  • Hello! I am an AI chatbot trained to assist you with the Generac 30kW RD03024ADSS User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
4 3 2 1
4 3 1
A
B
A
B
843 [32.2]
CENTER OF
GRAVITY
77 [3.0]
1952 [76.8]
OVERALL LENGTH
214 [8.4]
1800 [70.9]
888 [35.0]
OVERALL WIDTH
1369
[53.9]
OVERALL
HEIGHT
146 [5.7]
173 [6.8]
758 [29.8]
DOOR TYP
TITLE
INSTALL PROTECTOR D2.4L SW
ISSUE DATE:
SIZE CAGE NO DWG NO
0K4893A
REV
B
A
SCALE
0.050
WT-KG SHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2
REV
A
WINDCHILL VERSION
A.1
SERVICE ITEM 2.4L
OIL FILL CAP RIGHT SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER RIGHT SIDE
OIL DRAIN HOSE RIGHT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
AIR CLEANER ELEMENT LEFT SIDE
MUFFLER FRONT
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN (STEEL ENCL) 751 [1655]
WITH WOODEN SHIPPING SKID 787 [1735]
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2261 (89") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H2O.
9. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
LEFT SIDE VIEW
LIFTING PROVISION (4 PLACES)
SEE NOTE 9 AND CENTER OF GRAVITY DIMENSIONS
VISE ACTION LATCH,
ONE PER DOOR, ONE LIFT-OFF
DOOR PER SIDE OF GENERATOR
FRONT VIEW
RIGHT SIDE VIEW
EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE
REAR ENCLOSURE COVER
PANEL
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
REAR TANK COVER
SEE NOTE 4
RADIATOR/EXHAUST
DISCHARGE AIR
CUSTOMER ACCESS
ASSEMBLY. CONTROL PANEL
ACCESS. BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
TOP VIEW
BATTERY 12 VOLT
NEGATIVE GROUND
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
AIR INTAKE
(BOTH SIDES)
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
B
4 3 2 1
4 3 1
A
B
A
B
313 [12.3]
197 [7.7]
STUB-UP
AREA
675 [26.6] TYP
1275 [50.2] TYP
1875 [73.8] TYP
1036 [40.8]
1184 [46.6]
16.7 [.66]
MOUNTING HOLES
(8 PLACES)
181 [7.1]
TYP
888
[35.0]
818 [32.2]
913 [36.0]
1421 [56.0]
1544 [60.8]
1754 [69.0]
149 [5.9]
267 [10.5]
TYP
621 [24.5]
TYP
757 [29.8]
TYP
19 [.7] 851 [33.5] TYP
75 [2.9]
1952 [76.8]
55
[2.2]
8
[.3]
162 [6.4]
782 [30.8]
STUB-UP
AREA
850 [33.5]
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
TITLE
INSTALL STUB-UP VIEW PROTECTOR D2.4L
SW TANK
ISSUE DATE:
SIZE CAGE NO DWG NO
0K4893A
REV
B
A
SCALE
0.075
WT-KG SHEET
2 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
SH
2/2
REV
A
WINDCHILL VERSION
A.1
FUEL TANK
TOTAL CAPACITY 253.6 [67]
USABLE CAPACITY 230.9 [61]
CAPACITY: LITER [GALLONS]
DIMENSIONS: MM [INCH]
HIGH AND LOW VOLTAGE
STUB-UP AREA
CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER
CONNECTION OPENING
FUEL FILL
(2" NPT FEMALE)
FUEL LEVEL
GAUGE/SENDER
FUEL RETURN
FUEL SUPPLY
INNER TANK NORMAL VENT
(2" NPT FEMALE)
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
REMOVABLE
STUB-UP COVER
/