Tough Leads Professional Remote Control Switch User manual

Type
User manual

Tough Leads Professional Remote Control Switch grants you wireless control over your dust extractor with a DoL Motor Starter. Easily mount the control unit, connect the control cable, and pair additional remotes for a convenient and safe operation. Utilize the adjustable off delay feature to ensure clear ducting before shutdown, ranging from 0.1 seconds to 3 hours. The remote control unit also includes a STOP button that physically locks when pressed, enhancing safety.

Tough Leads Professional Remote Control Switch grants you wireless control over your dust extractor with a DoL Motor Starter. Easily mount the control unit, connect the control cable, and pair additional remotes for a convenient and safe operation. Utilize the adjustable off delay feature to ensure clear ducting before shutdown, ranging from 0.1 seconds to 3 hours. The remote control unit also includes a STOP button that physically locks when pressed, enhancing safety.

Installation and User Manual
Professional Remote
C
DoL Motor Starter
Installation
Instructions
Step 1 -
Ensure dust extractor is isol
Step 2 - Mount the
remote control unit
Remove the front cover.
Screw to a suitable surface.
Step 3 - Fit the control cable:
Unscrew the
DoL starter cover
Identifying a suitable position for the remote control cable gland.
Drill hole, insert gland and tighten in position.
Strip sufficient outer sheath from the control cable and thread through gland.
Step 4 -
Wire up the control cable
Connect cable 1 (live in) to a permanent live supply, fused at a max of 16A.
Connect cable 2 (neu
Connect cables 3 and 4 in
Connect cables 5 and 6 in
wire to be removed from a terminal on the STO
5, whilst wire 6 is connected to the terminal from which it was removed. It does not
matter which side of the STOP switch this occurs.
Check all new connections.
Replace the DoL starter
V1.3 22/05/2022
Installation and User Manual
C
ontrol Switch for E
xtractors with
Instructions
Ensure dust extractor is isol
a
ted from the mains supply. Use test equipment to verify.
remote control unit
:
Remove the front cover.
Screw to a suitable surface.
DoL starter cover
.
Identifying a suitable position for the remote control cable gland.
Drill hole, insert gland and tighten in position.
Strip sufficient outer sheath from the control cable and thread through gland.
Wire up the control cable
:
Connect cable 1 (live in) to a permanent live supply, fused at a max of 16A.
tral in) to a suitable neutral.
Connect cables 3 and 4 in
parallel
accross the START button N/O switch terminals.
Connect cables 5 and 6 in
series
to the STOP button N/C terminals. This will require a
wire to be removed from a terminal on the STO
P button and connected directly to wire
5, whilst wire 6 is connected to the terminal from which it was removed. It does not
matter which side of the STOP switch this occurs.
Check all new connections.
Replace the DoL starter
and remove control covers.
Installation and User Manual
xtractors with
a
ted from the mains supply. Use test equipment to verify.
Strip sufficient outer sheath from the control cable and thread through gland.
Connect cable 1 (live in) to a permanent live supply, fused at a max of 16A.
accross the START button N/O switch terminals.
to the STOP button N/C terminals. This will require a
P button and connected directly to wire
5, whilst wire 6 is connected to the terminal from which it was removed. It does not
Step 5 - Test:
Turn on the power to the extractor.
Ensure that STOP button on the remote unit is twisted into the on position (it locks off
when pressed)
Test that the extractor DoL starter START and STOP buttons operate normally.
Turn the extractor
on and press the STOP button on the remote unit to check that it
stops the extractor.
Untwist to unlock.
Press the ON and OFF buttons on the remote control fob to check that they operate
the extractor. Repeat for any additional fobs or switches.
Buttons o
n the extractor DoL starter, remote control unit and remote control fob can be
pressed in any order.
Pairing Additional Remotes
Within the remote control enclosure is a small black box
button.
With power connected to the unit, press the button on the black box once.
will flash
once and then remain on.
Press the module pairing button firmly once.
remain on.
Press the ON button
on the remote.
indicator will flash 3 times, remaining continually on after the third flash.
P
ress the OFF button on the remote.
the indicator will flash 3 tim
To completely clear all paired remotes, press the button 8 times.
The unit will only operate with remotes which have a separate ON and OFF button
s
ingle button remotes are not compatible.
Adjusting or Removing
The unit
is supplied with a 10 second off delay. This means that when the OFF button is
pressed on any remote, the extractor will run for a further 10 seconds from this time.
The purpose of an extractor off delay is to
clear before it shuts down.
The delay can adjusted
to between 0.1 seconds and 3 hours using the dials on the
timer.
With the power disconnected, use a small screw driver to adjust the dials to acheive the
required off delay.
The bottom dial selects the function of the timer, and is supplied set at D (delay off).
The top dial selects the maxium time.
The middle dial allows
finer a
time applied. 1=10%,
5=50% e.g.:
o
To select 10 seconds, turn the top dial to 10s and the middle to 10.
o
To select 30 seconds, turn the top dial to 1m and the middle to 5 e.g. it operates
at 50% of the selected 1m.
o To
select the shortest possible delay of
and the middle to 1.
Pairing button and indicator
V1.3 22/05/2022
Turn on the power to the extractor.
Ensure that STOP button on the remote unit is twisted into the on position (it locks off
Test that the extractor DoL starter START and STOP buttons operate normally.
on and press the STOP button on the remote unit to check that it
Untwist to unlock.
Press the ON and OFF buttons on the remote control fob to check that they operate
the extractor. Repeat for any additional fobs or switches.
n the extractor DoL starter, remote control unit and remote control fob can be
Pairing Additional Remotes
Within the remote control enclosure is a small black box
on the far right,
With power connected to the unit, press the button on the black box once.
once and then remain on.
Press the module pairing button firmly once.
The indicator will flash once and then
on the remote.
When the ON button has been sucesfully paired the
indicator will flash 3 times, remaining continually on after the third flash.
ress the OFF button on the remote.
When the OFF button has been sucesfully paired
the indicator will flash 3 tim
es, turning off after the third flash.
To completely clear all paired remotes, press the button 8 times.
The unit will only operate with remotes which have a separate ON and OFF button
ingle button remotes are not compatible.
Adjusting or Removing
the Off Delay
is supplied with a 10 second off delay. This means that when the OFF button is
pressed on any remote, the extractor will run for a further 10 seconds from this time.
The purpose of an extractor off delay is to
ensure that the ducting at the furthest point is
clear before it shuts down.
to between 0.1 seconds and 3 hours using the dials on the
With the power disconnected, use a small screw driver to adjust the dials to acheive the
The bottom dial selects the function of the timer, and is supplied set at D (delay off).
The top dial selects the maxium time.
finer a
djusted of the time, by selected the
percentage of the top
5=50% e.g.:
To select 10 seconds, turn the top dial to 10s and the middle to 10.
To select 30 seconds, turn the top dial to 1m and the middle to 5 e.g. it operates
at 50% of the selected 1m.
select the shortest possible delay of
just 0.1 seconds turn
the top dial to 1s
and the middle to 1.
Pairing button and indicator
Ensure that STOP button on the remote unit is twisted into the on position (it locks off
Test that the extractor DoL starter START and STOP buttons operate normally.
on and press the STOP button on the remote unit to check that it
Press the ON and OFF buttons on the remote control fob to check that they operate
n the extractor DoL starter, remote control unit and remote control fob can be
on the far right,
with a single
With power connected to the unit, press the button on the black box once.
The indicator
The indicator will flash once and then
When the ON button has been sucesfully paired the
indicator will flash 3 times, remaining continually on after the third flash.
When the OFF button has been sucesfully paired
The unit will only operate with remotes which have a separate ON and OFF button
;
is supplied with a 10 second off delay. This means that when the OFF button is
pressed on any remote, the extractor will run for a further 10 seconds from this time.
ensure that the ducting at the furthest point is
to between 0.1 seconds and 3 hours using the dials on the
With the power disconnected, use a small screw driver to adjust the dials to acheive the
The bottom dial selects the function of the timer, and is supplied set at D (delay off).
percentage of the top
To select 10 seconds, turn the top dial to 10s and the middle to 10.
To select 30 seconds, turn the top dial to 1m and the middle to 5 e.g. it operates
the top dial to 1s
V1.3 22/05/2022
If an off delay is not required and even 0.1 seconds is too long, the delay can be
removed completely by turning the bottom dial to B. With this function you must also
select 1s on the top dial and 5 on the middle dial. The time set in the B function is the
length of the off pulse sent to the DoL starter, not the off delay. Failure to adjust the time
when using function B may result in an excessively long off pulse, preventing the
extractor from being started until the end of the pulse.
← Time period
← Percentage of time period applied
← Timer function. D for time delay, B for no delay
Operating Instructions
Pressing the START button on the DoL starter will still start the extractor. With the
remote unit installed, pressing the ON button on any of the remotes sends a 0.5
second ON pulse to the DoL starter, to minic manually pressing the START button.
Pressing the STOP button on the DoL starter will continue to stop the extractor.
Pressing the OFF button on any of the remotes sends a 0.5 second OFF pulse to the
DoL starter, to minic manually pressing the STOP button.
In addition, the red STOP button on the remote control unit also stops the extractor.
Note that red button locks in the off position when pressed and must be twisted to
release it before the extractor will start again.
The buttons on the DoL starter and remotes can be pressed in any order to control the
extractor.
Ensure that the extractor is isolated at the mains before services etc, as it may start at
any time through the remote control fobs.
V1.3 22/05/2022
Wiring Diagram
Three Phase Example
4
5
6
3
X
Disconnect wire from
switch and connect
directly to wire 5.
Wires 3 and 4
are connected
in parallel to
the start
switch
1
2
1 (Live in) to permanent live supply
(fused at 16A max)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Tough Leads Professional Remote Control Switch User manual

Type
User manual

Tough Leads Professional Remote Control Switch grants you wireless control over your dust extractor with a DoL Motor Starter. Easily mount the control unit, connect the control cable, and pair additional remotes for a convenient and safe operation. Utilize the adjustable off delay feature to ensure clear ducting before shutdown, ranging from 0.1 seconds to 3 hours. The remote control unit also includes a STOP button that physically locks when pressed, enhancing safety.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI