Broan P5RF-X60K and Installation guide

Type
Installation guide

This manual is also suitable for

15 SEER
INSTALLATION INSTRUCTIONS
Single Package Air Conditioner - 2 Stage, R410A
P5RF-KA / PPA2RFX-KA SERIES
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being
able to install the product according to strict safety guidelines and instructing the customer on
how to operate and maintain the equipment for the life of the product. Safety should always be
the deciding factor when installing this product and using common sense plays an important
role as well. Pay attention to all safety warnings and any other special notes highlighted in the
manual. Improper installation of the furnace or failure to follow safety warnings could result
in serious injury, death, or property damage.
These instructions are primarily intended to assist qualified individuals experienced in the
proper installation of this appliance. Some local codes require licensed installation/service
personnel for this type of equipment. Please read all instructions carefully before starting the
installation. Return these instructions to the customer’s package for future reference.
2
Important Safety Information ....................................3
General Information ...................................................4
Before You Install this Unit .........................................4
Locating the Air Conditioner .....................................4
Minimum Clearance Requirements ..........................4
Service Access Clearances ..................................4
Clearances to Combustible Materials ...................4
Air Duct System ........................................................4
Air Conditioner Installation .......................................5
Unpacking the Unit ...................................................5
Installing Return & Supply Collars .............................5
Supply Duct ...........................................................5
Return Duct ...........................................................5
Locating & Installing the Return Air Assembly ..........6
Locating & Installing the Supply Dampers.................6
Condensate Drainage ..............................................6
Electrical Connections ...............................................6
Pre - Electrical Checklist ...........................................6
Line Voltage ...............................................................6
Grounding..................................................................7
Overcurrent Protection ..............................................7
Thermostat / Low Voltage Connections .....................8
2-Stage Heating .....................................................8
Cooling Mode .........................................................9
Electric Heat Package (optional) ...............................9
Blower Speed ...........................................................9
Outdoor Motor (4 & 5 Ton) .....................................9
Startup & Adjustments ............................................10
Pre - Start Checklist ................................................10
Start - Up Procedure ...............................................10
Air Circulation ....................................................... 10
System Cooling ....................................................10
Emergency Heat ..................................................10
Adjustment of Refrigerant Charge ........................... 10
Refrigerant Charging ...............................................10
Charging an R410A Unit in AC Mode w/ Outdoor
Temperatures above 55° F ......................................10
Air Conditioner Maintenance ...................................11
Component Functions .............................................11
Replacement Parts ...................................................11
Figures & Tables .......................................................12
Figure 7 - Unit Dimensions ..................................12
Table 4 - Physical Data ........................................12
Refrigerant Charging Charts ...................................13
Figure 8 - Charging Chart for 2 Ton Units ............13
Figure 9 - Charging Chart for 3 Ton Units ............13
Figure 10 - Charging Chart for 4 Ton Units ..........14
Figure 11 - Charging Chart for 5 Ton Units ..........14
Wiring Diagrams ...................................................... 15
Figure 12 - 2 & 3 Ton Units ..................................15
Figure 13 - 4 & 5 Ton Units ..................................16
Installation / Performance Checklist ....................... 20
TABLE OF CONTENTS
3
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment.
Pay attention to all safety warnings and any other special
notes highlighted in the manual. Safety markings are
used frequently throughout this manual to designate a
degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that
if not avoided, could result in personal injury or death.
CAUTION indicates a potentially hazardous situation that
if not avoided, may result in minor or moderate injury or
property damage.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
power to the indoor blower.
• Whenservicingcontrols,labelallwiresprior
to disconnecting. Reconnect wires correctly.
• Verifyproperoperationafterservicing.
WARNING:
These units are fully charged with R-410A
refrigerant and ready for installation. When
a system is installed according to these
instructions, no refrigerant charging is
required. If repairs make it necessary for
evacuation and charging, it should only be
attempted by qualified, trained personnel
thoroughly familiar with this equipment.
Some local codes require licensed installation
service personnel to service this type of
equipment. Under no circumstances should
the equipment owner attempt to install and/
or service this equipment. Failure to comply
with this warning could result in equipment
damage, personal injury, or death.
CAUTION:
This unit uses R-410A refrigerant. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.
WARNING:
The information listed below must be followed
during the installation, service, and operation
of this unit. Unqualified individuals should
not attempt to interpret these instructions or
install this equipment. If you do not posses
mechanical skills or tools, call your local
dealer for assistance. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious personal
injury or death.
• The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes and
the National Electrical Code (ANSI CI) for special
installation requirements.
• Allelectricalwiringmustbecompletedinaccordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
• Thisequipmentcontainsliquidandgaseousrefrigerant
under high pressure. DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by
qualified trained personnel thoroughly familiar with this
type equipment.
• Usecautionwhenhandlingthisapplianceorremoving
components. Personal injury can occur from sharp
metal edges present in all sheet metal constructed
equipment.
• Thisunitisdesignedforoutdoorinstallationsonlyand
should be located in a position as shown on page 6.
• Followallprecautionsin theliterature,ontags,and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment.
• Theinstallershouldbecomefamiliarwiththeunitswiring
diagram before making any electrical connections to
the unit. See the unit wiring label or Figures 12 - 13
(pages 15 - 16).
4
Air Duct System
Air ducts must be installed in accordance with the standards
of the National Fire Protection Association “Standard for
Installation of Air Conditioning and Ventilation Systems”
(NFPA 90A), “Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems” (NFPA
90B), these instructions, and all applicable codes. NFPA
publications are avaialable by writing to: National Fire
Protection Association, Batterymarch Park, Quincy, ME
02269 or visit www.NFPA.org on the web.
• Designtheductworkaccordingtomethodsdescribed
by the Air Conditioning Contractors of America (ACCA).
• The supply duct system, including the number and
type of registers, will have much more effect on the
performance of the system than any other factor. The
duct must be sufficiently large to conduct an adequate
amount of air to each register. See Figure 2 (page 5).
• Ductworkshouldbeattacheddirectlytotheunitanges
for horizontal applications.
• Forhighlyresistiveductsystemsitmaybenecessary
to add an additional return air duct and or supply to
achieve maximum performance and prevent coil icing
andrefrigerantoodback
• The air conditioning output of the system will not
cool the home if air is lost to the outside through
leaks in the duct system. Ducts that are collapsed
or restricted by foreign objects will also prevent
adequate air flow.
Figure 1. Minimum Unit Clearances
12"
12"
24"
TOP OF UNIT
TO BE
UNOBSTRUCTED
0"
GENERAL INFORMATION
This air conditioner is designed only for outdoor ground
level installations and can be readily connected to the
high static duct system of a home. This unit has been
tested for capacity and efficiency in accordance with
A.H.R.I. Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and
create unsafe hazards.
Before You Install this Unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. If there is any question
concerning the power supply, contact the local power
company.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage
prior to installing the equipment at the job site. Verify
coil fins are straight. If necessary, comb fins to remove
attenedor bentns.Claimsfordamageshould be
filed immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read
all instructions before installing the unit.
Locating the Air Conditioner
• Surveythejobsitetodeterminethebestlocationfor
mounting the outdoor unit. Select a solid, level position,
preferably on a concrete slab, slightly above the grade
level, and parallel to the home. If possible, select a site
for the unit that is as close as possible to the proposed
return grille location. DO NOT PLACE UNIT UNDER
THE HOME.
• The unit should be located with consideration of
minimizing the length of the supply and return ducts.
If practical, place the air conditioner and its ducts in
an area where they will be shaded from the afternoon
sun, when the heat load is greatest.
• Thelengthofthesupplyandreturnductsshouldbe
kept to a minimum with no sharp radius bends.
• Overheadobstructions,poorlyventilatedareas,and
areas subject to accumulation of debris should be
avoided. The hot condenser air must be discharged up
and away from the home, and if possible, in a direction
with the prevailing wind. Do not place the unit in a
confined space.
• Considerationshouldalsobegiventoavailability of
electric power, service access, noise, and shade.
Minimum Clearance Requirements
Sufcientclearanceforunobstructedairowthroughthe
outdoor coil must be maintained in order to provide room
for proper servicing and achieve rated performance. See
Figure 1 for minimum clearances to obstructions.
Service Access Clearance
Blower access panel side ..........................................24”
Electrical compartment access panel side ...............12”
Clearance between overhang and top of unit ........ 72”
Clearance around condenser coil area to wall or
shrubs (excludes duct panel side) ............................. 12”
Clearances to Combustible Materials
Supply and return air ducts .........................................0”
Duct connection side ...................................................0”
5
AIR CONDITIONER INSTALLATION
Unpacking the Unit
It is recommended that the unit be unpacked at the
installation site to minimize damage due to handling.
CAUTION:
Do not tip the unit on its side. Oil may enter
the compressor cylinders and cause starting
trouble. If unit has been set on its side, restore
to upright position and do not run for several
hours. Then run unit for a few seconds. Do this
three or four times with five minutes between
runs.
1. Remove the bands from around the unit.
2.Unfoldthetopandbottomcapanges.
3. Carefully remove the top cap and tube.
Installing Return & Supply Air Collars
If the supply and return collars are supplied with the unit,
they will be located in the supply duct. They can be easily
positioned over the unit openings (Figure 3) and secured
with sheet metal screws.
• Thediameterofthereturnductcollaris14”.
• Thediameterofthesupplyductcollaris12”.
Before permanently installing the collars, it is
recommended you pre-fit them over the openings first
to determine best fit and alignment.
Supply Duct
1. Position the supply duct collar so the edge of the unit
openingtsbetweentheangeandthebead.
2. Overlap the collar ends keeping the small screw holes
underneath.
Figure 3. Return & Supply Air Collars
Transition
Duct Screws
Supply Air
Return Air
Duct
Dimples
• All duct work passing through unconditioned space
must be properly insulated to minimize duct losses
and prevent condensation. Use insulation with an outer
vapor barrier. Refer to local codes for insulation material
requirements.
MULTIPLE DUCT APPLICATIONSINGLE DUCT APPLICATION
Figure 2. Single & Multiple Duct Applications
3. Align the holes in the crimped area and install one
screw. NOTE: It may be necessary to loosen the four
screws that hold the transition duct in order to install the
supply fitting. Re-tighten when installation is complete.
4. Tap collar (if necessary) to ensure engagement with
unit opening and install second screw.
5. Tighten first screw and rotate collar clockwise so joint
is near three o’clock position.
Return Duct
1. Assemble the collar by overlapping the two ends.
NOTE: One end of the collar is slotted and the opposite
end has two small holes. Position the end with small
screw holes underneath the slotted end.
2. Fasten the collar ends with two self drilling sheet metal
screws.
3. Position the collar over the unit opening. Align the
four holes in the collar with the four dimples or holes
(depending on unit model) in the panel.
4. Secure the collar to the rear panel using self drilling
screws (10-16x.5).
6
ELECTRICAL CONNECTIONS
WARNING:
To avoid risk of electrical shock, personal
injury, or death, disconnect all electrical power
to the unit before performing any maintenance
or service. The unit may have more than one
electrical supply.
Label all wires prior to disconnection when
servicing the unit. Wiring errors can cause
improper and dangerous operation
• Allelectricalconnectionsmustbeincompliancewith
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
• ForCanadianinstallationstheelectricalconnections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the
supply source match the specifications on the unit
rating plate.
Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper high and low
voltage wiring.
Verify factory wiring is in accordance with the unit wiring
diagram (Figures 12 & 13, pages 15 & 16). Inspect for
loose connections.
LineVoltage
• Awiringdiagramislocatedontheinsidecoverofthe
electrical box of the unit. The installer should become
familiar with the wiring diagram before making any
electrical connections to the unit.
• An electrical disconnect must be located within
sight of and readily accessible to the unit. This
switch shall be capable of electrically de-energizing
the unit.
• Line voltage to the unit should be supplied from a
dedicated branch circuit containing the correct fuse
or circuit breaker for the unit. Incoming field wiring
and minimum size of electrical conductors and circuit
protection must be in compliance with information listed
on the unit data label. Any other wiring methods must
be acceptable to authority having jurisdiction.
• Providepowersupplyfortheunitinaccordancewiththe
unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment. Extend leads through
power wiring hole (Figure 5, page 7). Connect L1 & L2
directly to the contactor.
Condensate Drainage
A 3/4” condensate fitting extends out of the side of the
unit as shown in Figure 4. The drain trap (shipped in the
electrical compartment), must be installed to prevent water
from collecting inside the unit.
1. Thread the elbow provided with the unit into the drain
connection until hand tight.
2. Connect the condensate tubing onto the fitting, forming
a trap near the drain connection.
3. Route the condensate tube from the trap to a suitable
drain. NOTE: For proper drainage, make sure the trap
is level to the ground and tubing outlet is below trap
level.
Elbow
Figure 4. Drain Trap
P-Trap
Locating & Installing the Return Air Assembly
To simplify installation, locate and install the return air
assembly first. If desired, the return opening can be
located inside a closet with louvered doors that has an
open area equal to or greater than a 12” x 20” grille. The
return air grille can be placed in the wall of a closet and
the air ducted into the filter box through a boxed-in area at
theclosetoorlevel.Verifythelterisreadilyaccessible.
Locating & Installing the Supply Damper(s)
CAUTION:
If installing this air conditioning system in
conjunction with a furnace, a damper must be
installed in the furnace base assembly to prevent
cold air from being discharged around the heat
exchanger. Damage to the heat exchanger and
asphyxiation may occur if a damper is not
installed.
Check with the furnace manufacturer for damper
requirements. Failure to install the required
furnace damper may invalidate code agency
listing and limited warranty on the furnace.
7
Figure 5. Power Entry
LowVoltage
LineVoltage
• Theunitrequiresbothpowerandcontrolcircuitelectrical
connections. Refer to the wiring diagram / schematic for
identification and location of unit field wiring interfaces
(Figures 12 & 13). Make all electrical connections in
accordance with all applicable codes and ordinances.
• Overcurrentprotectionmustbeprovidedatthebranch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes.
See the unit rating plate for minimum circuit ampacity
and maximum overcurrent protection limits.
• Useonlycopperwireforthelinevoltagepowersupply
to this unit as listed in Table 1. Use proper code agency
listed conduit and a conduit connector for connecting
the supply wires to the unit. Use of rain tight conduit is
recommended.
• 208/230Voltunitsareshippedfromthefactorywired
for 230 volt operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
• Optionalequipmentrequiringconnectiontothepower
or control circuits must be wired in strict accordance
of the NEC (ANSI/NFPA 70), applicable local codes,
and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the
National Electrical Code (ANSI/NFPA 70) or CSA C22.1
Electrical Code. Ground the air conditioning unit using
the green grounding screw provided in the control panel.
Overcurrent Protection
Generally, the best fuse or breaker for any air conditioner
is the smallest size that will permit the equipment to run
under normal usage and provide maximum equipment
protection. Properly sized fuses and breakers also prevent
nuisance trips during unit startup. If a fuse blows or a
breaker trips, always determine the reason. Do not
arbitrarily install a larger fuse or breaker and do not,
in any case, exceed the maximum size listed on the
data label of the unit.
COPPER WIRE SIZE — AWG
(1%VoltageDrop)
Supply Wire Length-Feet
Supply Circuit
Ampacity
200 150 100 50
6 8 10 14 15
4 6 8 12 20
4 6 8 10 25
4 4 6 10 30
3 4 6 8 35
3 4 6 8 40
2 3 4 6 45
2 3 4 6 50
2 3 4 6 55
1 2 3 4 60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
8
Thermostat/LowVoltageConnections
• Theseunitsare designed tooperatewitha 24VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having
jurisdiction. Thermostat connections should be made
in accordance with the instructions supplied with the
thermostat and the indoor equipment.
• The low voltage wires must be properly connected.
Route 24V control wires through the sealing grommet
(Figure 4, page 6) near the power entrance. Connect
the control wires to the defrost board and blower relay
wire (Figure 6). Recommended wire gauge and wire
lengths for typical thermostat connections are listed in
Table 2.
• Single stage or two-stage heating thermostats can
be used with this equipment depending on optional
accessories installed with the unit. Select a thermostat
that operates in conjunction with the installed
accessories.
• Thethermostatshouldbemountedabout5feetabove
theooronaninsidewall.DONOTinstallthethermostat
on an outside wall or any other location where its
operation may be adversely affected by radiant heat from
fireplaces, sunlight, or lighting fixtures, and convective
heat from warm air registers or electrical appliances.
Refer to the thermostat manufacturer’s instruction sheet
for detailed mounting information. NOTE: If installing
unit with an external furnace, refer to the installation
instructions supplied with the furnace for proper heat
anticipator setting.
• The 15 SEER air conditioner uses a special two speed
compressor to achieve a high level of efficiency in a
compact frame. For the highest efficiency, the use of a
2-stage Heat / Cool thermostat should be used with this
unit. The heat / cool thermostat prevents simultaneous
operation of the heating and cooling units and is
equipped with an ON-AUTO fan mode that allows the
home owner to operate the indoor blower when only
air circulation is desired.
Table 2. Thermostat Wire Gauge
Thermostat
Wire Gauge
Recommended T-Stat Wire
Length (Unit to T-Stat)
2-Wire
(Heating)
5-Wire
(Heating/Cooling)
24 55 25
22 90 45
20 140 70
18 225 110
Figure 6. Typical Wiring (Field Supplied) for 2-Stage Cool & 1 or 2-Stage Electric Heat
RED - 24VAC
R
Y1
G
W1
ORANGE - S2 HEAT
*
RED - 24VAC
R
Y1
G
BROWN
W
ORANGE
5 Wire 2 Stage Cool / 1 Stage Heat T-Stat
Single Stage Electric Heat
W2
Two-Stage Electric Heat
Y2
Y2
Optional
Outdoor Thermostat
(Field Supplied)
R
Y1
G
BROWN - S1 HEAT
W1
2-Stage Electric Heat
Y2
6 Wire 2 Stage Heat / Cool T-Stat
YELLOW - S1 COOL
GREEN - FAN
BLUE - S2 COOL
]
S1 + S2 HEAT
BLUE - S2 COOL
BLUE - S2 COOL
GREEN - FAN
GREEN - FAN
YELLOW - S1 COOL
YELLOW - S1 COOL
BROWN - S1 HEAT
ORANGE - S2 HEAT
*
RED - 24VAC
5 Wire 2 Stage Cool w/ Optional OD T-Stat
*Refer to specific electric heat kit for stage 2 heat capability.
Heat / Cool Thermostat
A 2 stage Cooling thermostat is recommended for this
product. A single or two stage heating thermostat may be
used depending on the optional accessories installed with
the unit. Install a thermostat that operates in conjunction
with the installed accessories. See Figure 6 for 5 or 6 wire
Heat / Cool applications
2 Stage Heat with Single Stage Heating Thermostat - If a
single stage heat thermostat is used and 2 stage heat is
desired, an “optional” outdoor thermostat may be installed.
Connect the “optional” outdoor thermostat between the
W1 (brown) connection and orange wire in the outdoor
unit. See Figure 6. Refer to the installation Instructions
supplied with the outdoor thermostat for setup details.
9
Model
Number
Wire Color/
Speed Tap
Motor
Speed
Air Flow
(0.3 in. WC)
X24KA
T1 Low 520
Orange/T2 Medium/Low* 560
Black/T3 Medium** 800
Red/T4 Medium/High*** 1,040
T5 High 1,250
X36KA
Orange/T1 Low* 630
T2 Medium/Low 900
Black/T3 Medium** 1,060
Red/T4 Medium/High*** 1,420
T5 High 1,500
X48KA
Orange/T1 Low* 980
T2 Medium/Low 1,230
Red/T3 Medium*** 1,400
Black/T4 Medium/High** 1,500
T5 High 1,280
X60KA
T1 Low 1,060
Orange/T2 Medium/Low* 1,204
Red/T3 Medium*** 1,504
Black/T4 Medium/High** 1,700
T5 High 1,968
* Denotes factory set low speed cooling / heating.
** Denotes factory set high speed cooling / heating.
*** Denotes factory set electric heating speed.
Table 3. Motor Lead Connection
Cooling Mode
1. On a call for cooling, the thermostat closes, and
applies 24VAC to the G & Y1 terminals of the control.
The compressor contactor closes and operates the
compressor in 1st stage.
2. If the thermostat is not satisfied in the required
time (based on the operation of the 2-stage cooling
thermostat), Y2 will energize and the compressor will
run at 2nd stage. Refer to the thermostat’s Installation
Instructions for the cooling profile.
3. When the thermostat is satisfied, the G & Y terminals on
the control board de-energized and open the compressor
contactor.
Electric Heat Package (optional)
This air conditioner is shipped without an auxiliary electric
heat kit installed. If electric heat is desired, an accessory
heater kit must be field installed.
• Selectthecorrectsizeheatpackagefortheinstallation.
See specifications sheet for available kits and
application. Install the heater kit according to the to
the installation instructions provided with the kit.
• Installationismosteasilyaccomplishedbeforemaking
duct or electrical connections.
• Theblowermustbesettohighspeedforelectricheat
operation. Refer to Table 3 for blower speeds.
Blower Speed
For optimum system performance and comfort, it may be
necessary to change the factory speed setting. See Table
3 for factory settings.
WARNING:
To avoid electric shock, personal injury, or death,
turn off the electric power at the disconnect
or the main service panel before making any
electrical connections.
To Change the blower speed of the high efficiency motor:
1. Disconnect all electrical power to the unit and remove
the service panel.
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
2. Locate the orange, black and red wires terminated to
the blower motor. The orange wire controls cooling
operation, the black wire controls high speed cooling
and the red wire controls the heating operation.
CAUTION:
To avoid personal injury or property damage,
make certain that the motor leads cannot come
into contact with any metal components of the
unit.
3.Verifytherequiredspeedfromtheairowdatafound
in Table 3. Place appropriate wire on the appropriate
motorspeedtapfortherequiredairow.
4. Check all factory wiring per the unit wiring diagram and
inspect the factory wiring connections to be sure none
loosened during shipping or installation.
Outdoor Motor - 4 & 5 Ton Models Only
The outdoor motor has variable speeds which adjust in
conjunction with the compressor and indoor blower motor.
The outdoor motor is preset at the factory and wired as
shown:
• 4 Ton Model: White wire is connected to Y1 and the
yellow wire is connected to Y2.
• 5 Ton Model: Yellow wire is connected to Y1 and the
white wire is connected to Y2.
NOTE: The blue wire from the outdoor ECM motor is
always common for either speed setting.
10
System Heating
(Available only when Electric heat is supplied)
1. Set the thermostat’s system mode to HEAT and the
fan mode to either AUTO (intermittent air) or to ON
(continuous air).
2. Set the thermostat’s temperature selector above existing
room temperature:
3. Allow the system to operate for several minutes and
check the supply registers for warm air.
4. Verify the outdoor AC compressor and fan are not
running. NOTE: The indoor blower will run according
to the thermostat’s fan mode setting.
Adjustment of Refrigerant Charge
CAUTION:
Packaged AC units contain liquid and gaseous
refrigerant under pressure. Adjustment of
refrigerant charge should only be attempted
by qualified, trained personnel thoroughly
familiar with the equipment and safe responsible
refrigerant handling procedures. Under no
circumstances should the homeowner attempt
to install and/or service this equipment. Failure
to comply with this warning could result in
equipment damage, personal injury, or death.
• Toachieveratedcapacityandefciencythecompressor
must be exposed to refrigerant for at least 24 hours
prior to running. After unit startup, the compressor must
run for a minimum of 12 hours.
• Therefrigerantchargecanbecheckedandadjusted
through the service ports provided external to the
unit. Use only gage line sets which have a “Schrader”
depression device present to actuate the valve.
Charging an R-410A Unit in AC Mode with Outdoor
Temperatures Above 55° F
1. With the system operating in a steady-state, measure
the liquid refrigerant pressure (in psig) at the service
valve.
2. Measure the liquid refrigerant temperature (° F) at the
service valve.
3. For the temperature measured, determine the required
liquid refrigerant pressure from your units label or
charging charts (Figures 8 - 11, pages 13 - 14).
• Ifthepressuremeasuredinstep1isgreaterthan
the required liquid refrigerant pressure determined
in step 3, there is too much charge in the system.
Remove refrigerant and repeat steps 1 - 3 until the
system is correctly charged.
• Ifthepressuremeasuredinstep1islessthanthe
required liquid refrigerant pressure determined in
step 3, there is too little charge in the system. Add
refrigerant and repeat steps 1 - 3 until the system is
correctly charged.
START UP & ADJUSTMENTS
Pre-Start Checklist
The following check list should be observed prior to
starting the unit.
Verify the unit is level and allows proper condensate
drainage.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/
control panels are in place. Unit must be installed with
the proper clearances as listed in Figure 1 (page 4).
Verify that the duct work is sealed to prevent air leakage.
Verify that the line voltage power leads are securely
connected and the unit is properly grounded. Check
the condenser fan to make sure it turns freely.
Verify the thermostat is wired correctly and installed
in a proper location. Make sure the low voltage wires
are securely connected to the correct leads on the low
voltage terminal strip.
Verify that the power supply branch circuit overcurrent
protection is sized properly.
Start-Up Procedure
NOTE: The control circuit thermostat may consist of an
anti-short cycle timer that will not let the compressor re-
start before 3 - 5 minutes have elapsed.
1. Set the system mode to OFF and the temperature
mode to its highest setting.
2. Turn power on at the disconnect switch.
3. Set the system mode to ON or COOL.
4. Set the temperature mode below room temperature.
Verify that the indoor blower, outdoor fan, and
compressor energize and the cooling function starts.
5. Verify the discharge air grilles are adjusted and the
system air is balanced.
6. Verify the duct work has no air leaks.
7. Verify the condensate drain is installed correctly and
functions properly.
8. Set the temperature mode above room temperature.
The unit should stop.
9. Instruct the homeowner on unit and thermostat operation
and filter servicing.
Air Circulation
Leave the thermostat system mode on OFF, and set the
fan mode to ON. Blower should run continuously. Check
the air delivery at the supply registers and adjust register
openings for balanced air distribution. If air is insufficient,
examine the ductwork for leaks or obstructions. Set the
thermostat fan mode to AUTO. The blower should stop
running.
System Cooling
Change the thermostat’s system mode to COOL and
the fan mode to AUTO. Set the thermostat temperature
selector below the existing room temperature. Allow the
cooling system to operate for several minutes and check
for the discharge of cool air at the supply registers.
11
COMPONENT FUNCTIONS
High Pressure Switch (HPS)
A high-pressure switch is factory-installed and located in
the liquid line internal to the unit. The switch is designed
to protect the system when very high pressures occur
during abnormal conditions. Under normal conditions,
the switch is closed. If the liquid pressure rises above
575 psig, the switch will open and de-energize the unit.
The switch will close again when the liquid pressure
decreases to 460 psig.
Low Pressure Switch (LPS)
A low-pressure switch is factory-installed and located in
the suction line internal to the unit. The switch is designed
to protect the compressor from a loss of charge. Under
normal conditions, the switch is closed. If the suction
pressure falls below 5 psig, the switch will open and de-
energize the unit. The switch will close again when the
suction pressure increases above 20 psig.
AIR CONDITIONER MAINTENANCE
WARNING:
To prevent electrical shock, personal injury,
or death, disconnect all electrical power to
the unit before performing any maintenance
or service. The unit may have more than one
electrical supply.
Proper maintenance is important to achieve optimum
performance from the air conditioner. The ability to properly
perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these
skills, contact your dealer for maintenance. Consult your
local dealer about the availability of maintenance contracts.
Routine maintenance should include the following:
• Inspectandcleanorreplaceairltersatthebeginning
of each heating and cooling season, or more frequently
if required.
• Inspectthecondensatedrainandoutdoorcoilatthe
beginning of each cooling season. Remove any debris.
Clean the outdoor coil and louvers as necessary using
a mild detergent and water. Rinse thoroughly with water.
• Inspecttheelectricalconnectionsfortightnessatthe
beginning of each heating and cooling season. Service
as necessary.
CAUTION:
The unit should never be operated without a
filter in the return air system. Replace disposable
filters with the same type and size.
• Donotattempttoaddadditionaloiltomotorsunequipped
with oil tubes. The compressor is hermetically sealed
at the factory and does not require lubrication.
REPLACEMENT PARTS
Replacement parts are available through all Nordyne
distributors. Please have the complete model and serial
number of the unit when ordering replacement parts.
Electrical
• Capacitors • TemperatureLimitSwitches
• Compressors • Thermostats
• Contactors • TimeDelayRelays
• PressureSwitches • Transformers
• Relays
Motors
• BlowerMotor
• FanMotor
Components
• BlowerAssembly • FanGrille
• CabinetPanels • Filter/Driers
• ExpansionValves
12
L
W
TopView
FIGURES & TABLES
18.01
Electric Heater Power Supply
Power Supply
Low Voltage Supply
Control
Access
Panel
Blower Access Panel
H
17.86
15.36
10.10
3/4" NPT
Drain Connection
1"
12.13
1.38
3.2
3.2 5.29
9.15
9.04
17.50
14" diameter
Return Duct
Opening
12" diameter
Supply Duct
Opening
3.0
5.5
1"
3.15
A
B
Back(Duct)View
SideView
Figure 7. Unit Dimensions
Table 4. Physical Data
Model
Number
(L)
Length
(W)
Width
(H)
Height
A B
X24KA 49 35 30.2 35.02 2.48
X36KA 49 35 30.2 35.02 2.48
X48KA 49 35 38.2 35.02 2.48
X60KA 63 35 38.2 35.02 2.48
13
REFRIGERANT CHARGING CHARTS
Figure 8. Charging Chart for 2 ton Units
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75 80 85 90 95 100 105110 115120 125 130 135
Liquid Pressure (psig)
Liquid Temperature (F)
X24KA Charging Chart - Cooling
Add refrigerant when below curve
Remove refrigerant when above curve
Figure 9. Charging Chart for 3 ton Units
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75 80 85 90 95 100 105110 115120 125 130 135
Liquid Pressure (psig)
Liquid Temperature (F)
X36KA Charging Chart - Cooling
Add refrigerant when below curve
Remove refrigerant when above curve
14
REFRIGERANT CHARGING CHARTS - CONTINUED
Figure 10. Charging Chart for 4 ton Units
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75 80 85 90 95 100 105110 115120 125 130 135
Liquid Pressure (psig)
Liquid Temperature (F)
X48KA Charging Chart - Cooling
Add refrigerant when below curve
Remove refrigerant when above curve
Figure 11. Charging Chart for 5 ton Units
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75 80 85 90 95 100 105 110115 120 125 130 135
Liquid Pressure (psig)
Liquid Temperature (F)
X60KA Charging Chart - Cooling
Add refrigerant when below curve
Remove refrigerant when above curve
15
3 AMP
FUSE
COMPRESSOR
OUTDOOR
FAN MOTOR
DUAL
CAPACITOR
S
R
C
L2 L1
T2 T1
COMPRESSOR
CONTACTOR
24V
COM
HIGH PRESSURE
SWITCH
240V
LOW
PRESSURE
SWITCH
S
R
C
5
4
3
2
1
9
8
7
6
COM NO
NC
F
H
C
HIGH SPEED
TRANSFORMER
BLUE
ORANGE
RED
BLACK
BLACK
YELLOW
YELLOW
YL/BK
YELLOW
24V
Y2 HIGH SPEED
YL/BK
R
C
G
W1
W2
Y1
Y2
5
4
3
2
1
N
G
L
C
BLOWER
MOTOR
GREEN/YELLOW
BLUE
YELLOW
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 V a la terre.
7112720
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
Packaged Air Conditioner - Single Phase
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 V to ground.
4. For replacement wires use conductors suitable for 105° C.
5. See installation instructions for blower motor airflow settings
YELLOW
RED
GREEN
BROWN
ORANGE
BLACK
RED
BLACK
BROWN
RED
WHITE
ORANGE
GREY
RED
YELLOW
BLACK
YELLOW
BLACK
BLUE
0812
Figure 12. Wiring Diagram for 2 & 3 Ton Units
WIRING DIAGRAMS
16
3 AMP
FUSE
COMPRESSOR
DUAL
CAPACITOR
S
R
C
COMPRESSOR
CONTACTOR
24V
HIGH PRESSURE
SWITCH
LOW
PRESSURE
SWITCH
5
4
3
2
1
9
8
7
6
L2 L1
T2 T1
COM NO
NC
COM
240V
F
H
C
HIGH SPEED
TRANSFORMER
RED
BLACK
YELLOW
YELLOW
YL/BK
YELLOW
24V
Y2 HIGH SPEED
R
C
G
W1
W2
Y1
Y2
WHITE
YELLOW
BROWN
BLACK
BLUE
YL/BK
5
4
3
2
1
N
G
L
C
BLOWER
MOTOR
3
2
1
N
G
L
OUTDOOR
FAN
MOTOR
GREEN/YELLOW
BLUE
YELLOW
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 V a la terre.
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
Packaged Air Conditioner - Single Phase
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 V to ground.
4. For replacement wires use conductors suitable for 105° C.
5. See installation instructions for blower motor airflow settings
YELLOW
RED
GREEN
BROWN
ORANGE
BLACK
RED
BLACK
BROWN
RED
WHITE
ORANGE
GREEN/YELLOW
GREY
YELLOW
RED
YELLOW
BLACK
YELLOW
BLACK
BLUE
7112730
0812
Figure 13. Wiring Diagram for 4 & 5 Ton Units
17
18
19
INSTALLATION / PERFORMANCE CHECK LIST
REFRIGERATION SYSTEM
Was unit given 24 hr warm up period
for crankcase heaters (if applicable)?
YES NO
Stage-1 Liquid Pressure (high side) ________________________
Stage-1 Suction Pressure (low side) ________________________
Has the owner’s information been
reviewed with the customer?
YES NO
Has the Literature Package been left
with the unit?
YES NO
INSTALLATION ADDRESS:
CITY ______________________ STATE _________________
UNIT MODEL # ________________________________________
UNIT SERIAL # _______________________________________
Unit Installed Minimum clearances
per Figure 1 (page 4)?
YES NO
INSTALLER NAME:
CITY ______________________
STATE ________________
PROPOSITION 65 WARNING: This product
contains chemicals known to the state of
California to cause cancer, birth defects or
other reproductive harm.
WARNING:
ELECTRICAL SYSTEM
Electrical connections tight? YES NO
Line voltage polarity correct? YES NO
Rated Voltage: ___________________________________VOLTS
L1-L2 Volts: _____________________________________VOLTS
Has the thermostat been calibrated? YES NO
Is the thermostat level? YES NO
Is the heat anticipator setting correct?
(If Applicable)
YES NO
IMPORTANT - This product has been designed and manufactured to
meet ENERGY STAR criteria for energy efficiency. However, proper
refrigerant charge and proper air ow are critical to achieve rated
capacity and efficiency. Installation of this product should follow the
manufacturer’srefrigerantchargingandairowinstructions.Failureto
conrmproperchargeandairowmayreduceenergyefciencyand
shorten equipment life.
7094650 (NEW)
Specifications & illustrations subject to change without notice or incurring obligations.
O’ Fallon, MO | Printed in U.S.A. (10/12)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Broan P5RF-X60K and Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI