Rosemount TankRadar Rex Commissioning Owner's manual

Type
Owner's manual
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
www.rosemount-tg.com
Commissioning Manual
Product Discontinued
www.rosemount-tg.com
Commissioning manual
Second edition
Revision B
Copyright
© June 2008
Rosemount Tank Radar AB
www.rosemount-tg.com
Copyright © June 2008
Rosemount Tank Radar AB
The contents, descriptions and specifications within this manual is
subject to change without notice. Rosemount Tank Radar AB accepts no
responsibility for any errors that may appear in this manual.
Trademarks
Rosemount, and the Rosemount logotype are registered trademarks of
Rosemount Inc.
TankRadar is a registered trademark of Rosemount Tank Radar AB.
HART is a registered trademark of HART Communication Foundation
Spare Parts
Any substitution of non-recognized spare parts may jeopardize safety.
Repair, e.g. substitution of components etc., may also jeopardize safety
and is under no circumstances allowed.
Rosemount Tank Radar AB will not take any responsibility for faults,
accidents, etc. caused by non-recognized spare parts or any repair
which is not made by Rosemount Tank Radar AB.
Specific FCC Requirements (USA only)
Rosemount TankRadar Rex generates and uses radio frequency energy.
If it is not installed and used properly, that is, in strict accordance with the
manufacturer´s instructions, it may violate FCC regulations on radio
frequency emission.
Rosemount TankRadar Rex has been FCC certified under test
conditions which assume a metallic tank. Installation on a non-metallic
tank is not certified, and is not allowed.
The FCC certificate for Rosemount TankRadar Rex requires that the
tank is closed as far as emitted radio energy is concerned. Tanks with
open manholes, external-floating-roof tanks without still-pipes etc. are
not covered by the certificate.
TOC-1
Rosemount TankRadar Rex
Table of Contents
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
Contents
1. CHECKS AND ADJUSTMENTS. . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.2 PREPARATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.3 TANK INTERIOR CONDITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.4 SYSTEM COMPOSITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.5 FCU CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.5.1 FCU information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.5.2 Visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.5.3 Electrical check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.5.4 Field bus check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.5.5 Group bus check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.5.6 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.6 FBM 2180 CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.6.1 FBM information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.6.2 Visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.6.3 Field bus check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.6.4 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.7 COMMUNICATION OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
1.8 RTG 3900 - GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . .1-6
1.8.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
1.8.2 Electrical check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
1.8.3 Tank measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-7
1.9 RTG 3920 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
1.9.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
1.9.2 Visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
1.9.3 Tank measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
1.9.4 Free space requirements . . . . . . . . . . . . . . . . . . . . . . . . .1-8
1.10 RTG 3930 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
1.10.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
1.10.2 Visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
1.10.3 Tank measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
1.10.4 Free space requirements . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Rosemount TankRadar Rex
Table of Contents
TOC-2
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.11 RTG 3950 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
1.11.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
1.11.2 Visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
1.11.3 Still-Pipe Requirements . . . . . . . . . . . . . . . . . . . . . . . . .1-13
1.11.4 Free space requirements . . . . . . . . . . . . . . . . . . . . . . . .1-13
1.12 RTG 3960 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-15
1.12.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-15
1.12.2 Visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-16
1.12.3 Still-Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-16
1.12.4 Verification Pins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-17
1.13 REX CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-19
1.13.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-19
1.13.2 Tank Distances and RTG Geometry . . . . . . . . . . . . . . . .1-19
1.13.3 Rex configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-20
1.13.4 Input Register parameters . . . . . . . . . . . . . . . . . . . . . . .1-21
1.13.5 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-22
1.14 DATA ACQUISITION UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-23
1.14.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-23
1.14.2 Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-23
1.14.3 Cable and Junction box . . . . . . . . . . . . . . . . . . . . . . . . .1-23
1.14.4 Electrical check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-23
1.14.5 Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-23
1.14.6 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-24
1.15 DAU CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-24
1.15.1 Tank Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-24
1.15.2 Temperature Check . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-24
1.15.3 Current inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-24
1.15.4 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-24
1.16 OPERATOR SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-25
1.16.1 TankMaster WinOpi . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-25
1.16.2 Back-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-25
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .INDEX-1
1-1
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1. Checks and Adjustments
1.1 General
Commissioning a Rex system aims at checking the mechanical and
electrical installations.
It includes calibrations and adjustments in order to achieve high
accuracy and reliability. The communication between various TRL/2 and
Rex units is checked, and necessary backups of database files etc. are
created. It also includes checking that the installations are done
according to safety regulations.
This manual provides brief descriptions of most of the items in the Check
List for Rosemount TankRadar Rex. The checklist is used as a guide
when commissioning a Rex system. When you need more information
on a certain item in the check list, read the corresponding section in this
chapter for further information.
Note! Before commissioning a Rex system, always read the Rex Installation
Manual (Document No. 308014), Rex Special Safety Instruction
(Document No. 308016), and Rex Safety Manual (SIL2; Document No.
308020).
1.2 Preparations
Check that the equipment is undamaged and that it corresponds to the
specifications. Note the following information:
Delivery no. the system number provided by the project depart-
ment at Emerson Process Management/Rosemount Tank
Gauging.
Name and location of plant.
Service agency: the name of the local agency responsible for the
installation.
Engineer responsible for the commissioning, and the date when
commissioning was concluded.
Note the tank distances needed for installation and configuration
of the Rosemount Tank Radar Rex system. See “Tank measure-
ments” on page 1-8 for illustrations of the different tank distances.
Note the addresses to be used for the communication between the
connected devices (RTG, DAU, FCU) and TankMaster.
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-2
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
Check that the correct hardware parts are installed.
Make sure that you bring appropriate tools and instruments.
Install TankMaster.
1.3 Tank Interior Conditions
Look for objects which may produce disturbing echoes like girders,
heating coils or agitators. Disturbing objects can severely affect the
accuracy of the measurements.
1.4 System Composition
Enter the following information about the system:
Number of tanks.
System Master. There may be several units acting as master at
different occasions. The system is supervised by TankMaster
(WinOpi). A portable service PC may temporarily be connected to
an FCU when system service is required (WinSetup). A host com-
puter can be connected to an FCU or to the TankMaster PC in
order to further process measured data (level, temperature, pres-
sure etc.).
The number of FCUs, FBMs, RTGs and DAUs.
1.5 FCU checklist
1.5.1 FCU information
Note the name, Unit ID
and address of each FCU.
This will facilitate the
configuration of the Rex
system. Check that the
Unit ID placed at the cover
of the FCU box and on the
FCU motherboard match.
Note the address which
will be used for the
different FCUs.
1.5.2 Visual check
The FCU is not intrinsically safe. It must therefore be installed in a
nonhazardous area.
Weather protection: make a note whether the FCU is placed in a
control room or another weather protected location.
Figure 1-1. Position of Unit ID on FCU
cover.
1-3
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.5.3 Electrical check
Power supply. Check that the switch inside the FCU box is set to
the correct value. 230 V is the default value. If 115 V is used, the
box on the nameplate "Mark box if re-wired for 115 VAC" shall be
marked.
Grounding: if there is no protective ground in the mains supply
cable, the FCU should be externally grounded via the ground con-
nection at the outside of the FCU box.
1.5.4 Field bus check
Use a shielded twisted pair cable with an area of at least 0.50 mm
2
for the TRL/2 bus.
Shielded cables are required in order to avoid crosstalk if the
cables run alongside and also to avoid other disturbances. The
field bus shield should be connected to ground at the FCU only.
Contact Emerson Process Management/Rosemount Tank
Gauging for further instructions.
Note the distance if there are two fieldbuses running in parallel.
1.5.5 Group bus check
Note the number of group buses that are used. The FCU can be
configured with two, three or four group bus ports.
Note whether the group bus communicates via the RS-232C or
the TRL/2 bus interface. By replacing the FCM board with an FCI
board, RS-485 communication can also be used.
1.5.6 Software
Note if redundant FCUs are used.
Note the FCU program version.
To view the FCU program version:
1 Select the FCU icon in the TankMaster WinSetup workspace.
2 Click the right mouse button and choose the Properties option.
3 Select the Communication tab.
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-4
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.6 FBM 2180 checklist
1.6.1 FBM information
Note the name and version of each FBM.
1.6.2 Visual check
Note if the FBM is installed outdoors or in the control room.
Check if there is anything in the surroundings which may disturb
the communication such as electromagnetic fields like radiators,
big motors and transformers.
1.6.3 Field bus check
Check that the TRL/2 bus is connected to socket 2 and 3. Use
twisted and shielded single pair cable with minimum cross sec-
tional area 0.50 mm
2
.
Table 1-1: Recommended wiring length
Connect the shield to terminal 1 or 4.
Connect ground cable to terminal 1 or 4.
1.6.4 Power supply
Do not use external power supply when the modem is connected
to the USB port. The USB interface itself supports power to the
FBM 2180 modem.
Cable dimension Maximum length
AWG 20 (0.50 mm
2
)
3000 m
AWG 18 (0.75 mm
2
)
4000 m
Figure 1-2 FBM 2180
TRL/2 bus
1-5
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.7 Communication overview
Make a simple drawing showing all tanks and installed units, see Figure
1-3. Include cable lengths. Describe the composition of tanks, Radar
Tank Gauges, Data Acquisition Units, Field Communication Units, Field
Bus Modems and system master. Try to provide as much detail as
possible. A complete view of the system including TankMaster WinOpi
and host computers should be provided, including information on which
Rex units the host computer is connected to.
Figure 1-3 Example of System Composition drawing.
TankMaster
WinOpi
Plant host
computer
FBM
FCU
FCU
Field bus
Field bus
RTG/
DAU
RTG/
DAU
RTG/
DAU
RTG/
DAU
RTG/
DAU
Portable
Service PC
Tank 1 Tank 2 Tank 3
Tank 4 Tank 5
Tank 6
Tank Group 1
Tank Group 2
Group Bus
(TRL/2 Bus)
RTG/
DAU
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-6
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.8 RTG 3900 - General information
1.8.1 Tank Information
Tank name
•Product in tank
Note the Unit ID, see Figure 1-4 It can also be found on the Signal
Processing Card (after C on the label). See TankRadar Rex Instal-
lation Manual Ed. 3 rev.B, chapter 3.1.1 for information on the
Transmitter Head Electronics Card.
Figure 1-4 Label with Unit ID.
1.8.2 Electrical check
RTG Power Supply: The 3900 Rex transmitter accepts 100-240
VAC, 50-60 Hz and max. 80 W. The built-in Transformer Rectifier
Card (TRC) automatically adapts to the connected supply voltage.
Optional: low voltage AC/DC versions (34-70 VAC/48-99 VDC).
Grounding: Certain national regulations requires protective
grounding of enclosure, see Special Safety Instruction for further
information. Special Safety Instruction is delivered together with
each Rex transmitter. Check with Emerson Process Management/
Rosemount Tank Gauging and/or local authorities if necessary.
Field bus continuity: Measure the resistance between leads 3
and 4. Resistance values between 1 and 20 Ω indicate that the
field bus cable is undamaged and correctly connected.
Field bus shield grounding: Check that the field bus shield is
connected to ground at the FCU only, and not at the RTG.
1-7
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.8.3 Tank measurements
Tank reference distance, R. The R distance is defined as the dis-
tance between the dipping datum point (zero level) and the tank
reference point.
RTG reference distance, G. G is the distance between the tank
reference point (hand dip nozzle) and the RTG reference point.
The RTG reference point is underneath the RTG flange, see Fig-
ure 1-5.
Minimum level distance, C. C is the distance between the dip-
ping datum point (zero level) and the bottom of the tank.
Note the distance (mm) from max product level to RTG reference
point.
Note! The G value is defined as positive if the Tank Reference point is located
above the RTG Reference point.
Figure 1-5 Tank distances.
Tank Reference Point
RTG Reference Point
Dipping Datum Point
(Zero Level)
Min. Level distance, C
RTG Ref.
distance, G
Tank Reference distance, R
RTG Reference
Point
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-8
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.9 RTG 3920
1.9.1 Tank Information
Check if there is water at the bottom of the tank.
1.9.2 Visual check
Free space below the RTG. Normally girders and pipes are not
allowed in the radar beam. If there are disturbing objects below the
antenna, the effect on the current measurement must be carefully
evaluated.
Check that waveguide, closing and antenna are mounted correctly
and take appropriate actions in order to replace broken parts.
1.9.3 Tank measurements
Diameter of the manhole and the socket height. The socket
must not be higher than 330 mm.
Note the distance X (mm) between the tank wall and the center of
the RTG. It will be used for calculations of the clearance angle
below the antenna.
1.9.4 Free space requirements
Check the Clearance Angle plumbline tankwall (arctan X/R). If
the clearance angle is less than 15°, the RTG must be inclined
away from the wall.
Figure 1-6 Inclination.
Antenna axis
30° radar beam
Vertical plumb line
Inclination 4° ±1°
Antenna axis
30° radar beam
Use the 4° flange if the
clearance angle is less
than 15°.
Vertical plumb
line
1-9
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
Inclination of RTG. Use
the 4° flange to direct the
radar beam 4° towards
the tank center if the
clearance angle is less
than 15°. For larger
clearance angles, the
gauge should be inclined
0°.
Sidewise angle:
0 ° ± 1°
(horizontal flange)
4 ° ± 1° (4 ° flange)
Figure 1-7 Clearance angle.
R
Figure 1-8 Sidewise angle.
Antenna axis
Sidewise angle:
0 ° ± 1° (horizontal flange)
4 ° ± 1° (4 ° flange)
Vertical plumb
line
Free passage
Clearance angle
X
Antenna axis
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-10
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.10 RTG 3930
1.10.1 Tank Information
Check if there is water at the bottom of the tank.
1.10.2 Visual check
Free space below the RTG. Normally girders and pipes are not
allowed in the radar beam. If there are disturbing objects below the
antenna, the effect on the current measurement must be carefully
evaluated.
Check that waveguide, closing, feeder and parabola are mounted
correctly and take appropriate actions in order to replace broken
parts.
1.10.3 Tank measurements
Diameter of the manhole and the socket height. If a 20" diame-
ter socket is used, the height of the socket must not exceed 0.6 m.
If the manhole is wider, the height of the socket may be corre-
spondingly higher as long as the requirement of a free passage
within 5° is fulfilled.
Note the distance X between the tankwall and the center of the
RTG. It will be used for calculations of the clearance angle below
the antenna.
Figure 1-9 RTG 3930.
1-11
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.10.4 Free space requirements
Check that the guide
pins on the TRL/2
adapter are directed
towards the center of
the tank. See TankRa-
dar Rex Installation
Manual Ed. 3 rev.B,
chapter 10.2.7 Mount-
ing the Antenna.
Check the Clearance
Angle between plum-
bline and tankwall
(arctan X/R). If the clear-
ance angle is less than
5°, the RTG must be
inclined 1.5° away from
the wall.
Inclination. The inclina-
tion of the gauge should
not exceed 1.5° towards
the center of the tank.
RTG 3930 is mounted
on the tank nozzle by
using the Flange Ball
which make it easy to
adjust the inclination.
Sidewise angle max 0.5°. Check that the flange is horizontal
within 3° along the tank wall.
Figure 1-11 Sidewise angle.
Figure 1-10 Inclination and Clear-
ance angle.
Antenna axis
R
Antenna axis
Sidewise angle
Vertical plumb
line
Free passage
Clearance angle
X
Inclination 1.5°
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-12
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.11 RTG 3950
1.11.1 Tank Information
Check if there is water at the bottom of the tank
1.11.2 Visual check
Check still-pipe (wildings, burrs, amount of rust, dirt and deposits).
Check that the RTG 3950 is installed according to the instructions
in the TankRadar Rex Installation Manual, chapter 10. Take
appropriate actions in order to replace any broken parts.
Figure 1-12 RTG 3950 Fixed and Inclined version.
1-13
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.11.3 Still-Pipe Requirements
Check the number of holes, distance between the holes (unit
meter) and the hole diameter (unit mm). It is important that the
area of the slots and holes not exceed the specified limits, see
Table 1-2.
Note the pipe inner diameter. It will be used when the RTG is con-
figured.
The still-pipe flange must be horizontal within ±2°.
The still-pipe must be vertical within 0.5° (0.2 m over 20 m).
Note! The topmost hole/slot in the still-pipe must be placed above maximum
product level.
1.11.4 Free space requirements
RTG 3950 Fixed Version
Figure 1-13 Free space requirements RTG 3950 Fixed Version
Pipe Dimension
(inch)
5681012
Max Area of Slots or
Holes (m
2
)
0,1 0.1 0.4 0.8 1.2
Table 1-2: Maximum area of the slots or holes
620 mm
700 mm
Min. 500 mm
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
1-14
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
RTG 3950 Inclined Version
Figure 1-14 Free space requirements RTG 3950 Inclined Version
Min. 500 mm 510 mm
590 mm
A
Make sure that there is sufficient
space to open the cover.
Pipe Size (in.) A (mm)
5430
6448
8480
10 518
12 545
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Rosemount TankRadar Rex Commissioning Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI