Regal G500 Series Temperature Control Unit User manual

Type
User manual
I.O.M. #149 updated : 04/24/2020
INSTRUCTION MANUAL • INSTALLATION • OPERATION • MAINTENANCE
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Service Department fax: 317-885-8683
www.AdvantageEngineering.com
Model:
Serial Number :
TEMPERATURE CONTROLLER
For Units with the G500 Series Control Instrument
INSTRUCTION MANUAL
Regal RK with
G500 Series Instrument
COVERING
INSTALLATION
OPERATION
MAINTENANCE
ADVANTAGE ENGINEERING, INC. 525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277 Service Department fax: 317-885-8683
www.AdvantageEngineering.com E-mail: [email protected]
TEMPERATURE CONTROLLER
Temperature Control Unit : Regal with G500 Series Instrument
Page: 4
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
TABLE OF CONTENTS
1.0 GENERAL 7
1.1 Receiving Instructions 8
1.2 Introduction 8
1.3 Safety 8
1.4 Components 10
2.0 INSTALLATION 13
2.1 General 14
2.2 To and from process connections 14
2.3 Water supply connection 15
2.4 Drain connection 15
2.5 Electrical connection 17
3.0 START UP SEQUENCE 19
3.1 General 20
3.2 System Fill / Operations 20
3.3 Instrument : Quick Start 24
3.4 Instrument : Basic Navigation 25
3.5 Instrument : Operating Screens 26
3.6 Instrument : Fault Screens 27
3.7 Instrument : Main Menu 28
3.8 Instrument : Setpoints Menu 28
3.9 Instrument : Utilities Menu 29
3.10 Instrument : Network Menu 30
3.11 Instrument : Options Menu 32
3.12 Instrument : Machine Menu 32
3.13 Shut Down / Disconnect 33
4.0 TROUBLESHOOTING 35
4.1 Unit will not start (Display is not Illuminated) 36
4.2 Unit will not start (Display is Illuminated) 36
4.3 Unit Stops 36
4.4 Unit Overheats 37
4.5 Unit Underheats 38
4.6 Pressure Relief Valve Leaks 38
5.0 MAINTENANCE 41
5.1 Preventative Maintenance 42
5.1 Pump Seal Replacement 43
5.2 Heater Replacement 45
5.3 Cooling Valve Service 46
5.4 Pressure Switch Service 47
5.5 Electronic Instrument Repair Policy And Procedure 48
Temperature Control Unit : Regal with G500 Series Instrument
Page: 5
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
6.0 COMPONENTS 49
6.1 Mechanical system 50
6.2 Electrical system 50
7.0 RELATED DRAWINGS 53
7.1 Physical 12 kW Heaters & 1 - 3 HP Pumps 54
7.2 Physical 16-24 kW Heaters & 1 - 3 HP Pumps 55
7.3 Physical 36-48 kW Heaters & 5 - 7.5 HP Pumps 56
7.4 Circuit Schematic with Cooling Circuit 57
8.0 APPENDIX 59
8.1 Model # And Suffix Coding 60
8.2 Water Cooled Process Pumps 61
8.3 Mold Purge 62
Page: 6
THIS PAGE INTENTIONALLY BLANK
Temperature Control Unit : Regal with G500 Series Instrument
Page: 7
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
1.0 GENERAL
1.1 Receiving Instructions
1.2 Introduction
1.3 Safety
1.4 Components
Temperature Control Unit : Regal with G500 Series Instrument
Page: 8
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
1.1 RECEIVING INSTRUCTIONS
A. Temperature control units are generally shipped skid mounted, boxed and wrapped in
plastic prior to shipment.
B. Unbox the unit before accepting delivery. Check for visible damage and document any
evident damage on the delivery receipt or refuse the shipment. Shipping damage is the
responsibility of the carrier.
C. In order to expedite payment for damages, should they occur, follow proper procedures
and keep detailed records. Take photographs of any suspected damage.
1.2 INTRODUCTION
A. This manual covers temperature control units from 12 to 48 kW of heating capacity
using the G500 Series microprocessor control instrument. The standard uid operating
temperature range for this temperature control unit is 100°F to 500°F. Consult the factory
if you have questions about the operating range of your temperature control unit.
B. The intent of this manual is to serve as a guide in the installation, operation and
maintenance of your temperature control unit. Improper installation can lead to equipment
damage and poor performance. Failure to follow the installation, operation and
maintenance instructions may result in damage to the unit that is not covered under the
limited warranty. This manual is for standard products. The information contained in this
manual is intended to be general in nature. The information is typical only and may not
represent the actual unit purchased.
C. When calling for assistance from the Manufacturer’s Service Department, it is important
to know the model and serial number of the particular unit. The model number includes
critical unit information which is helpful when troubleshooting operating difculties. The
serial number allows the service team to locate manufacturing and testing records which
can have additional information relating to a particular unit.
1.3 SAFETY
A. It is important to become thoroughly familiar with this manual and the operating
characteristics of the unit.
B. It is the owner’s responsibility to assure proper operator training, installation, operation,
and maintenance of the unit.
C. Observe all warning and safety placards applied to the unit. Failure to observe all
warnings can result in serious injury or death to the operator and severe mechanical
damage to the unit.
WARNING: This equipment contains hazardous voltages that can cause severe injury or
death. Disconnect and lock out incoming power before installing or servicing the equipment.
Temperature Control Unit : Regal with G500 Series Instrument
Page: 9
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
D. Observe all safety precautions during installation, startup and service of this equipment
due to the presence of high voltage. Only qualied personnel should install, startup and
service this equipment.
E. When working on this equipment, observe precautions in literature and on tags, stickers
and labels located on the equipment. Wear work gloves and safety glasses.
F. Before installing and operating the unit, be aware of and follow any local laws and codes
that apply to the installation.
G. Samples of Warning Labels applied to typical temperature control units.
1. Alerts users to the danger of high voltage.
2. Alerts the user to possible explosive danger.
3. Alerts the user to a hot surface danger due to high operating temperatures.
CAUTION
WARNING
J5318-BF
Temperature Control Unit : Regal with G500 Series Instrument
Page: 10
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
1.4 COMPONENTS
WARNING: Improper fluid quality will void unit warranty.
From Process Valve and Connection
Process Pump
Fluid Drain Valve
Water Drain Connection
Water Supply Connection
To Process Valve and Connection
Sight Glass
Heat Cylinder
Expansion Tank
Typical unit with lift-off cabinetry.
Temperature Control Unit : Regal with G500 Series Instrument
Page: 11
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
From Process Valve and Connection
Process Pump
Fluid Drain Valve
Water Drain Connection
Water Supply Connection
To Process Valve and Connection
Sight Glass
Heat Cylinder
Expansion Tank
Typical unit with clam shell cabinetry.
Page: 12
THIS PAGE INTENTIONALLY BLANK
Temperature Control Unit : Regal with G500 Series Instrument
Page: 13
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
2.0 INSTALLATION
2.1 General
2.2 To and From Process Connections
2.3 Water Supply Connection
2.4 Drain Connection
2.5 Electrical Connection
Temperature Control Unit : Regal with G500 Series Instrument
Page: 14
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
2.1 GENERAL
A. Care should be taken to use materials (hose, rigid piping, valves or filters) rated for
the temperature and pressure duty of your unit. Most units have a maximum operating
temperature of 500°F or less and a maximum pressure of 75 PSI. The unit is most
efficient when full size plumbing is run from the unit connections to and from the process.
If necessary, reduce the plumbing size at your process, not at the unit.
B. Be certain all process piping materials have the equivalent or larger diameter of the
particular process connection.
2.2 TO AND FROM PROCESS CONNECTIONS
A. Connect the unit’s To Process port to the Fluid In port on the process manifold.
B. Connect the unit’s From Process port to the Fluid Out port on the process manifold.
C. Please note: Process piping circuitry should be designed to avoid an excessive use of
elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid tight twists
or curls and excessive lengths.
.
2.3 WATER SUPPLY CONNECTION
A. Connect the unit’s Water Supply port to the plant’s city water, well water, tower water or
chilled water supply.
B. If unit is a Heating Only Unit, the water supply must be a minimum of 1/2 GPM at a
maximum temperature of 100°F for efcient component cooling. If the unit is a Heating
and Cooling Unit including a heat exchanger, the water supply must be a minimum of
3 GPM at a minimum temperature of 100°F. High water ow may be required for your
application depending on the process cooling requirement.
To process connection:
Connect to “fluid in” on process manifold
Compressed air connection:
Connect to plant compressed air source
when purging fluid from mold to unit for
storage
From process
connection:
Connect to “fluid out” on
process manifold
Fluid fill port:
Use when manually
adding fluid to the unit
Fluid fill/drain connection:
Use when adding fluid from a
pressurized source or when draining
majority of fluid volume from unit
Water drain connection:
Connect to one of the following:
• Plant’s open water drain
• Tower water system return
• Chilled water system return
Water supply connection:
Connect to one of the following:
• Plant’s city water source
• Well water source
• Tower water supply
• Chilled water supply
Temperature Control Unit : Regal with G500 Series Instrument
Page: 15
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
C. The factory recommend minimum operating water supply pressure requirement is a
minimum of 20 PSI. To protect the unit from operating without adequate supply water, a
water pressure switch is plumbed into the supply manifold. If the supply pressure is not
sufcient, the pressure switch will prevent unit operations.
D. On all units, cooling water circulates to the supply manifold, through the pump adapter
cooling jacket, and is then rejected to the drain manifold. This action maintains proper
pump seal cavity temperatures.
E. On units with the installed cooling option, a tube and shell heat exchanger for process
uid cooling is supplied and mounted to the expansion tank.
1. The purpose of the heat exchanger is to cool the process uid. Cooling water
from plant water supply circulates through the “tube” side of the heat exchanger.
The process uid circulates through the “shell” side. Cooling water ow is
controlled by the solenoid valve.
2. A 1/2” ball valve is placed in the heat exchanger water supply line after the
solenoid valve. The ball valve should be open during operations from 100°F to
200°F. During operations with temperatures over 200°F, this valve should be
closed. In such cases, the necessary cooling water is proportioned to the heat
exchanger through the small capillary line, which some water “steams off” to cool
the process uid. The steam and water mixture is then rejected to drain.
2.4 WATER DRAIN CONNECTION:
A. Connect the unit’s Water Drain port to one of the following, determined by the water
supply source:
1. Open water drain for well or city water supply.
2. Tower water system return for tower system water supply.
3. Chilled water system return for chilled water system supply.
B. The factory recommends a minimum of 20 psi pressure differential between the water
supply and water drain line for proper cooling.
1. For units equipped with the cooling feature, the amount of cooling provided by
the unit depends on:
a. Cooling heat exchanger size.
b. The cooling valve size
c. The pressure differential across the valve
d. The temperature difference between the unit set point and the cooling
water temperature
2. Consult factory when selecting the correct cooling valve for your application.
Temperature Control Unit : Regal with G500 Series Instrument
Page: 16
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
3. In general, the cooling capacity of the standard 3.5 sq ft heat exchanger is 6,000
Bth/hr (2 kW) for every 20°F difference between the cooling water temperature
and the uid temperature.
C. CAUTION: The unit must never be operated with a closed drain line valve. A closed
drain line valve prevents adequate system cooling and will lead to unit overheating.
Overheating of the unit may lead to unit damage and/or serious personal injury.
2.5 ELECTRICAL CONNECTION
A. Standard Models
1. Electrical power supply requirements for standard units are identied on the
equipment data tag. Verify that available voltage supply is the same as the unit’s
voltage requirements.
WARNING: DO NOT CONNECT THE UNIT TO A VOLTAGE SUPPLY SOURCE
NOT EQUAL TO THE UNIT’S VOLTAGE REQUIREMENTS AS SPECIFIED ON
THE UNIT’S DATA PLATE.
Use of incorrect voltage will void the unit’s warranty and cause a signicant
hazard that may result in serious personal injury and/or unit damage.
2. For standard units with 12 kW heaters and up to 3 horsepower pumps, a four
conductor cable, 10 foot in length, is provided for connection to an operator
supplied fused disconnect.
3. For units with 16 kW to 48 kW heaters, the owner must provide a four conductor
power cable and the fused disconnect.
4. The owner supplied fused disconnect must be sized and installed according to
the unit’s power supply requirements and local electrical codes.
B. Models With Factory Included Disconnect Switch and Other Custom Features
1. Some units may be customized and include a factory supplied power disconnect
switch and/or higher specication electrical enclosure. Electrical power supply
requirements are identied on the equipment data tag. Verify that available
voltage supply is the same as the unit’s voltage requirements.
WARNING: Never operate the Temperature Control Unit with a closed water drain.
WARNING: Do not connect the unit to a voltage supply not equal to the unit’s voltage
requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s
warranty and cause a significant hazard that may result in serious personal injury and unit
damage.
Temperature Control Unit : Regal with G500 Series Instrument
Page: 17
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
WARNING: DO NOT connect the unit to a voltage supply source not equal
to the unit’s voltage requirements as specied on the unit’s data plate. Use
of incorrect voltage will void the unit’s warranty and cause a signicant
hazard that may result in damage to the unit or serious personal injury.
2. Appropriate conduit and ttings should be selected which will maintain the
integrity of the cabinet.
3. Supply a power conductor sized according to the unit’s power supply
requirements. Connect the power conductor to the unit’s power supply entry
terminal block.
C. Control Circuit Wiring
1. The unit’s supplied control circuit is 110 volt, 1 phase, 60 cycle. The control circuit
is supplied by the factory installed transformer. A control circuit fuse is provided.
D. General
1. Make certain all ground connections to the unit are properly afxed. A proper
connection to earth ground is required. A conduit ground is not a reliable
conductor!
2. Make certain the power conductor, disconnecting means, and fusing are properly
sized according to the unit’s power supply requirements.
3. Make certain all electrical connections are tightly afxed. Any loose wiring
connections must be tighten before engaging the power supply.
4. Make certain no moisture or standing water is present inside the electrical
cabinet.
WARNING: Electric Shock Hazard. High Voltage is present in the electrical cabinet.
Disconnect power before servicing. Follow all facility lock-out tag-out procedures.
Temperature Control Unit : Regal with G500 Series Instrument
Page: 18
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
WARNING: Check that all electrical connections are tight before starting.
Disconnect power before servicing. Follow all facility lock-out tag-out procedures.
Typical Electrical Panel shown as reference of a RK-1230H model. Refer to the electrical drawing available for specific model.
A
B
C
D
E
F
G
H
I
A High temperature limit. Factory set to 515°F.
B High temperature limit instrument relay.
C Power entry terminal block.
D Motor starter and overload block.
E Transformer fuses.
F Control transformer
G Heater contactors
H Water supply pressure switch
I Power Cord. Note : typically included on most 12 kW models with up to 3 HP pumps. Units with 16 kW to 48 kW
heaters and pumps do not include a power cord.
Temperature Control Unit : Regal with G500 Series Instrument
Page: 19
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683 www.AdvantageEngineering.com
3.0 OPERATIONS
3.1 General
3.2 Machine Start Up and Operation
3.3 Instrument Operation : Quick Start
3.4 Instrument : Basic Navigation
3.5 Instrument : Operating Screens
3.6 Instrument : Fault Screens
3.7 Instrument : Main Menu
3.8 Instrument : Setpoints Menu
3.9 Instrument : Utilities Menu
3.10 Instrument : Network Menu
3.11 Instrument : Features Menu
3.12 Instrument : Options Menu
3.13 Instrument : Machine Menu
3.14 Shut Down / Disconnect
Temperature Control Unit : Regal with G500 Series Instrument
Page: 20
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683www.AdvantageEngineering.com
3.1 GENERAL
A. Failure to follow the factory required operation procedures may adversely affect the unit’s
ability to adequately control process temperature and may create a hazardous operating
condition which may result in unit damage or serious operator injury.
B. The Operations segment of this manual is outlined below:
3.2 Machine start-up/operations procedure - follow this segment to start the unit
after the initial installation or to restart the unit after reinstallation to the same or
different process. This section includes information on system ll, electric motor
phasing (pump rotation) and process ow adjustments.
3.3 Instrument Operation - follow this segment to start up and operate the
instrument. This section includes information on setpoint selection and
adjustment and feature explanations.
3.4 Shut down procedure - follow this segment to shut down the unit. This segment
includes information on system cool down, shut down, electrical power supply
precautions, and disconnection from the system.
3.2 MACHINE START UP AND OPERATION
A. System Fill
1. Use only approve high temperature heat transfer uids in this unit such as
Paratherm NF or an equivalent uid (www.paratherm.com). Never use water in
this unit.
List of Approved Heat Transfer Fluids
• Paratherm OR (https://www.paratherm.com/heat-transfer-uids/paratherm-or-heat-transfer-uid/)
• Paratherm NF (https://www.paratherm.com/heat-transfer-uids/paratherm-nf-heat-transfer-uid/)
• Multitherm PG-1 (http://www.multitherm.com/multitherm-pg-1.html)
• Calo FG (https://lubricants.petro-canada.com/productoverview/brand/calo)
2. The primary method of system ll is through the ll port located on the top of the
unit. Simply remove the cap plug and add uid. Replace the cap plug and tighten
when the ll is complete.
3. The alternate method of system ll is through the ll/drain valve. If a pressurized
source is available, simply connect to the ll/drain valve, open the valve and
engage the supply source. Close the valve when the ll is complete.
4. Proper unit ll is essential for efcient and safe operation. An oil level sight
glass is provided to determine unit ll. For initial ll: units up to 12 KW - ll until
WARNING: Follow all Factory operations procedures. Failure to do so may create a
hazardous operating condition which may result in serious operator injury and/or unit damage.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Regal G500 Series Temperature Control Unit User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI