8 Operation
1. On a first stage call for heating or
cooling (Y1), the outdoor unit will modulate
according to the return air temperature.
The system will try to reach and maintain
the same temperature that satisfied the
last call. After 30 or 60 minutes (based
on the position of SW1-2), the unit will
increase its capacity to fulfill the demand,
regardless of the return air temperature.
Based on the capacity, the control will
enable up to three different fan speeds of
the air handler (G1,G2 and G3).
2. On a second stage call (Y2), the outdoor
unit will run at maximum capacity.
3. When the outdoor unit performs a defrost
cycle, the indoor fan will stop. The DF
output is activated and can be used to start
an auxiliary backup heater.
4. In heating mode, when the outside tempe-
rature drops, it may become more efficient
or more economical to stop the heat pump
and only use the auxiliary heating. The
control board can manage this switchover,
based on the position of the ENC2 switch.
Otherwise, the switchover is managed by
the position of dip switch SW1-3 and the
thermostat signals
5. If a malfunction occurs, an error code will
be displayed on the control board. Also,
24V output (L) and a dry contact (ALARM)
are activated.
Considerations
When pairing with a gas or oil furnace, or
in an add-on installation (coil installed in the
supply air of the air handler), it is important that
both heat pump and auxiliary heat do not work
simultaneously. To achieve this, the auxiliary
heat signal from the thermostat must go in the
W1 input terminal of the 24V adapter control.
When the indoor coil is installed in the return air
of the air handler (electric furnace), both heat
pump and auxiliary heater can run at the same
time. To achieve this, the auxiliary heat signal
from the thermostat needs to connect to the
E/AUX input terminal of the 24V adapter control.
8.1 Defrost
By default, the indoor fan will stop during a
defrost cycle. This is set by dip switch SW1-4
(see section 7).
To turn on the auxiliary heat during the
defrost cycle, DF of the control board must be
connected to Wof the furnace.
Manual Defrost
To force a defrost cycle, press and hold the
button KEY (next to ENC2) for three seconds. The
board will display and the defrost cycle will
commence.
8