Samsung AM056FN1DEH/TL Installation guide

Category
Split-system air conditioners
Type
Installation guide

This manual is also suitable for

This product is RoHS compliant
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 32 2014-10-16 오후 2:58:54
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
Cassette Type
1 Way cassette : AM

FN1DEH
EN ES PT
DB68-04174A-03
This manual is made with 100% recycled paper.
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 33 2014-10-16 오후 2:58:54
2
Contents
Safety Precautions
(Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.)
WARNING
Always disconnect the air conditioner from the power supply before servicing it or
accessing its internal components.
Verify that installation and testing operations are performed by qualified personnel.
Verify that the air conditioner is not installed in an easily accessible area.
General information
Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order to be
able to use it as reference after installation.
For maximum safety, installers should always carefully read the following warnings.
Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the
air conditioner is sold or transferred.
This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types of units
with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for
damages arising from the use of non compliant units.
The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper connection of electric
and hydraulic lines. Failure to comply with these instructions or to comply with the requirements set forth in the Operating limits
table, included in the manual, shall immediately invalidate the warranty.
The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable to be
installed in areas used for laundry.
Do not use the units if damaged. If problems occur, switch the unit off and disconnect it from the power supply.
In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact SAMSUNGs
technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations should be
performed by qualified personnel only.
The unit contains moving parts, which should always be kept out of the reach of children.
Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may cause
electric shocks or fires.
Do not place containers with liquids or other objects on the unit.
All the materials used for the manufacture and packaging of the air conditioner are recyclable.
The packing material and exhaust batteries of the remote control(optional) must be disposed of in accordance with current laws.
The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air conditioner
must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly and safely.
Q
Safety Precautions ................................................................................................2
Q
Accessories ...............................................................................................................4
Q
Selecting the Installation Location ...............................................................4
Q
Indoor Unit Installation ......................................................................................6
Q
Purging the Unit ...................................................................................................8
Q
Connecting the Refrigerant Pipe ...................................................................9
Q
Cutting/Flaring the Pipes ............................................................................... 10
Q
Performing Leak Test & Insulation .............................................................. 11
Q
Drain pipe and Drain Hose Installation .................................................... 13
Q
Wiring Work .......................................................................................................... 16
Q
Setting an indoor unit address and installation option ................... 19
Q
Final Checks and User Tips ............................................................................. 28
Q
Troubleshooting ................................................................................................. 29
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 2 2014-10-16 오후 2:58:44
3
ENGLISH
Safety Precautions(Continued)
installinG the unit
IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines.
Always disassemble the electric lines before the refrigerant tubes.
Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged,
DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has
collected the material from the retailer.)
After completing the installation, always carry out a functional test and provide the instructions on how to operate
the air conditioner to the user.
Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid
the occurrence of fires, explosions or injuries.
The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable to be
installed in areas used for laundry.
Our units must be installed in compliance with the spaces indicated in the installation manual to ensure either accessibility from
both sides or ability to perform routine maintenance and repairs. The units components must be accessible and that can be
disassembled in conditions of complete safety either for people or things.
For this reason, where it is not observed as indicated into the Installation Manual, the cost necessary to reach and repair the unit
( in safety, as required by current regulations in force) with slings, trucks, scaffolding or any other means of elevation won’t be
considered in-warranty and charged to end user.
Power suPPly line, fuse or circuit breaker
Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance
with current local safety standards.
Always verify that a suitable grounding connection is available.
Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient
to ensure the operation of any other domestic appliance connected to the same electric lines.
Always verify that the cut-off and protection switches are suitably dimensioned.
Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring
diagram included in the manual.
Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric specifications
and with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable
to the installation of air conditioners.
Make sure that you earth the cables.
- Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire.
If earthing is not complete, electric shock or fire may occur.
Install the circuit breaker.
- If the circuit breaker is not installed, electric shock or fire may occur.
Make sure that the condensed water dripping from the drain hose runs out properly and safely.
Install the power cable and communication cable of the indoor and outdoor unit at least 1m away
from the electric appliance.
Install the indoor unit away from lighting apparatus using the ballast.
- If you use the wireless remote control, reception error may occur due to the ballast of the lighting
apparatus.
Do not install the air conditioner in following places.
- Place where there is mineral oil or arsenic acid. Resin parts flame and the accessories may drop or
water may leak. The capacity of the heat exchanger may reduce or the air conditioner may be out
of order.
- The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
The copper pipe or connection pipe may corrode and refrigerant may leak.
- The place where there is a machine that generates electromagnetic waves. The air conditioner
may not operate normally due to control system.
- The place where there is a danger of existing combustible gas, carbon fiber or flammable dust.
The place where thinner or gasoline is handled. Gas may leak and it may cause fire.
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 3 2014-10-16 오후 2:58:44
4
Wireless Remote Control-Buttons and DisplayAccessories
Selecting the Installation Location
The following accessories are supplied with the indoor unit.
The type and quantity may differ depending on the specifications.
AMFN1DEH
Pattern sheet
Insulation drain
Flexible hose
Grommet Rubber
Insulation Base
Manual
Indoor Unit
There must be no obstacles near the air inlet and outlet.
Install the indoor unit on a ceiling that can support its weight.
Maintain sufficient clearance around the indoor unit.
Make sure that the water dripping from the drain hose runs away
correctly and safely.
The indoor unit must be installed in this way, that they are out of public
access. (Not touchable by the users)
Rigid wall without vibration.
Where it is not exposed to direct sunshine.
Where the air filter can be removed and cleaned easily.
As a rule, the unit cannot be installed at a height of less than 2.5 m.
It is possible to install the unit at a height of between 2.2~2.5m from
the ground, if the unit has a duct with a well defined length (300mm or
more) to avoid fan motor blower contact.
If you install the cassette or duct type indoor unit on the ceiling with
humidity over 80%, you must apply extra 10mm of polyethylene foam
or other insulation with similar material on the body of the indoor unit.
Space Requirements for Indoor Unit
AMFN1DEH
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 4 2014-10-16 오후 2:58:44
5
ENGLISH
Wireless Remote Control-Buttons and Display
The following accessories are supplied with the indoor unit.
The type and quantity may differ depending on the specifications.
Pattern sheet
Insulation drain
Flexible hose
Grommet Rubber
Insulation Base
Manual
Unit : mm
Dimension of the indoor unit
No. Name Description
Liquid pipe connection
AM056FN1****
: ø6.35 (1/4”)
AM071FN1****
: ø9.52 (3/8”)
Gas pipe connection
AM056FN1****
: ø12.70 (1/2”)
AM071FN1****
: ø15.88 (5/8”)
Drain pipe connection OD ø29, ID ø25
Power supply connection -
Air discharge grille -
Air suction grille -
AM056/071FN1DEH
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 5 2014-10-16 오후 2:58:47
6
Wireless Remote Control-Buttons and Display
Concrete
Suspension bolt(ø9.52 or M10)
Hole in anchor
Hole in plug
Insert
Ceiling support
It is recommended to install the Y-joint before installing the indoor unit.
1
Place the pattern on the ground and place the marking. With the help of
laser, place the bolt location on ceiling.
Since the diagram is made of paper, it may shrink or stretch
slightly due to temperature or humidity. For this reason,
before drilling the holes maintain the correct dimensions
between the markings.
Note
2
Use the bolt of sizer 8 ~ 10mm
3
Install the suspension bolts depending on the ceiling type.
Ensure that the ceiling is strong enough to support
the weight of the indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
If length of the bolt is more that 1.5 m, additional cross is
required in opposite bolts.
If this is not possible, create an opening on the false ceiling
in order to be able to use it to perform the required operations
on the indoor unit.
Indoor Unit Installation
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 6 2014-10-16 오후 2:58:47
7
ENGLISH
Wireless Remote Control-Buttons and Display
Indoor Unit Installation
4
Use check nut along with main nut on each bolt.
You must install the suspension bolts more than four when
installing the indoor unit.
5
Check the level of the indoor unit by using a leveler.
A tilt of the indoor unit may cause malfunction of a built-in float switch
and water leaks.
6
Adjust the height of the indoor unit by using jigs.
You should adjust the jigs and the pattern sheet to fit the cutting
dimensions of ceiling.
Noise may occur if you do not adjust the location of the indoor unit
according to location of the jigs during installation.
- Adjust the location of the indoor unit according to the jigs.
Make sure that the indoor unit is installed in level. If the indoor unit
slants too much, there can be water leaks from drain pan.
AM056/071FN1DEH
7
Tighten the upper part nuts.
8
Remove the jigs after installing the indoor unit.
Level
Nut
Washer
Rubber
Fasten the nut
CeilingGauge of Dimensions
15mm
15mm
Air
inlet
Air
outlet
Indoor Unit
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 7 2014-10-16 오후 2:58:48
8
Wireless Remote Control-Buttons and DisplayPurging the Unit
Gas refrigerant
port
Liquid refrigerant port
g The designs and shape are subject to
change according to the model.
From factory the unit is supplied and set with a pre-charge of nitrogen gas
(insert gas). Therefore, all insert gas must be purged before connecting the
assembly piping.
Unscrew the pinch pipe at the end of each refrigerant pipe.
Result: All inert gas escapes from the indoor unit.
Note To prevent dirt or foreign objects from getting into the pipes
during installation, do NOT remove the pinch pipe completely
until you are ready to connect the piping.
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 8 2014-10-16 오후 2:58:48
9
ENGLISH
Wireless Remote Control-Buttons and DisplayConnecting the Refrigerant Pipe
There are two refrigerant pipes of differing diameters:
A smaller one for the liquid refrigerant
A larger one for the gas refrigerant
The inside of copper pipe must be clean & has no dust.
1 Before connecting the reprigerant pipe, open the cover side.
2 Remove the pinch pipe on the pipes and connect the assembly pipes
to each pipe, tightening the nuts, first manually and then with a torque
wrench, a spanner applying the following torque.
Outer Diameter
(mm)
Torque
kgf•cm N•m
6.35 140~180 14~18
9.52 350~430 34~42
12.70 500~620 49~61
15.88 690~830 68~82
Must apply refrigerant oil on the flaring area to prevent
a leak.
Note
3 Be sure that there must be no crack or kink on the bended area.
Connect the indoor and outdoor units using pipes with flared
connections(not supplied). For the lines, use insulated, unwelded,
degreased and deoxidized copper pipe,(Cu DHP type to ISO 1337),
suitable for operating pressures of at least 4200kPa and for a burst
pressure of at least 20700kPa. Copper pipe for hydro-sanitary
applications is completely unsuitable.
For sizing and limits (height difference, line length, max. bends,
refrigerant charge, etc.) see the outdoor unit installation manual.
All refrigerant connection must be accessible, in order to permit either
unit maintenance or removing it completely.
Refrigerant oil
Torque wrench
Flare nut
Union
Spanner
Cover side
g The designs and shape are subject to
change according to the model.
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 9 2014-10-16 오후 2:58:48
10
Wireless Remote Control-Buttons and Display
1
Make sure that you prepared the required tools.
(tube cutter, reamer/ scrapper, flaring tool and pipe holder are for R410A refrigerant)
2
If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut
edge remains at 90° with the side of the pipe. There are some
examples of correctly and incorrectly cut edges below.
Oblique Rough Burr
3
To prevent a gas leak, remove all burrs at the cut edge of the pipe using a
reamer/ scrapper.
4
Carry out flaring work using flaring tool as shown below.
Flaring tool
Clutch type Wing nut type
A
Die
Copper pipe
Yoke
Die
Copper pipe
Flare nut
Outer diameter
[D (mm)]
Depth [A (mm)]
Flare tool for
R-410A clutch type
Conventional flare tool
Clutch type Wing nut type
6.35
0~0.5 1.0~1.5 1.5~2.0
9.52
0~0.5 1.0~1.5 1.5~2.0
12.70
0~0.5 1.0~1.5 1.5~2.0
15.88
0~0.5 1.0~1.5 1.5~2.0
5
Check if you flared the pipe correctly. There are some examples of
incorrectly flared pipes below.
InclinedCorrect Damaged Surface Cracked Uneven Thickness
6
Align the pipes and tighten the flare nuts first manually and then with a torque
wrench, applying the following torque.
Outer
diameter
(mm)
Connection
Torque
Flare dimension
(mm)
Flare shape
(mm)
kgf•cm N•m
6.35 140~180 14~18 8.70~ 9.10
9.52 350~430 34~42 12.80 ~13.20
12.70 500~620 49~61 16.20 ~16.60
15.88 690~830 68~82 19.30 ~19.70
R 0.4~0.8
90° ±
45°
±
In case of needing brazing, you must work with Nitrogen gas blowing.
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 10 2014-10-16 오후 2:58:48
11
ENGLISH
Wireless Remote Control-Buttons and DisplayPerforming Leak Test & Insulation
g The designs and shape are subject to
change according to the model.
Leak check
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before creating vacuum and
circulating the R-410A, it’s responsible of installer to pressurize the whole
system with nitrogen (using a pressure regulator) at a pressure above
4.1MPa/ 550 PSI (gauge).
LEAK TEST WITH R-410A (after opening valves)
Before opening valves, discharge all the nitrogen into the system and
create vacuum. After opening valves check leaks using a leak detector for
refrigerant R-410A.
Leak test
Insulation
Once you have checked that there are no leaks in the system,
you can insulate the piping and hose.
1
To avoid condensation problems, place T13.0 or thicker Acrylonitrile
Butadien Rubber separately around each refrigerant pipe.
Note Always make the seam of pipes face upwards.
2
Wind insulating tape around the pipes and drain hose avoiding to compress
the insulation too much.
3
Finish wrapping insulation (Closed Cell Elastomeric Nitrile Rubber Insulation)
around the rest of the pipes leading to the outdoor unit.
4
The pipes and electrical cables connecting the indoor unit with the outdoor
unit must be fixed/ supported to the wall/ ceiling supports with suitable
fixtures.
No gap
NBR(T13.0 or thicker)
All refrigerant connection must be accessible, in order to permit
either unit maintenance or removing it completely.
Discharge all the nitrogen to create a vacuum and charge
the system.
Insulation cover pipe
Indoor unit
Be sure to overlap
the insulation
Must fit tightly against body
without any gap.
Insulation pipe
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 11 2014-10-16 오후 2:58:48
12
Wireless Remote Control-Buttons and DisplayPerforming Leak Test & Insulation (Continued)
5
Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe referring to the thickness
according to the pipe size.
Indoor temperature of 30°C and humidity of 85% is the standard condition.
If installing in a high humidity condition, use one grade thicker insulator by
referring to the table below.
If installing in an unfavorable conditions, use thicker one.
Insulator’s heat-resistance temperature should be more than 120°C.
Pipe
Pipe size
Insulation Type (Heating/Cooling)
Remarks
Standard
[30°C, 85%]
High humidity
[30°C, over 85%]
EPDM,NBR
Liquid
pipe
Ø6.35 ~ Ø9.52 9t
Internal temperature
is higher than 120°C
Ø12.7 ~ Ø50.80 13t
Gas
pipe
Ø6.35 13t 19t
Ø9.5225.40
19t
25t
Ø28.58~Ø44.45 32t
Ø50.80 25t 38t
When installing insulation in places and conditions below, use the same insulation
that is used for high humidity conditions.
<Geological condition>
- High humidity places such as shoreline, hot spring, near lake or river, and
ridge (when the part of the building is covered by earth and sand.)
<Operation purpose condition>
- Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
- The ceiling frequently exposed to moisture and cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory and studio or near an
exit that opens and closes frequently.
- The place where the pipe is installed is highly humid due to the lack of
ventilation system.
Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU
You can contact the gas side and liquid side pipes but the pipes
should not be pressed.
When contacting the gas side and gas side pipe, use 1 grade thicker
insulator.
Refrigerant pipe after EEV kit and MCU
Install the gas side and liquid side pipes, leave 10mm of space.
When contacting the gas side and liquid side pipe, use 1 grade
thicker insulator.
Gas pipe
10mm
Liquid pipe
Gas pipe
Liquid pipe
Insulation
Insulation
10mm 10mm10mm
Install the insulation not to get wider and use the adhesives
on the connection part of it to prevent moisture from entering.
Wind the refrigerant pipe with insulation tape if it is exposed to
outside sunlight.
Install the refrigerant pipe respecting that the insulation does not
get thinner on the bent part or hanger of pipe.
Add the additional insulation if the insulation plate gets thinner.
Additional insulation
Hanger
Refrigerant pipe insulation
a×3
a
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 12 2014-10-16 오후 2:58:48
13
ENGLISH
Wireless Remote Control-Buttons and DisplayDrain pipe and Drain Hose Installation
Insulation drainpipe
Band
Band
Flexible
hose
Drain
hose
port
Drainpipe
Adhesives
Insulation cover band
Insulation cover drain
Band(Not supplied)
Indoor
Unit
Drain hose port
Care must be taken when installing the drainpipe and drain hose for the indoor unit so
that condensate water is drained correctly outside.
1
Fix the flexible hose to the drainpipe.
The connection port of the flexible hose and PVC drainpipe must be fixed
with PVC adhesives.
Check out that the connected part doesnt leak.
Drain pipe type :
VP20
2
Connect the flexible hose to the drain hose port.
Make sure that a rubber ring is installed on the drain hose port.
Drain hose port location differs depending on the unit types.
3
Install the drain pipe as shortly as possible.
Give a slightly slant to the drainpipe for proper drainage of condensate
water.
There must be no gap on the connected part so that the drainpipe is
not separated from the flexible hose.
4
Insulate the drainpipe, and then fix it as indicated.
Whole drainpipe should be insulated by 5t(or more) insulation to prevent
water condensation.
Drainpipe
Flexible hose
AMFN1DEH
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 13 2014-10-16 오후 2:58:48
14
Wireless Remote Control-Buttons and Display
Drainpipe Connection
1
The drain pipe should be installed within 100mm from the flexible hose,
lift up from 100mm to 550mm and lift down 20mm or more.
2
Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger
space of 1~1.5m.
3
Install the air vent in the horizontal drainpipe to prevent water flow back to
the indoor unit.
You may not need to install it if there were proper slope in the
horizontal drainpipe.
Note
4
The flexible hose should not be installed upward position, it may cause
water flow back to the indoor unit.
5
Install U-trap at the end of the drainpipe to prevent a nasty smell to reach
the indoor unit.
Flexible hose
Air vent
300mm or less
Horizontal drainpipe
more than 1/100 slope
100~550mm
or less
1~1.5m
100mm
or more
Ceiling
Hanger
Centralized Drainage
1
Install main air vent at the front of the farthest indoor unit from the main
drain when installed indoor units are more than 3.
2
You may need to install individual air vent to prevent water flow back at the
top of each indoor unit drainpipe.
Hanger
Main drainpipe
Individual
air vent
Main air vent
Centralized horizontal drainpipe
(more than 1/100 slope)
550mm or less
1~1.5m
Max. allowable axis gap
Max. 20mm
Indoor
Unit
Install horizontally
Be horizontal
Indoor
Unit
Flexible hose
Max. allowable bending angle
Max. 3
Indoor
Unit
Handle with using adhesive not to block the
inside of flexible hose
Connect to
PVC drain
pipe
Connect to
indoor unit
Insulation
PVC
drain pipe
(Apply
adhesive on
the inside)
Insulation
Flexible hose
(Apply adhesive on
the outside)
g Flexible hose Installation
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 14 2014-10-16 오후 2:58:49
15
ENGLISH
Wireless Remote Control-Buttons and Display
1
Install main air vent at the front of the farthest indoor unit from the main
drain when installed indoor units are more than 3.
2
You may need to install individual air vent to prevent water flow back at the
top of each indoor unit drainpipe.
550mm or less
Testing the Drainage
You should test drainage after completing the installation.
Prepare a little water about 1.0 liter.
1
Open the cover water supply intake.
2
Pour water into the water supply intake.
3
Operate the unit in the Cool mode and check a drain pump pumping.
4
Check drain water drops at the end of the drainpipe.
Drainpipe
Drain water drops
5
Make sure there is no water leak at the drainage.
6
When you finished the test, close the coverside.
When maintaining the air conditioner, remove condensate water
remained in the drain pan by using a drain port for maintenance.
Leveler
Air outlet
AMFN1DEH
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 15 2014-10-16 오후 2:58:49
16
Wireless Remote Control-Buttons and Display
Silver solder
N L
N L N L N L
Indoor Unit 1
Outdoor Unit
Indoor Unit 2 Indoor Unit 3
Wired Remote
Control
220-240V~
h
ELB : Essential Installation
EEV kit
Indoor Unit 4 Indoor Unit 5 Indoor Unit 6
h
Ceiling, wall-mounted indoor unit.
Selecting compressed ring terminal
1
Before wiring work, you must turn off all power source.
2
Indoor unit power should be supplied through the breaker(MCCB, ELB) separated by the outdoor power.
3
The power cable should be used only copper wires.
4
Connect the power cable{1(L), 2(N)} among the units within maximum length and communication cable(F1, F2) each.
5
Connect F3, F4(for communication) when installing the wired remote Control.
Power and communication cable connection
Norminal
dimen-
sions for
cable
(mm
2
)
Norminal
dimensions for
screw (mm)
B D d1 E F L d2 t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min. Min. Max.
Standard
dimension
(mm)
Allowance
(mm)
Min.
1.5
4 6.6
±0.2 3.4
+0.3
-0.2
1.7 ±0.2 4.1 6 16 4.3
+0.2
0
0.7
4 8
2.5
4 6.6
±0.2 4.2
+0.3
-0.2
2.3 ±0.2 6 6 17.5 4.3
+0.2
0
0.8
4 8.5
4 4 9.5 ±0.2 5.6
+0.3
-0.2
3.4 ±0.2 6 5 20 4.3
+0.2
0
0.9
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 16 2014-10-16 오후 2:58:49
17
ENGLISH
Wireless Remote Control-Buttons and Display
h Rating current
Unit Model
Rating
current
AMFN1DEH

056


071

0.28A
0.40A
Specification of electronic wire
Power supply MCCB ELB Power cable Earth cable
Communication
cable
Max : 242V
Min : 198V
X A
X A, 30mmA
0.1 s
2.5mm
2
2.5mm
2
0.75~1.5mm
2
Decide the capacity of ELB and MCCB by below formula.
The capacity of ELB, MCCB X [A] = 1.25 X 1.1 X
Ai
X
: The capacity of ELB, MCCB
Ai : Sum of Rating currents of each indoor unit.
Refer to each installation manual about the rating current of indoor unit.
Decide the power cable specification and maximum
length within 10% power drop among indoor units.
Coef: 1.55
Lk: Distance among each indoor unit[m], Ak: Power cable specification[mm
2
]
ik : Running current of each unit[A]
∑ (
Coef×35.6×L
k×ik
) <
10% of input
voltage[V]
1000×A
k
n
k=1
Example of Installation
- Total power cable length L = 100(m), Running current of each units 1[A]
- Total 10 indoor units were installed
10[A]
Indoor unit10
20[m]10[m]0[m]
9[A] 1[A]
100[m]
MCCB
Indoor unit2Indoor unit1
ELB
Apply following equation.
∑ (
Coef×35.6×L
k×ik
) <
10% of input
voltage[V]
1000×A
k
n
k=1
h Calculation
Installing with 1 sort wire.
220[V]
-2.2[V] -2.0[V]
············ 2.5[mm
2
] ············
208.8[V](Within 198V~242V)
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2[V]
it's okay
2.5[mm
2
] 2.5[mm
2
]
Installing with 2 different sort wire.
220[V]
-1.4[V] -1.2[V]
············ 2.5[mm
2
] ············
209.5[V](Within 198V~242V)
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5[V]
it's okay
4.0[mm
2
] 4.0[mm
2
]
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 17 2014-10-16 오후 2:58:49
18
Wireless Remote Control-Buttons and Display
Select the power cable in accordance with relevant local and national
regulations.
Wire size must comply with local and national code.
Power Supply cords of parts of appliances for outdoor use shall not be lighter
than polychloroprene sheathed flexible cord. (Code designation IEC:60245 IEC
57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
You should connect the power cable into the power cable terminal
and fasten it with a clamp.
The unbalanced power must be maintained within 10% of supply
rating among whole indoor units.
If the power is unbalanced greatly, it may shorten the life of the
condenser. If the unbalanced power is exceeded over 10% of supply
rating, the indoor unit is protected, stopped and the error mode
indicates.
To protect the product from water and possible shock, you should keep
the power cable and the connection cord of the indoor and outdoor
units in the iron pipe.
Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be incorporated
in the fixed wiring(≥3mm).
You must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and
communication cable.
Maximum length of power cables are decided within 10% of power
drop. If it exceeds, you must consider another power supplying
method.
The circuit breaker(MCCB, ELB) should be considered more capacity
if many indoor units are connected from one breaker.
Use round pressure terminal for connections to the power terminal
block.
For wiring, use the designated power cable and connect it firmly,
then secure to prevent outside pressure being exerted on the terminal
board.
Use an appropriate screwdriver for tightening the terminal screws.
A screwdriver with a small head will strip the head and make proper
tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the terminal screws.
Tightening torque
N
m kgf
cm
M3.5 0.8~1.2 8.0~12.0
M4 1.2~1.8 12.0~18.0
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 18 2014-10-16 오후 2:58:49
19
ENGLISH
Wireless Remote Control-Buttons and DisplaySetting an indoor unit address and installation option
Set the indoor unit address and installation option with remote controller option.
Set the each option separately since you cannot set the ADDRESS setting and indoor
unit installation setting option at the same time. You need to set twice when setting
indoor unit address and installation option.
The procedure of option setting
Step 1. Entering mode to set option
1. Remove batteries from the remote controller.
2. Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button.
3. Check if you have entered the option setting status.
Step 2. The procedure of option setting
After entering the option setting status, select the option as listed below.
High Temp Button
High Fan Button
Mode change
Low Temp Button
Low Fan Button
Entering mode for
option setting
Option setting mode
Option setting is available from SEG1 to SEG 24
SEG1, SEG7, SEG13, SEG19 are not set as page option.
Set the SEG2~SEG6, SEG8~SEG12 as ON status and SEG14~18, SEG20~24 as
OFF status.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
0 X X X X X 1 X X X X X
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
2 X X X X X 3 X X X X X
On(SEG1~12) O(SEG13~24)
SAC_1way,2way NASA용 인도향_IM_EN_04174A-03.indd 19 2014-10-16 오후 2:58:49
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Samsung AM056FN1DEH/TL Installation guide

Category
Split-system air conditioners
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI