16kVA 0069490

Generac 16kVA 0069490 User manual

  • Hello! I am an AI chatbot trained to assist you with the Generac 16kVA 0069490 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the total capacity of the fuel tank?
    What is the usable capacity of the fuel tank?
    Which side houses the generator's oil filter?
    What kind of outlet is used for the 2-inch exhaust outlet?
    What is the minimum recommended concrete pad size for installation?
    How many lifting provisions does the generator have?
    Where is the circuit breaker information located?
    Where is the battery charger located?
    What is the overall height of the generator?
    What is the overall length of the generator?
4 3 2 1
4 3 1
A
B
A
B
735 [28.9]
CENTER OF GRAVITY
(SEE NOTE 5)
1236
[48.7]
OVERALL
HEIGHT
776
[30.6]
OVERALL VIEW
303
[11.9]
TYP
182
[7.2]
1065 [41.9]
1582 [62.3]
OVERALL LENGTH
212
[8.3]
110
[4.3]
630 [24.8]
DOOR TYP
SERVICE ITEM 2.3L
OIL FILL CAP RIGHT SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER RIGHT SIDE
OIL DRAIN HOSE RIGHT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
COOLANT RECOVERY BOTTLE LEFT SIDE
RADIATOR FILL CAP ACCESS ROOF TOP
AIR CLEANER ELEMENT EITHER SIDE
MUFFLER FRONT
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN 555 [1224]
WITH WODDEN SHIPPING SKID 594 [1310]
TITLE
INSTALL PROTECTOR D2.3L G16
SINGLE WALL TANK
ISSUE DATE: 06/2014
SIZE CAGE NO DWG NO
0K7394AY17
REV
B
N/A
A
SCALE
0.050
WT-KG SEE ABOVE SHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2
REV
A
WINDCHILL VERSION
A.1
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 1887 (74.3") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR STUB-UP AND REAR ENCLOSURE COVER PANELS TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,
NEUTRAL CONNECTION, AND BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES
AND ACCESSORY RELAY CONNECTION (QTY 4)
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
10. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW RESTRICTION REQUIREMENTS.
11. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
LEFT SIDE VIEW
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS,
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
REMOVABLE STUB-UP COVER
SEE NOTE 4
VISE ACTION LATCH,
ONE PER DOOR, ONE LIFT-OFF
DOOR PER SIDE OF GENERATOR.
EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE
TOP VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
REAR VIEW
CIRCUIT BREAKER
SEE NOTE 3
RIGHT SIDE VIEW
LIFTING PROVISION (4 PLACES)
SEE NOTES 5, 8 AND
CENTER OF GRAVITY
DIMENSIONS
RADIATOR/EXHAUST
DISCHARGE AIR
ENCLOSURE PANEL MUST
BE REMOVED TO FACILITATE
BATTERY INSTALLATION AND REMOVAL
BATTERY 12 VOLT
NEGATIVE GROUND
P/N: 058665
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
AIR INTAKE
(BOTH SIDES)
2" O.D. EXHAUST
OUTLET
4 3 2 1
4 3 1
A
B
A
B
251 [9.9]
FUEL TANK HT.
112
[4.4]
TYP
792 [31.2]
TYP
1472 [57.9]
TYP
354
[13.9]
739 [29.1]
MOUNTING CENTERS
19
[.7]
445 [17.5]
695 [27.4]
786 [31.0]
851 [33.5]
1007 [39.7]
1120 [44.1]
625
[24.6]
TYP
1368 [53.9] 169
[6.7]
STUB-UP
AREA
19
[.7]
100
[3.9]
9
[.4]
105
[4.1]
674
[26.5]
STUB-UP
AREA
1582 [62.3]
51
[2.0]
738 [29.1]
776 [30.6]
TITLE
INSTALL STUB-UP VIEW PROTECTOR D2.3L
SINGLE WALL TANK
ISSUE DATE: 06/2014
SIZE CAGE NO DWG NO
0K7394AY17
REV
B
N/A
A
SCALE
0.080
WT-KG SEE SHEET 1 SHEET
2 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
2/2
REV
A
WINDCHILL VERSION
A.1
FUEL TANK
TOTAL CAPACITY 169 [44]
USABLE CAPACITY 151 [40]
HIGH AND LOW
VOLTAGE
STUB-UP AREA
CIRCUIT BREAKER
NEUTRAL AND CUSTOMER
CONNECTION OPENING
CAPACITY: LITER [GALLON]
DIMENSIONS: MM [INCH]
TOP VIEW
LEFT SIDE VIEW
REAR VIEW
REMOVABLE STUB-UP COVER
SEE NOTE 4 ON
SHEET 1 OF 2
FUEL SUPPLY
FUEL
RETURN
FUEL LEVEL
GAUGE/SENDER
FUEL FILL
(2" NPT FEMALE)
EMERGENCY VENT
(2" NPT FEMALE)
NORMAL VENT
(2" NPT FEMALE)
16.66 [.66]
MOUNTING HOLES
6X
/