OJ Electronics F-NVP Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the OJ Electronics F-NVP Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
AnlægsfølerF-NVPF-16ertilmontagedirekte
pårør,f.eks.vedsikringmodkondens.
F-NVPF-16harindbygget680kohmmodstand
ogkantilsluttesF-NVPvia2terminaler.
VIGTIGT:FølerbåndetpåfølerneF-NVPF
ogF-NVPF-16måikkemonteresdirektepå
elektriskledendeoverflader,daderdervedkan
opståfejlfunktion.Skalfølerenfølepåelektrisk
ledendeoverflader,skaldermellemfølerbåndet
ogdenelektriskledendeoverflade,etableresen
ikke-ledendeisolering.
LimtypeF-NVPFLerenporøslim,hvorvand
kantrængeigennem.Forbrugca.0,3litertil25
mfølerbånd.
TILSLUTNING
Figur1.Tilslutningsdiagram
Figur2.Omsætningstabel
Figur3.Mål
OJ ELECTRONICS A/S
Stenager13B·DK-6400Sønderborg
Tel.:+4573121314·Fax:+4573121313
[email protected]·www.ojelectronics.com
English
APPLICATION
F-NVPmonitorswaterinstallationsetc.and
protectsequipmentsuchascomputerequipment
orothervalues.Acottonsensortapeis
suppliedwiththetheF-NVP.Thesensortapeis
suppliedbythemeterandismountedinthefloor
orwrapped/gluedtothewaterpipe.Onlyafew
humiditydropswillmaketheF-NVPalarm.
Furthermore,itcanbeusedtooversteer
regulationvalvesincoolingceilingsifcondense
arisesontubesorvalve.
PRODUCT PROGRAMME
Product Type
Humidityalarm230V,10Arelay F-NVP-15
24V,10Arelay F-NVP-35
HumidityalarmwithacousticalarmsignalF-NVP-16
Sensortapebythemeter F-NVPF
Unitsensor F-NVPF-16
Glueforsensortape NVDPFL
FUNCTION
F-NVPmeasurestheelectricalconductivityin
thesensorchosen.Whentheconductivityof
thesensorishigherthanthelevelsetonthe
F-NVP(whichhappenswhenthereishumidity
onthesensor)thebuilt-inrelay(F-NVP-15)is
activatedandredLEDindicatesalarm.Also,if
thesensorcircuitisshort-circuitedorbroken
therelaygoesinalarmposition.
Furthermore,F-NVPissuppliedwithaLEDfor
operation,whichwilllightgreen,ifthesupply
voltageisconnected.
TheF-NVP-16hasthesamefunction,but
whentherelaygoesinalarmpositionabuilt-in
acousticalarmisactivated.
CE MARKING
OJdeclareundertheirownresponsibility
thatthisproductmeetstherequirementsof
theEuropeanCouncil’sdirective89/336and
successivemodificationsastoelectro-magnetic
compatibilityandtheCouncildirective73/23
astoelectricalequipmenttobeappliedwithin
certainvoltageranges.
Standards applied
EN50081andEN50082.
Theproductmayonlybeenergisedwhenthe
entireinstallationmeetsthecurrentdirective
requirements.Whentheproductisinstalled
accordingtothisinstructionsguideandthe
currentinstallationguidelines,itiscovered
byfactoryguarantee.Iftheproducthasbeen
exposedtodamagee.g.intransport,itmust
becheckedandoverhauledbyqualifiedstaff
beforetheproductisconnectedtothepower.
TECHNICAL DATA
Supplyvoltage...... 24V,230V±10%,50-60Hz
Powerconsumption.....................................3VA
Weight ......................................................190g
Ambienttemperature......................... -20/+50°C
Sensitivity........................... 2-20µS,500-50kΩ
Sensorvoltage.................................Max.8VDC
Acousticalarm-F-NVP-16.................Ca.55dB
LED INDICATION
GreenLED:...............Supplyvoltageconnected
RedLED:.........Humidityalarmorsensorfailure
SENSOR F-NVPF
Thesensorconsistsofacottontapewhichis
deliveredbythemeterandwithtwointerwoven
wires.Thetwointerwovenwiresisconnectedin
theendbyaresistance.
Thesensorisconnectedtothealarmunit
F-NVPandincaseofhumidityonthesensor,
theconductivityisincreased(smallerresistance)
andaccordingtoadjustmentofsensitivitythe
built-inrelayisenergised(atthesametimethe
F-NVP-16givesanacousticalarm).
Thesensorwillgivealarmincaseofhumidity/
waterleakandshouldthereforenotbemounted
inadampposition,forinstanceconcretefloor/
wall,asafalsesignalmaythenarise.Incase
oflong-termhumidityinfluencethesensorwill
corrode,asgalvaniccorrosionwillarise.
Thesensorshouldbeplacedinsuchawaythat
itcanbechanged.Thesensortapemustnotbe
earthed.
GluetypeF-NVPFLisaporousglueandcan
bepenetratedbywater.Approx.0.3litresis
requiredfor25msensortape.
TheunitsensorF-NVPF-16isformounting
directontopipe,forinstancetosecureagainst
condensing.TheF-NVPF-16hasabuilt-in680
kΩresistanceandcanbeconnectedtothe
F-NVPvia2terminals.
IMPORTANT:ThesensortapeforF-NVPFand
F-NVPF-16sensorsmustnotbefitteddirectly
toelectricallyconductivesurfacesasthismay
causemalfunction.Ifthesensoristobeused
tomonitoranelectricallyconductivesurface,
non-conductiveinsulationmustbeestablished
betweenthesensortapeandtheelectrically
conductivesurface.
CONNECTION
Fig.1. Connectiondiagram
Fig.2 Conversationtable
Fig.3. Dimensions
Fig. 2
Fig. 3
F-NVP
F-NVPF-16
F-NVPF
Fig. 1
OBS!
Isolatesensorbandawayfrom
electricalleadingmaterial!
The trademark is registered and belongs to OJ Electronics A/S · © 2013 OJ Electronics A/S
/