INSTRUCTION MANUAL FOR:
LOBOY 16
AIR CONDITIONERS
McLean Midwest Corp.
dba: McLean Cooling Technology
11611 Business Park Blvd. N Champlin, MN 55316
Tel: 763-323-8200 Fax: 763-576-3200
www.mcleancoolingtech.com
Page 1 10-1008-05 Rev 1
INSTRUCTION MANUAL
TABLE OF CONTENTS
Receiving the Air Conditioner.......................................................................... 1
Handling and Testing the Air Conditioner .......................................................1
Model Information ...........................................................................................2
Model Drawing ................................................................................... 2
Model Number Information ................................................................ 3
Installation Instructions.................................................................................... 3
Cut Out Drawing ................................................................................ 3
Technical Information ..................................................................................... 5
Sequence of Operation ..................................................................... 5
Component Operation ....................................................................... 5
Refrigerant Properties .......................................................................6
Unit Characteristics ........................................................................... 7
Functional Data ................................................................................. 7
Wiring Diagrams ................................................................................ 8
Service Data ................................................................................................. 10
Component List................................................................................ 10
Maintenance....................................................................................... 8
Trouble Shooting.............................................................................. 11
Technical Support ........................................................................... 12
McLean Cooling Warranty............................................................................. 13
RECEIVING THE AIR CONDITIONER
Inspect the air conditioner and check for concealed damage that may have occurred during shipment. Damage
evident upon receipt should be noted on the freight bill. Save the packing material and request an inspection.
Then file a claim with the delivering carrier within 15 days of delivery.
McLean Cooling cannot accept responsibility for freight damages; however, we will assist you in any way
possible.
HANDLING & TESTING THE AIR CONDITIONER
If the air conditioner has been in a horizontal position, be certain it is placed in an upright, vertical or mounting
position for a minimum of five (5) minutes before operating.
Warning: Do not attempt to operate the air conditioner while it is horizontal or on its side, back or front. The
refrigeration compressor is filled with lubricating oil. This will cause permanent damage to the air conditioner and
also voids the warranty.
TEST FOR FUNCTIONALITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE.
Refer to the nameplate for proper electrical current requirements, and then wire unit to a properly grounded
power supply. Minimum circuit ampacity should be at least 125% of the amperage shown in the design data
section for the appropriate model. No other equipment should be connected to this circuit to prevent
overloading.
Immediately after applying power the evaporator blower (enclosure air) should start running. Operate the air
conditioner with the compressor running for five (5) to ten (10) minutes. You will need to set the cooling
thermostat below the ambient temperature to operate the compressor.
Condenser air temperatures should be warmer than normal room temperatures within a few minutes after the
condenser air blower starts.
See sequence of operation for specifics on how the unit operates when powered up.
Page 2 10-1008-177 Rev 1
MODEL INFORMATION
Model Drawing
How to Read Model Numbers
LB16 -
10 2 6 -
G015
1 2 3 4 5
1. Identifies the type/family of air conditioner and the approximate height (i.e. LB16 = LOBOY
family about 16” high).
2. This is the air conditioner’s listed capacity in Btu/hr at rated conditions. (i.e. 10 = 10,000 Btuh at
125/125F)
3. 1 = 115 Volt, 2 = 230 Volt, 4 = 460 Volt.
4. 6 = 50/60 Hz or 60 Hz only.
5. Unique set of numbers for each air conditioner which identifies the accessories on a model.
Page 3 10-1008-05 Rev 1
INSTALLATION INSTRUCTIONS
Step 1: Inspect air conditioner. Verify functionality before mounting the air conditioner, see Handling & Testing
the Air Conditioner on page 1.
Step 2: Use the cut out drawing in Figure 1 for proper openings for the air conditioner. Using the mounting
gasket kit provided with the unit, install gaskets to the air conditioner.
Step 3: Mount air conditioner on enclosure taking care not to damage the mounting gasket. The mounting
gasket is the seal between the air conditioner and the enclosure. Avoid dragging the air conditioner on the
enclosure with the mounting gasket attached as this could cause rips or tears in the gasket and risk losing the
water tight seal.
Step 4: Allow unit to remain upright for a minimum of five (5) minutes before starting. Caution: Air conditioner
must be in upright position during operation.
Step 5: Refer to the nameplate for electrical requirements. Wire the unit to a properly grounded power supply.
Electrical circuit should be fused with slow blow or HACR circuit breaker.
Step 6: Some air conditioners require a remote mounted thermostat. Wire the thermostat outputs to the
appropriate terminals on the 24VAC terminal strip (note locations on the wiring diagram).
Step 7: Set thermostat for required cabinet temperature. Refer to Sequence of Operation for tstat adjustment &
operation.
Figure 1
Cutout Drawing
Page 4 10-1008-177 Rev 1
TECHNICAL INFORMATION
Sequence of Operation
The air conditioner comes standard with one internally mounted thermostat. When the unit is plugged in, the
evaporator fan will be running.
Cooling
When the enclosure temperature is above the cooling thermostat setpoint, power is applied through the time
delay relay. After the delay time the contactor is energized and the compressor starts. The condenser fan will
start once the compressor starts. Component specific information is listed below.
Operating the air conditioner below the minimum ambient temperature or above the maximum ambient
temperatures indicated on the nameplate voids all warranties.
The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube continuously this
can only mean that ambient air is entering the enclosure. Be aware that frequent opening of the enclosure’s
door admits humid air that the air conditioner must then dehumidify.
Standard and Optional Component Operation
Thermostat
The LB16 air conditioner uses our standard 52-6155-02 thermostat. The thermostat setpoint equals the
temperature that the air conditioner turns off. The thermostat has an adjustable differential from setpoint until it
calls for cooling; the typical differential is 5°F. An example of operation is shown below.
For cooling (75-100°F range):
Tstat setpoint = 80° F
Cooling turns on at 85° F
Cooling turns off at 80° F
Time Delay Relay
Factory set for 6 minutes (top dial at 1-10 minutes, bottom dial at 6)
The purpose of the time delay relay is to prevent short cycling of the compressor.
Contactor
The contactor uses a 230V coil.
Page 5 10-1008-05 Rev 1
Standard and Optional Component Operation (continued)
Refrigerant Properties Chart (R407c)
°F °C Bubble Pt Dew Point °F °C Bubble Pt Dew Point
-40 -40 2.9 4.5 60 15.6 117.7 96.8
-35 -37.2 5.2 0.7 65 18.3 128.7 106.7
-30 -34.4 7.9 1.7 70 21.1 140.2 117.2
-25 -31.7 10.7 4 75 23.9 152.5 128.4
-20 -28.9 13.9 6.5 80 26.7 165.5 140.4
-15 -26.1 17.3 9.3 85 29.4 179.2 153.1
-10 -23.3 21.1 12.4 90 32.2 193.6 166.5
-5 -20.6 25.2 15.8 95 35 208.8 180.8
0 -17.8 29.6 19.5 100 37.8 224.9 195.8
5 -15 34.4 23.6 105 40.6 241.8 211.8
10 -12.2 39.6 28 110 43.3 259.6 228.7
15 -9.4 45.2 32.7 115 46.1 278.2 246.5
20 -6.7 51.3 37.9 120 48.9 297.8 265.3
25 -3.9 57.8 43.6 125 51.7 318.3 285.2
30 -1.1 64.7 49.6 130 54.4 339.9 306.1
35 1.7 72.2 56.2 135 57.2 362.4 328.2
40 4.4 80.2 63.2 140 60 386 351.4
45 7.2 88.7 70.7 145 62.8 410.7 375.9
50 10 97.8 78.8 150 65.6 436.5 401.7
55 12.8 107.5 87.5
Page 6 10-1008-177 Rev 1
Unit Characteristics
Model
LB16-1026-GXXX
Dimensional Data
Height 15.75”
Width 19”
Depth 25.2”
Unit Weight 140
Unit Protection Rating Type 12, 4
Cooling Data
Refrigerant R-407c
Refrigerant Charge 25oz. / 709g
Cooling Capacity at 95F enclosure 95F ambient (Btu/hr / W) 8343 / 2445
Cooling Capacity at Max Conditions (Btu/hr / W) 9038 / 2649
Maximum Ambient Temp 125°F / 52°C
Minimum Ambient Temp -40°F / -40°C
Condensate Management Hose discharge
Electrical Data
Rated Voltage (50/60 Hz) 230 V
Rated Frequency 50 / 60 Hz
Voltage Range +/- 10% of rated
Cooling Amps at Max Conditions (50/60 Hz) 12.4/11.0
-XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific
model numbers.
Functional Data
LB16-1026-GXXX
Evaporator Condenser Evaporator Condenser Evaporator Condenser Condenser
Air In Air In Unit Pressure Pressure Delta Delta Subcooling
F) F) Amps (psi) (psi) F) F) F)
65-95 65-95 7.0-8.0
- - 18-25 - -
Page 7 10-1008-05 Rev 1
Wiring Point to Point Diagram
Figure 3 – Wiring Diagram
Page 8 10-1008-177 Rev 1
SERVICE DATA
LB16 Series Component List
Part Description Part Number
Blower Motor, Condenser 10-1020-04
Blower Motor, Evaporator 10-1020-10
Capacitor, Condenser Blower 52-6083-00
Capacitor, Evaporator Blower 52-6084-05
Capacitor, Compressor, Run 52-6031-01
Time Delay Relay 10-1005-71
Coil, Condenser 16-7001-00
Coil, Evaporator 52-6121-01
Compressor 10-1026-115
Contactor, Compressor 10-1005-42
Evaporator Inlet Filter 10-1000-08
Filter/Dryer 52-6028-00
Capillary Tube 99-0640-35
Thermostat 52-6155-02
Maintenance
Compressor
The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should
provide years of satisfactory operating service.
Condenser and Evaporator Blower Motors
Blower motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life
of the motor.
Caution: Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly
deteriorate condenser coils, blowers and motors, etc. Contact McLean Cooling for special recommendations.
Refrigerant Loss
Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks.
Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment
during manufacture may require repair or recharging of the system. This work should only be performed by
qualified professionals, generally available through a local, reputable air conditioning repair or service company.
Should the refrigerant charge be lost, access ports on the suction and discharge sides of the compressor are
provided for recharging and/or checking suction and discharge pressures. Under no circumstances should the
access fitting covers be loosened, removed or tampered with. Breaking of seals on compressor access fittings
during warranty period will void warranty on hermetic system. Recharging ports are provided for the ease and
convenience of reputable refrigeration repair service personnel for recharging the air conditioner
.
Refer to the data on the nameplate that specifies the type of refrigerant and the charge size in ounces.
Before recharging, make sure there are no leaks and that the system has been properly evacuated into a
deep vacuum. Technician must weigh in charge according to the nameplate specifications.
Page 9 10-1008-05 Rev 1
Troubleshooting
1. Check manufacturer’s nameplate located on the unit for correct power supply.
2. Turn the power to the unit on. The evaporator (Enclosure or “COLD” air) blower should come on. Is
there airflow?
YES, proceed to step # 3.
NO, possible: Open motor winding
Stuck blower motor
Obstructed wheels/blades
3. Check thermostat setting? Adjust thermostat to the lowest setting. This should turn the condenser
blower and the compressor on. Did condenser blower and compressor come on when the thermostat was
turned on?
YES, proceed to step #4.
NO, possible: Defective thermostat
4. Are both blowers and the compressor running? If not the unit will not cool properly.
5. Check condenser (Ambient or “HOT” air) blower for airflow. Is there airflow?
YES, proceed to step # 6.
NO, possible: Defective thermostat
Open motor winding
Stuck blower motor
Obstructed wheels/blades
6. Carefully check the compressor for operation - motor should cause slight vibration, and the outer case
of the compressor should be warm.
YES, wait 5 minutes, then proceed to step #7.
NO, possible: Defective thermostat
Defective capacitor
Defective overload
Defective relay
7 Make sure the coils are clean. Then check evaporator “air in” and “air out” temperatures. If the
temperatures are the same:
Possible loss of refrigerant
Possible bad valves in the compressor
8. To check for a bad thermostat. Turn power to the unit off. Remove control box cover, place both
thermostat wires onto one terminal (replace control box cover for safety). This will bypass the switch in
the thermostat. Turn the power on. If both blowers and the compressor come on, the thermostat needs
to be replaced.
Repair o
r
Replace
defective parts.
Replace part.
Repair o
r
Replace
defective parts.
Repair o
r
Replace
defective parts.
Repair o
r
Replace
defective parts.
Page 10 10-1008-177 Rev 1
Symptoms and Possible Causes:
SYMPTOM POSSIBLE CAUSE
Unit won’t cool * Clogged fins on coil(s)
* Dirty filters
* Blowers/fans not running
* Compressor not running
* Compressor runs, but has bad valves
* Loss of refrigerant
Compressor tries to start but won’t run * Low line voltage at start. Should be +/-10% rated voltage
* Compressor motor stuck
* Bad contactor
* Bad overload switch
* Bad run/start capacitor
Unit blows breakers * Under sized breaker/fuse or not time delayed
* Short in system
Getting water in enclosure * Drain plugged
* Drain tube kinked
* Enclosure not sealed (allowing humidity in)
* Mounting gasket damaged
For additional technical support contact McLean Cooling at 866-545-5252.
Page 11 10-1008-05 Rev 1
MCLEAN COOLING TECHNOLOGY WARRANTY
Please note: Warranty effective at time of shipment.
McLean Cooling Technology warrants that all material and workmanship are free of defects in quality which
impair the usefulness of the air conditioner or heat exchanger for a period of five (5) years for non-operating
parts, except for the filter; and for one (1) year for everything else when installed and operated under the
following conditions:
A. Maximum voltage variation no greater than plus or minus 10% of nameplate nominal rating.
B. Maximum frequency variation no greater than plus or minus 3 Hz. of nameplate nominal rating.
C. Must not exceed minimum and maximum stated temperatures on the nameplate.
D. Not to exceed (BTU/Hr.) rating, including any heat sink, as indicated on the nameplate.
E. The unit must not be restarted for a period of one (1) minute after intentional or accidental shut-off.
(This does not apply to heat exchanger or filter fan.)
F. Extended operation with thermostat stop screw removed and setting below 70°F.
McLean Cooling warrants that all material and workmanship are free of defects in quality which impair the
usefulness of the filter fan package and all custom air conditioners and heat exchangers for a period of one (1)
year, except for the filter, when installed and operated under conditions A, B, C and D as listed above.
Not covered in this warranty is damage to the air conditioner or heat exchanger due to the introduction of other
than the nameplate-designated refrigerant. Operation of any McLean Cooling product that has not been
designed with proper protective coatings and/or options and is in an abnormal or corrosive environment voids
the warranty. Prolonged operation with dirty filters also voids the warranty.
Should any part prove defective within the above warranty period, the customer may choose to return the
defective product that is under warranty to McLean Cooling for repair at no charge or the customer has the
option to repair the defective products at his own expense and McLean Cooling will supply repair parts at no
charge providing the defective part is returned and found to have failed under warranty. Parts supplied as
warranty replacement parts will assume the balance of the warranty on the part returned for warranty
consideration.
Please be advised: According to the Federal Register, no person maintaining, servicing, repairing, or disposing
of appliances may knowingly vent or otherwise release into the environment any class I or class II substance
used as refrigerant.
McLean Cooling assumes no liability beyond the repair or replacement of its own product. Customer
modification of any McLean Cooling product voids this warranty.
The purchaser assumes the responsibility of grounding the unit and installing it in accordance with local
electrical and safety codes, as well as the National Electric Code (NEC) and OSHA.
This express warranty constitutes the entire warranty with respect to the PRODUCT and IS IN LIEU OF ALL
OTHERS, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OR MERCHANTABILITY AND
WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND IN NO EVENT IS MCLEAN
COOLINGRESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.
HOLD HARMLESS
In consideration of purchase of equipment from McLean Cooling by a customer, McLean Cooling agrees to
indemnify and hold harmless such customer and users with a defense, as to any claim, demand, statutory court
cost, fees for attorney's services provided for below, and/or judgment, for actual of alleged patent infringement in
any country, arising out of the use, sale or advertisement of any equipment manufactured or sold by McLean
Cooling to McLean Cooling’s own specifications, provided that the customer or user shall promptly notify
McLean Cooling in writing of any such claim or demand, provided further that McLean Cooling shall have the
right and option to undertake and control the entire defense of such claim, or demand instituted against the
customer or user, but limited to the products made or sold by McLean Cooling, through counsel selected by
McLean Cooling, and to settle and pay any claim award arising out of such claim or demand, and provided
further that the customer or user will provide such information and assistance as McLean Cooling may request
subject to reimbursement by McLean Cooling for any out-of pocket expense incurred in providing such
requested assistance. Liability of McLean Cooling for any infringement or claim thereof shall be limited to the
above undertaking.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8