conditioning unit or the air
conditioning unit may interfere with the normal operation
of the medical equipment
When humidity level exceeds 80% or when the drainage
system is clogged, indoor units may drip water.
Installation of a centralized drainage system for the outdoor
unit may also need to be considered to prevent water drips
from the outdoor units.
Do not place the unit on or over things that may not get wet.
Caution
Caution
Caution
Before Installing (Relocating) the Unit or Performing Electric Work
Ground the unit.
Do not connect the grounding on the unit to gas pipes,water
pipes, lightning rods, or the grounding terminals of
telephones. Improper grounding presents a risk of electric
shock, smoke, fire, explosion, or the noise caused by
improper grounding may cause the unit to malfunction.
Before the Test Run
Do not operate switches with wet hands to avoid electric
shock. Allow for at least five minutes before turning off the unit,
otherwise the unit may leak water or experience other
problems.
Do not turn off the power immediately after stopping the unit.
If the wires are too taut, they may break or generate heat
and/or smoke and cause fire or explosion.
Make sure the wires are not subject to tension.
Install a breaker for current leakage at the power source
to avoid the risk of electric shock.
Without a breaker for current leakage, there is a risk of
electric shock, smoke or fire.
Use breakers and fuses (electrical current breaker, remote
switch<switch+Type-B fuse>,molded case circuit breaker)
with a proper current capacity.
The use of large-capacity fuses, steel wire, or copper wire
may damage the unit or cause smoke or fire.
When installing draining pipes, follow the instructions in the
manual, and make sure that they properly drain water so as
to avoid dew condensation.
If not installed properly, they may cause water leaks and
damage the furnishings.
Do not spray water on the air conditioners or immerse the
air conditioners in water.
Water on the unit presents a risk of electric shock.
Periodically check the platform on which is placed for damage
to prevent the unit from falling.
If the unit is left on a damaged plarform, it may topple over,
causing injury.
Things such as nails may be included in the package.
Dispose of them properly to prevent injury.
Plastic bags present a choking hazard to children. Tear
up the plastic bags before disposing of them to prevent
accidents.
Properly dispose of the packing materials.
Do not touch the refrigerant pipes with bare hands during
and immediately after operation.
Depending on the state of the refrigerant in the system,
certain parts of the unit such as the pipes and compressor
may become very cold or hot and may subject the person
to frost bites or burning.
Do not operated the unit without panels and safety guards
in their proper places.
They are there to keep the users from injury for accidentally
touching rotating, high-tempreture or high-voltage parts. Dust particles in the air may clog the system and cause
malfunction.
Do not operate the unit without air filters.
Caution
Caution
When moving, to disassemble and re-install the air conditioning, please contact your dealer for technical support.
In the composition material of air conditioning, the content of lead, mercury, hexavalent chromium, polybrominated biphenyls and
polybrominated diphenyl ethers are not more than 0.1% (mass fraction) and cadmium is not more than 0.01% (mass fraction).
Please recycle the refrigerant before scrapping, moving, setting and repairing the air conditioning; for the air conditioning scrapping,
should be dealt with by the qualified enterprises.
15
Move and scrap the air conditioning
Read Before Installation
Tools/Materials Use Notes
Gauge Manifold Evacuating,refrigerant charging 5.09MPa on the High-pressure side.
Charging Hose Evacuating, refrigerant charging Hose diameter larger than the concentional ones.
Refrigerant Recovery Equipment Refrigerant recovery
Refrigerant Cylinder Refrigerant charging Write down the refrigerant type. Pink in color at the top of the cylinder.
Refrigerant Cylinder Charging Port Refrigerant charging Hose diameter larger than the conventional ones.
Flare Nut Connecting the unit to piping Use Type-2 Flare nuts.
Tools/Materials Use Notes
Gas leak detector Detection of gas leaks The ones for HFC type refrigerant may be used.
Vacuum Pump Vacuum drying May be used if a reverse flow check adaptor is attached.
Refrigerant Recovery Equipment Recovery of refrigerant May be used if designed for use with R32
Flare Tool Flare machining of piping Chages have been made in the flare machining dimension.Refer to the next page.
Tools/Materials Use Notes
Vacuum Pump with a Check Valve Vacuum drying
Bender Bending pipes
Pipe Cutter Cutting pipes
Torque Wrench Tightening flare nuts Only 12.70 (1/2'') and 15.88(5/8'') have a larger flare machining dimension.
Welder and Nitrogen Cylinder Welding pipes
Refrigerant Charging Meter Refrigerant charging
Vacuum Gauze Checking vacuum degree
Tools/Materials Use Notes
Charging Cylinder Refrigerant Charging Must not be used with R32-type units.
CAUTION
Items to Be Checked
(1) Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type: R32
(2) Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the
refrigerant cycle.
(3) Be sure to carefully read the safety precautions at the beginning of this document.
(4) If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas hydrofluoric acid may
form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to deteriorate.
Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Necessary tools for use with R32 (Adaptability of tools that are for use with R407C).
1. To be used exclusively with R32 ( Not to be used if used with R22 or R407C )
2. Tools and materials that may be used with R32 with some restrictions
3. Tools and materials that are used with R410A that can also be used with R32
4. Tool and materials that must not used with R32
Tools for R32 must be handled with special care, and keep moisture and dust from entering the cycle.
16
17
Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment's air tightness, taking
temperature variations into account.
When investigating leakage locations using a refrigerant, be sure to use R32.
Insure that R32 is in a liquid state when charging.
Use of oxygen as the pressurized gas may cause an explosion.
Charging with R32 gas will lead the composition of the remaining refrigerant in the cylinder to change and then this
refrigerant can not be used.
R32 leakage Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 or R410A cannot detect R32
leakage.
Halide torch
NO
R22 or R407C leakage detector
NO
Items to be strictly observed :
Reasons:
Because R32 is a simulated azeotropic refrigerant, it can be handled in almost the same manner as a refrigerant such as
R410A. Howerver, if the refrigerant is removed in the vapor phase, the composition of the refrigerant in the cylinder will
somewhat change.
Remove the refrigerant in the liquid phase. Additional refrigerant may be added in case of a refrigerant leak.
Characteristics of the Conventional and the New Refrigerants
Required accuracy of the vacuum gauge
Use a vacuum gauge that can measure up to 650Pa. Do not use a general gauge manifold since it cannot measure a
vacuum of 650Pa.
Vacuuming
Vacuum pump with check valve
A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant
circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual
vacuum pump afterwards.
Standard degree of vacuum for the vacuum pump
Use a pump which reaches 65Pa or below after 5 minutes of operation.
In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the
vacuum pump is not properly maintained, the degree of vacuum may be too low.
Evacuating time
Evacuate the equipment for 1 hour after 650Pa has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
Operating procedure when the vacuum pump is stopped
In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the
charge hose to drawn in air before stopping operation.The same operating procedure should be used when using a
vacuum pump with a check valve.
1.
2.
3.
4.
5.
1.
2.
3.
1.
2.
R32 is a pseudo-azeotropic refrigerant (boiling point R32= -52 C, R125= -49 C) and can roughly be handled in the same
way as R410A; however, be sure to fill the refrigerant from the liquid side, for doing so from the gas side will somewhat
change the composition of the refrigerant in the cylinder.
Charging Refrigerant
R must be in a liquid state when charging.
Reasons:
Note
In the case of a cylinder with a syphon, liquid R32 is charged without turning the cylinder up side down. Check the type
of cylinder before charging.
When refrigerant leaks, additional refrigerant may be charged. (Add the refrigerant from the liquid side)
Remedies to be taken in case of a refrigerant leak
Accessories supplied with the outdoor unit:
Procedure for Selecting the Location
NOTE:
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise, will not cause a nuisance to the
neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient space for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
Locate the unit so that the noise and the discharged hot air will not annoy the neighbors.
7) Install units, power cords and inter-unit cables at least 3048mm away from television and radio sets. This is to prevent
interference to images and sounds. (Noises may be heard even if they are more than 3048mm away depending on radio
wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
10) On a flat surface that does not collect rain water.
11) Away from strong wind.
12) Away from direct exposure to rain or snow.
13) Away from sea breeze.
14) Away from inflammable materials.
15) Away from high temperature or open flames.
1) Cannot be installed hanging from ceiling or stacked.
2) If installing on a high place such as a roof, with a fence or guard rail around it.
3) If there is a potential for accumulated snow to block the air inlet or heat exchanger, install the unit on a higher base.
4) R32 refrigerant is an unsafe, nontoxic and flammable refrigerant. However, if there is a concern about a dangerous
level of refrigerant concentration in the case of refrigerant leakage, add extra ventilation.
5) Avoid installing the outdoor unit where corrosive gases, such as sulfur oxides, ammonia, and sulfurous gas, are
produced. If unavoidable, consult with an installation specialist about using a corrosion-proof or anti-rust additive to protect
the unit coils.
18
Accessories
Drainage elbow 2
3
No.
1
2
Quantity
4
Name of parts
Rubber cushion
Clap
Drawing
3
5U125S2PN1FA
4
4
3
6) For seacoast applications, block the unit from direct exposure to sea breeze by installing the unit behind a structure
(such as a building) or a protective wall that is 1.5 times higher than the unit, leaving 700 mm of space between the wall
and unit for air circulation.Consult an installation expert about taking anti-corrosion measures, such as removing salinity
on the heat exchanger and applying a rust inhibitor more frequently than once a year.
ODU
ODU
ODU
ODU
Sea breeze
Sea breeze Sea breeze
Sea
Sea Sea
Protection walls
ODU
7) Set the unit on mounting brackets or pad. To avoid the adverse effects of snow, ice and defrosting issues, install the
unit on heat pump risers to ensure a sufficient height from the ground. In all cases, refer to local code for correct riser
height.
Make sure the outdoor unit is installed level and is stable.
Install snow protection hood as necessary.
19
Procedure for Selecting the Location
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI