2
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TABLE OF CONTENTS
TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
For the Home or Business Owner: . . . . . . . . . . . . . . 4
For the Installing Dealer/Contractor: . . . . . . . . . . . . . 4
Owner Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . 4
Equipment Description. . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Delivery Inspection . . . . . . . . . . . . . . . . . . . . . . . . 5
Shipment Contents . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring Interconnections . . . . . . . . . . . . . . . . 6-7
SYSTEM OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TESTING THE AUTOMATIC TRANSFER SWITCH . . . . 8
Automatic Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Utility Fail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Engine Warm-Up . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Utility Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Retransfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Engine Cool Down . . . . . . . . . . . . . . . . . . . . . . . . 8
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Model 01813 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Model 01814 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
When Calling The Factory . . . . . . . . . . . . . . . . . . . . . . 8
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DIAGRAMS, EXPLODED VIEWS, PARTS LISTS . . . . . 10-13
NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
SAFETY RULES
This is the safety alert symbol. It is used to
alert you to potential personal injury
hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
The safety alert symbol ( ) is used with a signal word
(DANGER, CAUTION,WARNING), a pictorial and/or a
safety message to alert you to hazards. DANGER indicates
a hazard which, if not avoided, will result in death or
serious injury. WARNING indicates a hazard which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, might
result in minor or moderate injury. CAUTION, when
used without the alert symbol, indicates a situation that
could result in equipment damage. Follow safety messages
to avoid or reduce the risk of injury or death.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard.The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others.You must also make sure that the
procedure, work method or operating technique that you
choose does not render the transfer switch unsafe.
DO NOT touch bare wires or receptacles.
DO NOT use transfer switch with worn, frayed, bare or
otherwise damaged wiring.
DO NOT handle electrical cords while standing in water,
while barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand on
an insulated dry surface to reduce shock hazard.
DO NOT allow unqualified persons or children to operate or
service transfer switch.
In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact local
authorities. Avoid direct contact with the victim.
Failure to properly ground transfer switch can
result in electrocution.
WARNING
Only qualified electricians should attempt installation
of this system, which must strictly comply with
applicable codes, standards and regulations.
WARNING
Use transfer switch only for intended uses.
If you have questions about intended use, ask dealer or
contact Briggs and Stratton Power Products.
DO NOT expose transfer switch to excessive moisture, dust,
dirt, or corrosive vapors.
Despite the safe design of the transfer switch, operating this
equipment imprudently, neglecting its maintenance or being
careless can cause possible injury or death.
Remain alert at all times while working on this equipment.
NEVER work on the equipment when you are physically or
mentally fatigued.
If connected devices overheat, turn them off and turn off their
circuit breaker/fuse.
Improper treatment of transfer switch can damage it
and shorten its life.
CAUTION
4
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
INTRODUCTION
Thank you for your purchase of this Briggs & Stratton
Power Products Automatic Transfer Switch.This product is
intended for use with Briggs & Stratton Home Standby
Generator sets ONLY.This is an optional home standby
system which provides an alternate source of electric
power and to serve loads such as heating, refrigeration
systems, and communication systems that, when stopped
during any power outage, could cause discomfort, or the
like.This product DOES NOT qualify for emergency
standby as defined by NFPA 70 (NEC).
Briggs and Stratton Power Products (BSPP) has made every
effort to provide for a safe, streamlined and cost-effective
installation. Each installation is unique, it is impossible to
know of and advise of all conceivable procedures and
methods by which installation might be achieved.We could
not know of possible hazards and/or the results of each
method or procedure. For these reasons,
Only licensed electrical contractors should
install transfer switches. Installations must
strictly comply with all applicable federal,
state and local codes, standards and
regulations.
Your BSPP Transfer Switch is supplied with this combined
“Installation and Owner’s Manual”.This is an important
document and should be retained by the owner after the
installation has been completed.
Every effort has been expended to make sure that the
information in this manual is both accurate and current.
However, the manufacturer reserves the right to change,
alter or otherwise improve the system at any time without
prior notice.
For the Home or Business Owner
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand the
Owner Orientation Section of this manual
BEFORE
contracting or starting
your transfer switch installation.
To arrange for proper installation, contact the store at
which you purchased your BSPP Transfer Switch, your
dealer, or your utility power provider.
The Transfer Switch Warranty is VOID
unless the system is installed by a
licensed electrical professional.
For the Installing Dealer/Contractor
Check federal, state and local codes for questions on
installation.
If you need more information about the transfer switch,
call 1-800-743-4115, between 8:00 AM and 5:00 PM CT.
Owner Orientation
The illustrations are for typical circumstances and are
meant to familiarize you with the installation options
available with your transfer switch.
Local codes, appearance, and distances are the factors that
must be considered when negotiating with an installation
professional.As the distance from the existing electrical
service increases, compensation in wiring materials must be
allowed for.This is necessary to comply with local codes
and overcome electrical voltage drops.
The factors mentioned above will have a direct effect
on the overall price of your transfer switch installation.
NOTE: Your installer must check local codes AND obtain
permits before installing the system.
Read and follow the instructions given in this manual.
Follow a regular schedule in caring for and using your
transfer switch, as specified in the manual.
Installer Responsibilities
Read and observe the safety rules.
Read and follow the instructions given in this manual.
Check federal, state and local codes.
5
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
Equipment Description
These switches are a new generation of transfer switches
that are intended to transfer the entire load of normal
residential installations.The load is connected either to
utility power (normal) or home standby power
(emergency).The transfer switch monitors utility and
generator voltages and will automatically connect to the
appropriate source of power.
Major components of the transfer switch are a 2 pole
double throw transfer switch, control circuit board, fused
utility terminals and interconnecting wiring.
The transfer switch is solenoid-operated from utility or
generator inputs and contain suitable mechanical and
electrical interlock switches to eliminate the possibility of
connecting the utility service to the generator output. It
has ratings capable of switching full utility power into the
residence. In addition, a manual override lever is provided
for the transfer function.
The control circuit board has active circuits sensing utility
and generator voltages. It creates a signal for the generator
start-up, switch transfer, retransfer when utility is restored
and generator cool down periods.The control board also
contains red and green LED’s indicating the power sources
available and two relay operated contacts that provide
supervisory control of external loads.
INSTALLATION
Unpacking
Delivery Inspection
After removing the carton, carefully inspect the transfer
switch components for any damage that may have occurred
during shipment.
IMPORTANT: If loss or damage is noted at time of
delivery, have the person(s) making delivery note all damage
on the freight bill and affix his signature under the
consignor's memo of loss or damage. If loss or damage is
noted after delivery, contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Shipment Contents
Automatic Power Transfer Switch
Installation and Owner’s Manual
Mounting Dimensions
Figure 1 depicts the physical size and mounting hole
locations of the NEMA 3R automatic transfer switch
enclosure.This enclosure is suitable for indoor/outdoor use.
The transfer switch enclosure is commonly secured
through the predrilled holes, as shown.
Figure 1 — Automatic Power Transfer Switch Dimensions
Model 01813
Model 01814
Enclosure Dimensions
Mounting Dimensions
Enclosure Dimensions
Mounting Dimensions
6
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
Mounting Guidelines
The Automatic Transfer Switch is enclosed in a NEMA Type
3R enclosure suitable for indoor/outdoor use. Guidelines for
mounting the Automatic Transfer Switch include:
Install the switch on a firm, sturdy supporting structure.
The switch must be installed with minimum NEMA 3R
hardware for conduit connections.
To prevent switch contact distortion, level and plumb the
enclosure.This can be done by placing washers between
the switch enclosure and the mounting surface.
NEVER install the switch where any corrosive substance
might drip onto the enclosure.
Protect the switch at all times against excessive moisture,
dust, dirt, lint, construction grit and corrosive vapors.
A typical installation of the Automatic Power Transfer
Switch is depicted in Figure 2. It is best if it is mounted
near the utility meter, either inside or outside. Discuss
layout suggestions/changes with the owner before beginning
the system installation process.
Power Wiring Interconnections
All wiring must be the proper size, properly supported and
protected by conduit.
Complete the following connections between the transfer
switch, main distribution panel, utility power and generator
(Figure 3, on next page).
1. Ensure utility power is turned OFF. Connect utility
power supply leads to transfer switch terminals
marked “UTILITY CONNECTION”.
2. Connect utility neutral to the transfer switch
“NEUTRAL” terminal.
3. Connect main distribution panel power leads to transfer
switch terminals marked “LOAD CONNECTION”.
4. Connect main distribution panel neutral lead to
transfer switch “NEUTRAL” terminal.
5. Connect generator power supply leads from the
generator’s control panel to transfer switch terminals
marked “GENERATOR CONNECTION”.
6. Connect generator Neutral from the control panel to
the transfer switch “NEUTRAL” terminal.
7. Connect generator “GND” from the control panel to
the transfer switch “GND” terminal.
8. Connect main distribution panel “GND” to the
transfer switch “GND” terminal.
9. Connect generator utility 240 VAC terminals to
transfer switch utility 240 VAC terminals.
10. Terminal strip on control module in transfer switch has
four connections for customer use.There are two sets
of “Normally Closed” contacts available.They will be
activated when generator power is required.These can
be used for supervisory control of large connected
loads on generator, for example, disconnecting air
conditioner, water heater, etc. or an alarm source.
11. Tighten all wire connections/fasteners to proper torque.
Failure to follow above warning could cause damage and/or
malfunction of equipment.
Low voltage wire cannot be installed in same conduit
as power voltage wiring.
CAUTION
Figure 2 — A Typical Transfer Switch Mounting
Main
Breaker
Panel
Transfer Switch
Generator
Service
Disconnect
Watt-
Hourmeter
7
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
Figure 3 — A Typical Installation Diagram for Transfer Switch
MODEL 01813
MODEL 01814
Main
Main Distribution Panel
Ground Bus
Neutral
Bus
To Generator
Neutral
Terminal
To Utility Power
Normally
Closed
Contacts
Load
Connection
Ground Lug
Generator
Connection
Utility
Connection
Main
Main Distribution Panel
Ground Bus
Neutral
Bus
To Generator
Neutral
Terminal
To Utility Power
Normally
Closed
Contacts
Load
Connection
Ground Lug
Generator
Connection
Utility
Connection
8
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
SYSTEM OPERATION
To select automatic transfer operation, do the following:
1. Set service disconnect switch that sends utility power
to transfer switch to On” position.
2. Set generator’s main circuit breaker to its On
position.
3. Install 15 Amp fuse in control panel on generator.
4. Set AUTO/OFF/MANUAL switch on generator to
AUTO” position.
The system will now be in automatic operation mode.
TESTING THE
AUTOMATIC TRANSFER
SWITCH
Turn the service disconnect feeding the transfer switch, to
the “Off” position.The automatic sequence will follow.To
go back to utility power, turn the service disconnect to the
On” position.
Automatic Sequence
Utility Fail
Utility voltage sensor senses when utility voltage is below
70 percent of nominal. Engine start sequence is initiated
after 6 second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer
fixed at 20 seconds or 50 seconds with optional cold
weather package.
Transfer
Transfers from utility to standby supply occurs after
standby voltage is above set levels. Minimum engine run
time is 4 minutes after transfer.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from standby to utility supply 10 seconds after
utility voltage supply is above pickup level.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
Specifications
UL® 1008 Listed Transfer Switch
Model 01813
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 100 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz
Fault Current Rating . . . . . . . . . . 22,000 RMS Symmetrical
Amperes
Supervisory Contacts Rating . . . 5 Amp, 125 Volt AC
Weight . . . . . . . . . . . . . . . . . . . . . 21 lbs.
Model 01814
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 200 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz
Fault Current Rating . . . . . . . . . . 25,000 RMS Symmetrical
Amperes
Supervisory Contacts Rating . . . 5 Amp, 125 Volt AC
Weight . . . . . . . . . . . . . . . . . . . . . 34 lbs.
When Calling the Factory
Before contacting Briggs and Stratton Power Products
regarding service or repair of this transfer switch, obtain
the Model Number and Serial Number from the unit data
decal located on or inside the case.
To contact Briggs and Stratton Power Products call
1-800-743-4115, between 8:00 AM and 5:00 PM CT.
9
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TROUBLESHOOTING
Problem
Automatic transfer switch does
not transfer to generator
Automatic transfer switch does
not transfer to utility
Generator is still running after
switch transfers to utility power
Supervised loads (air conditioner,
etc.) are not operating when
utility is present
Cause
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Service disconnect breaker open.
2. Utility voltage not acceptable.
Engine cool down period.
NC contacts not operating correctly.
Correction
1. Reset generator circuit breaker.
2. Refer to generator manual.
1. Reset service disconnect breaker.
2. Wait for utility voltage to return
to normal.
Engine should stop after 1 minute.
Check NC contact for proper
operation and/or check control wiring
to external load.
10
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TRANSFER SWITCH SCHEMATIC
11
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TRANSFER SWITCH WIRING DIAGRAM
12
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TRANSFER SWITCH EXPLODED VIEW & PARTS LIST
Item Part # Description
1 192154GS ENCLOSURE
2 192155GS BACK PANEL
3 191995GS TRANSFER SWITCH, 100A, with
Cover & Handle
4 36701GS SCREW
5 36903GS SCREW
6 36905GS SCREW
7 36933GS SCREW
8 193159GS DECAL, Reinstall After
9 191668GS CONTROL, Board
10 192701GS SPACER, Nylon
11 B4856GS LUG, Ground
12 22097GS WASHER, Lock
13 22473GS WASHER
14 22127GS NUT
15 190841GS TERMINAL, Neutral
16 B4857GS FUSE
Item Part # Description
17 192151GS HOLDER, Fuse
18 192557GS STANDOFF, Purse Lock
19 190850GS DECAL,ATS, BSPP
20 192702GS DECAL,Term Strip
21 B5106GS DECAL, Connection, Utility
22 B5107GS DECAL, Connection, Generator
23 192688GS DECAL, 100A,ATS
24 192690GS DECAL, UL Listed, 100A,ATS
25 190992GS DECAL,Warning Shock
26 190984GS DECAL, Fuse
27 B4986GS DECAL, Ground
28 192597GS DECAL, Utility, 240V AC
29 192165GS DECAL,APPVD CB
30 193307GS DECAL, Load
31 23897GS WASHER
32 23762GS WASHER
33 36901GS SCREW
MODEL 01813
13
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TRANSFER SWITCH EXPLODED VIEW & PARTS LIST
Item Part # Description
1 192156GS ENCLOSURE
2 192170GS BACK PANEL
3 192024GS TRANSFER SWITCH, 200A, with
Cover & Handle
4 36701GS SCREW
5 36903GS SCREW
6 36905GS SCREW
7 36901GS SCREW
8 193159GS DECAL, Reinstall After
9 191668GS CONTROL, Board
10 192701GS SPACER, Nylon
11 B4856GS LUG, Ground
12 22097GS WASHER, Lock
13 22473GS WASHER
14 22127GS NUT
15 192696GS TERMINAL, Neutral
16 B4857GS FUSE
Item Part # Description
17 192151GS HOLDER, Fuse
18 192557GS STANDOFF, Purse Lock
19 190850GS DECAL,ATS, BSPP
20 192702GS DECAL,Term Strip
21 B5106GS DECAL, Connection, Utility
22 B5107GS DECAL, Connection, Generator
23 192689GS DECAL, 200A,ATS
24 192691GS DECAL, UL Listed, 200A,ATS
25 190992GS DECAL,Warning Shock
26 190984GS DECAL, Fuse
27 B4986GS DECAL, Ground
28 192597GS DECAL, Utility 240V AC
29 192166GS DECAL,APPVD CB
30 193307GS DECAL, Load
31 23897GS WASHER
32 23762GS WASHER
MODEL 01814
14
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
NOTES
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC EQUIPMENT OWNER WARRANTY POLICY
LIMITED WARRANTY
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s), of the equipment that is defective in material
or workmanship or both. Transportation charges on parts submitted for repair or replacement under this warranty must be borne by
purchaser. This warranty is effective for the time periods and subject to the conditions stated below. For warranty service, find the nearest
Authorized Service Dealer in our dealer locator map at www.briggspowerproducts.com.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW ANY
AND ALL IMPLIED WARRANTIES ARE EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED
TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some states or countries do not allow limitations on how long an implied warranty
lasts, and some states or countries do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation
and exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state
to state or country to country.
OUR EQUIPMENT*
OUTBOARD
MOTOR
PRESSURE
WASHER
WATER PUMP
(Not available in the
USA)
PORTABLE
GENERATOR
WELDER
Less tthan 110 KKW Less tthan 110 KKW
TRANSFER
SWITCH
2 years
none
1 year
90 days
1 year
90 days
2 years
1 year
2 years
1 year
3 years or
1500 hours
1 year
WARRANTY PERIOD**
HOME GENERATOR SYSTEM
(Includes Transfer Switch, if sold with equipment.)
Consumer Use
Commercial Use
* The engine and starting batteries are warranted solely by the manufacturers of those products.
** 2 years for all consumer products in the European Union. Parts only on 2nd year for consumer use of Portable Generator and
Home Generator System - Less than 10 KW, outside of European Union.
The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time
stated in the table above. “Consumer use" means personal residential household use by a retail consumer. “Commercial use" means all other
uses, including use for commercial, income producing or rental purposes. Once equipment has experienced commercial use, it shall thereafter
be considered as commercial use for purposes of this warranty. Equipment used for Prime Power in place of utility are not applicable to
this warranty. Electric Powered Pressure Washers used for commercial purposes are not warranted.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR
PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY
SERVICE IS REQUESTED, THE MANUFACTURING DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY
PERIOD.
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most
warranty repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not
apply if equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper installation.
Similarly, the warranty is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered
or modified. During the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to
be defective under normal use and service. This warranty will not cover the following repairs and equipment:
Normal Wear: Outdoor Power Equipment, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not
cover repair when normal use has exhausted the life of a part or the equipment.
Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized
installation or alteration and modification, misuse, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as,
in our judgment, to adversely affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments,
fuel system cleaning and obstruction (due to chemical, dirt, carbon, lime, etc.).
Other Exclusions: This warranty excludes wear items such as quick couplers, oil gauges, belts, o-rings, filters, pump packing, etc., pumps that
have been run without water supplied or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or improper servicing
or freezing or chemical deterioration. Accessory parts such as guns, hoses, wands and nozzles are excluded from the product warranty. Also
excluded is used, reconditioned, and demonstration equipment; equipment used for prime power in place of utility power and equipment used in
life support applications.
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
JEFFERSON, WI, USA
Effective January 1, 2003 replaces all undated Warranties and all Warranties dated before January 1, 2003
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Briggs & Stratton 01813-0 User manual

Category
Juice makers
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI