2
Field supplied pipe and fittings are required to complete the installation. The combustion air and vent pipe
fittings must conform to American National Standards Institute (ANSI) and American Society for Testing
and Materials (ASTM) standards D1785 (schedule-40 PVC), D2665 (PVC-DWV), D2441 (SDR-21 and
SDR 26 PVC), D2661 (ABS DWV), or F628 (schedule-40 ABS). Pipe cement and primer must conform to
ASTM standards D2564 (PVC) or D2235 (ABS).
In Canada, construct all combustion air inlet and exhaust vent pipes for this unit with CSA or ULC certified
schedule-40 PVC, PVC-DWV pipe and pipe cement.
A. ROOF TERMINATION
1. Determine the best location for the termination kit.
NOTE: A roof termination is less susceptible to
damage. It has reduced chances for intake
contaminants and less visible vent vapors.
2. Cut a hole in the roof 4” in diameter for 2”
concentric vent, or 5” in diameter for 3” concentric
vent kit.
3. Partially assemble concentric vent termination kit.
a. Cement Y concentric fitting to larger
diameter kit pipe (see Fig. 1).
b. Cement rain cap to smaller diameter kit
pipe (see Fig. 1).
Do not operate the appliance with rain cap removed. Re-circulation of combustion products may occur.
Water may also collect inside larger combustion air pipe and flow to burner enclosure. Operating
appliance without rain cap could result in product damage, improper operation, personal injury, or death.
4. Install Y concentric fitting and pipe assembly
through the hole in the roof and field supplied
boot/flashing. NOTE: Do not allow insulation or
other material to accumulate inside the pipe
assembly when installing through the hole.
5. Secure assembly to roof structure as shown in
Fig. 4 using field supplied metal strapping or
equivalent support material.
NOTE: Ensure termination height is above the roof
surface or anticipated snow level (1’ in USA or 1 ½’
in Canada) as shown in Fig. 3.
NOTE: If assembly is too short to meet height
requirements, the two pipes supplied in the kit may
be replaced by using same diameter, field supplied
SDR-26 PVC (D2241) pipe. Do not extend
dimension D more than 60” (See Fig. 2.) DO NOT
USE COUPLINGS TO EXTEND PIPE.
NOTE: When shortening the length of the concentric vent, the inner pipe is longer than the outer pipe.
Make sure you cut the same amount from each pipe. DO NOT make the pipes equal in length.
Figure 1 – Kit Components
Figure 2 – Concentric Vent Dimensional Drawing