Robur GAHP WS Installation, Use And Maintenance Manual

Type
Installation, Use And Maintenance Manual

This manual is also suitable for

Installation, use and maintenance manual
GAHP GS/WS
powered by gas and renewable energies
water/water gas absorption heat pump
This Installation, use and maintenance manual has been drawn up and printed by Robur S.p.A.; whole or partial
reproduction of this Installation, use and maintenance manual is prohibited.
The original is led at Robur S.p.A.
Any use of this Installation, use and maintenance manual other than for personal consultation must be previously
authorised by Robur S.p.A.
The rights of those who have legitimately led the registered trademarks contained within this publication are not
aected.
With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the
data and contents of this Installation, use and maintenance manual without prior notice.
Revision: V
Code: D-LBR509
DISPOSAL
The appliance and all its accessories must be disposed of separately in accordance with the regulations in force.
Use of the WEEE symbol (Waste Electrical and Electronic Equipment) indicates that this product cannot be disposed of as household waste.
Proper disposal of this product helps to prevent potential negative consequences for the environment and human health.
Installation, use and maintenance manual – GAHP GS/WS
3
INDEX OF CONTENTS
I Introduction .............................................................................
p.4
Recipients ..........................................................................
p.4
Control device ..................................................................
p.4
II Symbols and denitions ...............................................
p.4
II.1 Key to symbols .................................................................
p.4
II.2 Terms and denitions ....................................................
p.4
III Warnings......................................................................................
p.4
III.1 General and safety warnings ......................................
p.4
III.2 Conformity ........................................................................
p.6
III.3 Exclusions of liability and warranty ..........................
p.6
1 Features and technical data ......................................
p.7
1.1 Features ..............................................................................
p.7
1.2 Dimensions .......................................................................
p.8
1.3 Components ...................................................................
p.10
1.4 Electrical wiring diagram ...........................................
p.13
1.5 Electronic boards ..........................................................
p.13
1.6 Operation mode ............................................................
p.15
1.7 Controls ............................................................................
p.15
1.8 Technical characteristics .............................................
p.16
2 Transport and positioning ........................................
p.18
2.1 Warnings ..........................................................................
p.18
2.2 Handling ...........................................................................
p.18
2.3 Appliance position (outdoor version) ...................
p.18
2.4 Installation premises (indoor variant)....................
p.19
2.5 Minimum clearance distances..................................
p.19
2.6 Mounting base ...............................................................
p.19
3 Heating engineer ...............................................................
p.19
3.1 Warnings ..........................................................................
p.19
3.2 Hydraulic system ...........................................................
p.19
3.3 Hydraulic connections ................................................
p.20
3.4 Water circulation pumps ............................................
p.21
3.5 Antifreeze function .......................................................
p.21
3.6 Antifreeze liquid ............................................................
p.21
3.7 System water quality ...................................................
p.22
3.8 System lling ..................................................................
p.22
3.9 Fuel gas supply ..............................................................
p.22
3.10 Combustion products exhaust ................................
p.23
3.11 Flue gas condensate discharge ................................
p.26
3.12 Safety valve exhaust (indoor version) ....................
p.26
4 Electrical installer ..............................................................
p.27
4.1 Warnings ..........................................................................
p.27
4.2 Electrical systems ..........................................................
p.27
4.3 Electrical power supply ...............................................
p.28
4.4 Set-up and control ........................................................
p.28
4.5 Water circulation pumps ............................................
p.31
5 First start-up ..........................................................................
p.34
5.1 Preliminary checks ........................................................
p.34
5.2 Electronic adjustment on the machine – Menus
and parameters of the S61 board ...........................
p.34
5.3 Modifying settings ........................................................
p.35
6 Normal operation ..............................................................
p.36
6.1 Warnings ..........................................................................
p.36
6.2 Switch on and o ..........................................................
p.36
6.3 Modifying settings ........................................................
p.36
6.4 Eciency ..........................................................................
p.36
7 Maintenance ..........................................................................
p.36
7.1 Warnings ..........................................................................
p.36
7.2 Pre-emptive maintenance .........................................
p.37
7.3 Scheduled routine maintenance .............................
p.37
7.4 Messages on the display ............................................
p.37
7.5 Restarting a locked-down unit.................................
p.37
7.6 Periods of inactivity ......................................................
p.38
8 Diagnostics ..............................................................................
p.38
8.1 Operative codes.............................................................
p.38
9 Appendices..............................................................................
p.42
9.1 Product che...................................................................
p.42
Introduction
4
I
I INTRODUCTION
Manual
This Manual is an integral part of the GAHP GS/WS units
and must be handed to the end user together with the
appliance.
RECIPIENTS
This Manual is intended for:
End user, for appropriate and safe use of the appliance.
Qualied installer, for correct appliance installation.
Planner, for specic information on the appliance.
CONTROL DEVICE
In order to be able to work, the GAHP GS/WS unit needs a con-
trol device (DDC, CCP/CCI or external requests), which must be
connected by the installer.
II SYMBOLS AND DEFINITIONS
II.1 KEY TO SYMBOLS
DANGER
WARNING
NOTE
PROCEDURE
REFERENCE (to other document)
II.2 TERMS AND DEFINITIONS
GAHP Appliance/Unit = equivalent terms, both used to des-
ignate the gas powered absorption heat pump GAHP (Gas
Absorption Heat Pump).
TAC = Technical Assistance Centre authorised by Robur.
External request = generic control device (e.g. thermostat,
clock or any other system) equipped with a voltage-free NO con-
tact and used as control to start/stop the GAHP unit.
CCI Controller (Comfort Controller Interface) = optional Robur
control device which lets you manage up to three modulating
heat only GAHP units (A, WS, GS).
CCP Controller (Comfort Control Panel) = Robur control de-
vice which lets you manage in modulation mode up to three
GAHP units and all system components (probes, diverter/mixing
valves, circulating pumps), including any integration boiler.
DDC Control (Direct Digital Controller) = optional Robur adjust-
ment device to control one or more Robur appliances (GAHP
heat pumps, GA chillers and AY00-120 boilers) in ON/OFF mode.
RB100/RB200 Devices (Robur Box) = optional interface devices
complementary to DDC, which may be used to broaden its func-
tions (heating/cooling/DHW production service demands, and
control of system components such as third party generators,
adjustment valves, circulators, probes).
Heat generator = equipment (e.g. boiler, heat pump, etc..) pro-
ducing heating and/or DHW.
GUE (Gas Utilization Eciency) = eciency index of gas heat
pumps, equal to the ratio between the thermal energy pro-
duced and the energy of the fuel used (relative to LCV, lower
caloric value).
First start-up = appliance commissioning operation which may
only and exclusively be carried out by a TAC.
S61/Mod10/W10 Boards = electronic boards on the GAHP unit,
to control all functions and to provide interface with other devic-
es and with the user.
III WARNINGS
III.1 GENERAL AND SAFETY WARNINGS
Installer's qualications
Installation must exclusively be performed by a qualied
rm and by qualied personnel, with specic knowledge
on heating, cooling, electrical systems and gas applianc-
es, in compliance with the laws in force in the Country of
installation.
Declaration of conformity
Upon completing installation, the installing rm shall
issue to the owner/client the appliance's workmanlike
conformity declaration, according to national/local reg-
ulations in force and the manufacturer's instructions/
provisions.
Misuse
The appliance must only be used for the purposes for
which it has been designed. Any other use is deemed
hazardous. Incorrect use may aect operation, duration
and safety of the appliance. Adhere to the manufactur-
er's instructions.
Hazardous situations
Do not start the appliance in hazardous conditions, such
as: gas smell, problems with the plumbing/electrical/gas
system, parts of the appliance under water or damaged,
malfunctioning, disabling or bypassing control and safe-
ty devices.
In case of danger, request intervention by qualied per-
sonnel.
In case of danger, switch o the electrical power and gas
supplies only if this can be done in total safety.
Warnings
Installation, use and maintenance manual – GAHP GS/WS
5
III
Do not entrust children, persons with physical, sensory
or mental disabilities or persons with poor knowledge
and experience with use of the appliance.
Gas component tightness
Before performing any operation on gas ducting compo-
nents, close the gas valve.
Upon completing any procedure, perform the tightness
test according to regulations in force.
Gas smell
If you smell gas:
Do not use electrical devices such as telephones, mul-
timeters or other equipment that may cause sparks next
to the appliance.
Shut o the gas supply by turning the valve o.
Disconnect electrical power supply by means of the
external isolation switch in the power supply electrical
panel.
Use a telephone away from the appliance to ask for inter-
vention from qualied personnel.
Poisoning
Ensure the ue gas ducts are tightness and compliant
with the regulations in force.
Upon completing any procedure, ensure components
are tightness.
Moving parts
The appliance contains moving parts.
Do not remove guards during operation, and in any case
prior to disconnecting the power supply.
Burn hazard
The appliance contains very hot parts.
Do not open the appliance and do not touch internal
components before the appliance has cooled down.
Do not touch the ue gas exhaust before it has cooled
down.
Pressure vessels
The appliance has a sealed circuit classied as pres-
sure vessel, the tightness of which is tested by the
manufacturer.
Do not carry out any intervention on the sealed circuit or
on the appliance's valves.
Water-ammonia solution
The GAHP/GA unit uses the ammonia-water absorption
cycle. The water-ammonia solution is contained in the
sealed circuit. The solution is harmful for health if it is in-
gested, inhaled or comes in contact with the skin.
In the event of coolant leak keep away and disconnect
the power and gas supply (only if it is possible to do so
with no danger).
Ask for TAC intervention.
Electrocution hazard
Disconnect the electrical power supply before any oper-
ation on appliance components.
For electrical connections exclusively use compliant
components and according to the specications provid-
ed by the manufacturer.
Ensure the appliance cannot be accidentally switched
back on.
Earthing
Electrical safety depends on eective earthing system,
correctly connected to the appliance and installed ac-
cording to the regulations in force.
Distance from combustible or ammable materials
Do not deposit ammable materials (paper, diluents,
paints, etc.) near the appliance.
Limescale and corrosion
Depending on the chemical/physical properties of the
system water, limescale or corrosion may damage the
appliance (Paragraph 3.7
p.22
).
Check system sealing.
Avoid frequent top-ups.
Chloride concentration
The concentration of chlorides or free chlorine in the
system water must not exceed the values in Table
3.2
p.22
.
Aggressive substances in the air
Halogenated hydrocarbons containing chlorine and u-
orine compounds cause corrosion. The air of the installa-
tion site must be free from aggressive substances.
Acid ue gas condensate
Discharge the acid condensate of combustion ue gas,
as indicated in Paragraph 3.11
p. 26
, in compliance
with current exhaust regulations.
Switching the appliance o
Disconnecting the power supply while the appliance
is running may cause permanent damage to internal
components.
Except in the case of danger, do not disconnect the pow-
er supply to switch o the appliance, but always and ex-
clusively act through the provided control device (DDC,
CCP/CCI or external request).
In the event of failure
Operations on internal components and repairs may
exclusively be carried out by a TAC, using only original
parts.
In the event of failure of the appliance and/or breakage
of any component, do not attempt to repair and/or re-
store and immediately contact the TAC.
Routine maintenance
Proper maintenance assures the eciency and good op-
eration of the appliance over time.
Maintenance must be performed according to the
Warnings
6
III
manufacturer's instructions (see Chapter 7
p. 36
) and
in compliance with current regulations.
Appliance maintenance and repairs may only be entrust-
ed to rms legally authorised to work on gas appliances
and systems.
Enter into a maintenance contract with an authorised
specialised rm for routine maintenance and for servic-
ing in case of need.
Use only original parts.
Decommissioning and disposal
If the appliance is to be disposed of, contact the manu-
facturer for its disposal.
Keep the Manual
This Installation, use and maintenance manual must al-
ways accompany the appliance and must be handed to
the new owner or installer in the event of sale or removal.
III.2 CONFORMITY
EU Directives and standards
The absorption heat pumps of the GAHP series are certied as
conforming to standard EN 12309 and comply with the essential
requirements of the following Directives:
2016/426/EU "Gas Appliances Regulation" as amended and
added.
2014/30/EC "Electromagnetic Compatibility Directive" as
amended and added.
2014/35/EC "Low Voltage Directive" as amended and added.
2006/42/EC "Machine Directive" as amended and added.
2014/68/EU "Pressure Equipment Directive" as amended
and added.
811/2013/EU "Energy-Related Products regulation" as
amended and added.
813/2013/EU "Ecodesign requirements regulation" as
amended and added.
Furthermore, they comply with the requirements of the follow-
ing standards:
EN 677 Specic requirements for condensing boilers with
nominal heat input up to 70 kW.
EN 378 Refrigerating systems and heat pumps.
Other applicable provisions and standards
The design, installation, operation and maintenance of the sys-
tems shall be carried out in compliance with current applicable
regulations, depending on the Country and location, and in ac-
cordance with the manufacturer's instructions. In particular, reg-
ulations regarding the following shall be complied with:
Gas systems and equipment.
Electrical systems and equipment.
Heating and air conditioning systems, and heat pumps.
Environmental protection and combustion products ex-
haust.
Fire safety and prevention.
Any other applicable law, standard and regulation.
III.3 EXCLUSIONS OF LIABILITY AND
WARRANTY
Any contractual or extra-contractual liability of the man-
ufacturer for any damage caused by incorrect installation
and/or improper use and/or failure to comply with reg-
ulations and with the manufacturer's directions/instruc-
tions shall be disclaimed.
In particular, the warranty on the appliance may be ren-
dered void by the following conditions:
Incorrect installation.
Misuse.
Failure to comply with the manufacturer's indications on
installation, use and maintenance.
Alteration or modication of the product or any part
thereof.
Extreme operational conditions or however outside of
the operational ranges set forth by the manufacturer.
Damages caused by external agents such as salts, chlo-
rine, sulphur or other chemical substances contained in
the installation water or present in the air of the instal-
lation site.
Abnormal actions transmitted to the appliance by the
plant or installation (mechanical stresses, pressure, vi-
brations, thermal expansion, electrical surges...).
Accidental damages or due to force majeure.
Features and technical data
Installation, use and maintenance manual – GAHP GS/WS
7
1
1 FEATURES AND TECHNICAL DATA
1.1 FEATURES
Operation
Based on the thermodynamic water-ammonia absorption cycle
(H
2
0–NH
3
), the appliance simultaneously produces hot water
and chilled water, using the ground or well/ground/surface wa-
ter as a renewable energy source (cold source) and natural gas
(or LPG) as primary energy.
The thermodynamic cycle takes place within a hermetically
sealed circuit, in welded construction, perfectly tight, facto-
ry-tested, which does not require any maintenance or coolant
top-ups.
Mechanical and thermo-hydraulic components
Steel sealed circuit, externally treated with epoxy paint.
Sealed combustion chamber (type C).
Metal mesh radiant burner, equipped with ignition elec-
trodes and ame detection, managed by an electronic ame
control box.
Titanium stainless steel shell-and-tube water exchanger
(condenser), externally insulated.
Titanium stainless steel shell-and-tube water exchanger
(evaporator), externally insulated.
Stainless steel, shell-and-tube recovery exchanger of ue gas
latent heat.
Control and safety devices
S61 electronic board with microprocessor, LCD display and
knob.
Mod10 additional electronic board (integrated in S61).
Auxiliary W10 electronic board.
Installation water ow meter (hot side).
Installation water ow switch (cold side).
Generator limit thermostat, with manual reset.
Flue gas thermostat, with manual reset.
Generator ns temperature probe.
Sealed circuit safety relief valve.
Bypass valve, between high and low-pressure circuits.
Ionization ame control box.
Double shutter electric gas valve.
Antifreeze functions for hydraulic circuit.
Condensate discharge sensor.
Outdoor and indoor versions
The GAHP GS/WS units are available in two versions, indoor or
outdoor, according to the installation site.
Features and technical data
8
1
1.2 DIMENSIONS
Figure1.1 Indoor GAHP GS/WS dimensions
A Flue gas output Ø 80
B Combustion air inlet Ø 80
C Fumes thermostat manual reset
D Power supply cables input
E Ventilation fan
F Burner on warning light
G Gas connection Ø 3/4"
H Hot water inlet Ø 1"¼
L Renewable source water return Ø 1"¼
M Renewable source water delivery Ø 1"¼
N Hot water delivery Ø 1"¼
Q Safety valve outlet ducting Ø 1"¼
Features and technical data
Installation, use and maintenance manual – GAHP GS/WS
9
1
Figure1.2 Outdoor GAHP GS/WS dimensional drawing
A Flue gas output Ø 80
B Combustion air inlet Ø 80
C Fumes thermostat manual reset
D Power supply cables input
E Ventilation fan
F Appliance operation warning light
G Gas connection Ø 3/4"
H Hot water inlet Ø 1"¼
L Renewable source water return Ø 1"¼
M Renewable source water delivery Ø 1"¼
N Hot water delivery Ø 1"¼
P Condensate drain
Features and technical data
10
1
1.3 COMPONENTS
Figure1.3 Internal components - front view
1 Ventilation fan
2 Gas valve
3 Combustion blower
4 Tmix air-gas mixture temperature probe
5 Electrical panel
6 Oil pump
7 Flow meter (hot side)
Features and technical data
Installation, use and maintenance manual – GAHP GS/WS
11
1
Figure1.4 Internal components - left side view
1 Manual air vent (cold side)
2 Flow switch (cold side)
3 Manual reset of the ue exhaust thermostat
4 Ø 80 ue gas exhaust
5 Sensing element of the ue exhaust thermostat
6 Generator ns temperature probe
7 Condensate drain sensor
8 Flame sensor / ignition electrodes
9 Condensate drain siphon
10 Manual air vent valve (hot side)
1
3
4
2
5
6
7
8
9
10
Features and technical data
12
1
Figure1.5 Internal components - right side view
1 Safety valve
2 TG generator temperature probe
3 Limit thermostat
4 Ignition transformer
5 Flow temperature probe (hot side)
Features and technical data
Installation, use and maintenance manual – GAHP GS/WS
13
1
1.4 ELECTRICAL WIRING DIAGRAM
Figure1.6 Appliance wiring diagram
SCH1 Controller S61
SCH2 W10 circuit board
SCH3 Mod10 circuit board
TER Power supply terminal block
CNTBOX Flame controller
PWRTR Board transformer
BLW Blower
PMP Oil pump
IGNTR Ignition transformer
IGN Ignition electrodes
FLS Flame sensor
LS Gas valve ON indicator lamp
GV Gas solenoid valve
THMF Cold water delivery temperature sensor
THRF Cold water return temperature sensor
TMIX Combustion air temperature sensor
TA Ambient air temperature sensor
TG Generator temperature sensor
THMC Hot water ow temperature probe
THRC Hot water return temperature probe
REED Oil pump rotation sensor
TF Fumes temperature sensor or generator n
sensor
TC Manual ue gas thermostat
TL Generator limit thermostat
FM Hot side owmeter
FL Renewable source water ow switch
CWS Condensate water sensor
MA Terminal block
1.5 ELECTRONIC BOARDS
Electronic boards (S61+Mod10)
The unit's electrical board contains:
Electronic board S61 (Figure 1.7
p. 14
), with
microprocessor, it controls the appliance and displays data,
messages and operative codes. The appliance is monitored
and programmed by interacting with the display and the
knob.
Auxiliary Mod10 Electronic Board (Figure 1.8
p. 15
),
overlapping S61, controls power modulation of the burner
Features and technical data
14
1
and water circulation pump rate variation.
Satellite W10 electronic board (Figure 1.9
p. 15
),
interconnected to the S61 board and located next to it, used
mainly to control hot side circulating pump.
Figure1.7 Electronic board S61
SCH1 Controller S61
SCH3 Mod10 electronic board (see specic gure
for further details)
A1, A2 Auxiliary inputs
ENC Knob
F1 T 2A fuse
F2 T 10A fuse
F3 T 2A fuse
F4 T 3,15A fuse
FAN (BK, WH, BR) Cooling fan output
FL Flow switch input
FS5 (24V AC) board supply 24-0-24 Vac
IGN.BOX (L, N) Flame controller power supply
230 Vac
J1 CAN bus Jumper
J10 Jumper N.O. contact
J82 W10 board connector (on Mod10)
JP10 6-pole ame controller connector
JP12 Flue gas probe or generator n probe input
JTAG S61 board programming connector
MAIN 230V (L, N) S61 board supply input 230 Vac
N.O. CONTACT Normally open pump contact
P7 (R, W, Y, O) Enable input
P8 (GND, L, H) CAN bus connector
PUMP 230V (L, N) Oil pump supply output
SPI Communication port with Mod10
controller
SRT1 Oil pump rotation sensor input
SRT2 Hot water owmeter input
TA Ambient air temperature probe input
TA1 Hot water ow temperature probe input
TA2 Hot water inlet temperature probe input
TCN Combustion air temperature probe input
TF Flue gas thermostat input
TG Generator temperature probe input
THMF Cold water inlet temperature probe input
THRF Cold water inlet temperature probe input
TL Generator limit thermostat input
Features and technical data
Installation, use and maintenance manual – GAHP GS/WS
15
1
Figure1.8 Mod10 controller
HFLOW Not used
CFLOW Condensation water sensor control
J51 S61 connector
HPMP Primary circuit hot water pump control
output (0-10 V) [A/GS/WS]
CPMP Cold side water pump control output
[GS/WS]
NC1-C1 Status indication of locking warnig/error
CN5 Blower control
J82 W10 auxiliary controller connector
J83 W10 cable shielding connection
CN1 Inputs 0-10V (not used)
1235 4
Figure1.9 W10 electronic controller
JP1 Communication with S61/Mod10
1.6 OPERATION MODE
ON/OFF or modulating operation
The GAHP unit may work in two modes:
Mode (1) ON/OFF, i.e. on (at full power) or o, with circulat-
ing pumps at constant ow.
Mode (2) MODULATING, i.e. at variable load from 50% to
100% of power, with circulating pumps at variable ow (hot
side) and constant ow (cold side).
For each mode, (1) or (2), specic control systems and devices
are provided (Paragraph 1.7
p.15
).
1.7 CONTROLS
Control device
The appliance may only work if it is connected to a control de-
vice, selected from:
(1) DDC control
(2) CCP/CCI control
(3) external request
1.7.1 Control system (1) with DDC (GAHP unit ON/
OFF)
The DDC controller is able to control appliances, a single GAHP
unit, or even several Robur GAHP/GA/AY units in cascade, only
in ON/OFF mode (non modulating). For more details refer to the
DDC, RB100, RB200 Manuals and the Design Manual.
DDC Controller
The main functions are:
Setup and control of one (or more) Robur units of the
Features and technical data
16
1
absorption line (GAHP, GA, AY).
Data display and parameters setting.
Hourly programming.
Climatic curve control.
Diagnostics.
Errors reset.
Possibility to interface with a BMS.
DDC functionality may be extended with auxiliary Robur devices
RB100 and RB200 (e.g. service requests, DHW production, Third
Party generator control, probe control, system valves or circulat-
ing pumps, ...).
1.7.2 Control system (2) with CCP/CCI (modulating
GAHP unit)
The CCP/CCI control is able to control in heating only (and pos-
sibly passive cooling) up to 3 GAHP units in modulating mode
(therefore A/WS/GS only, excluding AR/ACF/AY), plus any inte-
gration ON/OFF boiler. For additional details and diagrams refer
to the CCP/CCI Manual and the Planning Manual.
CCP/CCI Control
See CCP/CCI device Manual.
1.7.3 Adjustment system (3) with external request
(GAHP unit ON/OFF)
The appliance may also be controlled via generic request de-
vices (e.g. thermostat, timer, button, contactor...) tted with
voltage-free NO contact. This system only provides elementary
control (on/o, with xed setpoint temperature), hence without
the important functions of systems (1) and (2). It is advisable to
possibly limit its use to simple applications only and with a sin-
gle appliance.There are two control options: heating request or
cooling request.
For connection of the selected device to the appliance's
electronic board please refer to Paragraph 4.4
p.28
.
1.8 TECHNICAL CHARACTERISTICS
Table1.1 GAHP GS/WS technical data
GAHP GS HT GAHP WS
Heating mode
Seasonal space heating energy eciency class
(ErP)
medium-temperature application (55 °C) - A++
low-temperature application (35 °C) - A+
Heat output
Evaporator inlet temperature/Delivery
temperature
B0W35 kW 41,6 -
B0W50 kW 37,6 -
B0W65 kW 31,4 -
W10W35 kW - 43,9
W10W50 kW - 41,6
W10W65 kW - 35,8
GUE eciency
Evaporator inlet temperature/Delivery
temperature
B0W35 % 165 -
B0W50 % 149 -
B0W65 % 125 -
W10W35 % - 174
W10W50 % - 165
W10W65 % - 142
Heat input
nominal (1013 mbar - 15 °C) (1) kW 25,7
real kW 25,2
Hot water delivery temperature
maximum for heating °C 65
maximum for DHW °C 70
Hot water return temperature
maximum for heating °C 55
maximum for DHW °C 60
minimum temperature in continuous operation °C 30 (2)
Thermal dierential nominal °C 10
Heating water ow
nominal l/h 3170 3570
maximum l/h 4000
minimum l/h 1400
Pressure drop heating mode
for nominal water ow (B0W50) bar 0,49 (3) -
for nominal water ow rate(W10W50) bar - 0,57 (3)
Ambient air temperature (dry bulb)
maximum °C 45
minimum °C 0 (4)
Renewable source operating conditions
(1) Relative to NCV (net caloric value).
(2) In transient operation, lower temperatures are allowed.
(3) For ows other than nominal see Design Manual, Pressure losses Paragraph.
(4) Data referred to the indoor version. For the outdoor version, the minimum ambient air temperature is -15 °C. A special outdoor version is available as an option for operation down to -30 °C.
(5) ±10% depending on power voltage and absorption tolerance of electric motors.
(6) PCI (G20) 34,02 MJ/m³ (15 °C - 1013 mbar).
(7) PCI (G30/G31) 46,34 MJ/kg (15 °C - 1013 mbar).
(8) Sound power values detected in compliance with the intensity measurement methodology set forth by standard EN ISO 9614; C type installation.
(9) Maximum sound pressure levels in free eld, with directionality factor 2, obtained from the sound power level in compliance with standard EN ISO 9614; C type installation.
(10) Indoor variant only.
(11) Overall dimensions excluding fumes pipes.
Features and technical data
Installation, use and maintenance manual – GAHP GS/WS
17
1
GAHP GS HT GAHP WS
Power recovered from renewable source
Evaporator inlet temperature/Delivery
temperature
B0W35 kW 16,4 -
B0W50 kW 12,1 -
B0W65 kW 7,0 -
W10W35 kW - 18,7
W10W50 kW - 16,6
W10W65 kW - 10,6
Renewable source water return temperature maximum °C 45
Renewable source delivery water temperature minimum °C -5 3
Renewable source water ow rate (with 25%
glycol)
nominal (B0W50) l/h 3020 -
maximum l/h 4000 -
minimum l/h 2000 -
Renewable source water ow rate
nominal (W10W50) l/h - 2850
maximum l/h - 4700
minimum l/h - 2300
Renewable source pressure drop at nominal water ow bar 0,51 (3) 0,38 (3)
Electrical specications
Power supply
voltage V 230
type - SINGLE PHASE
frequency Hz 50
Electrical power absorption nominal kW 0,41 (5)
Degree of protection IP - X5D
Installation data
Gas consumption
G20 natural gas (nominal) m³/h 2,72 (6)
G20 natural gas (min) m³/h 1,34
G25 (nominal) m³/h 3,16
G25 (min) m³/h 1,57
G30 (nominal) kg/h 2,03 (7)
G30 (min) kg/h 0,99
G31 (nominal) kg/h 2,00 (7)
G31 (min) kg/h 0,98
NO
x
emission class - 5
NO
x
emission ppm 25,0
CO emission ppm 36,0
sound power L
w
(max) dB(A) 66,1 (8)
sound pressure L
p
at 5 metres (max) dB(A) 44,1 (9)
minimum storage temperature °C -30
maximum water pressure in operation bar 4,0
maximum ow ue condensate l/h 4,0
Water content inside the apparatus
hot side l 4
cold side l 3
Water tting
type - F
thread 1 1/4
Gas connection
type - F
thread 3/4
safety valve outlet channel tting 1 1/4 (10)
Flue gas exhaust
diameter (Ø) mm 80
residual head Pa 80
product conguration C63
type of installation - C13, C33, C43, C53, C63, C83, B23P, B33
Dimensions
width mm 848 (11)
depth mm 690
height mm 1278
Weight in operation kg 300
General information
Cooling uid
ammonia R717 kg 7,0 7,2
water H
2
O kg 10,0 9,6
maximum pressure of the cooling circuit bar 32
(1) Relative to NCV (net caloric value).
(2) In transient operation, lower temperatures are allowed.
(3) For ows other than nominal see Design Manual, Pressure losses Paragraph.
(4) Data referred to the indoor version. For the outdoor version, the minimum ambient air temperature is -15 °C. A special outdoor version is available as an option for operation down to -30 °C.
(5) ±10% depending on power voltage and absorption tolerance of electric motors.
(6) PCI (G20) 34,02 MJ/m³ (15 °C - 1013 mbar).
(7) PCI (G30/G31) 46,34 MJ/kg (15 °C - 1013 mbar).
(8) Sound power values detected in compliance with the intensity measurement methodology set forth by standard EN ISO 9614; C type installation.
(9) Maximum sound pressure levels in free eld, with directionality factor 2, obtained from the sound power level in compliance with standard EN ISO 9614; C type installation.
(10) Indoor variant only.
(11) Overall dimensions excluding fumes pipes.
Transport and positioning
18
2
Table1.2 PED data
GAHP GS HT GAHP WS
PED data
Components under pression
generator l 18,6
leveling chamber l 11,5
evaporator l 3,7
cooling volume transformer l 4,5
absorber/condenser l 3,7
cooling absorber solution l 6,3
solution pump l 3,3
test pressure (in air) bar g 55
maximum pressure of the cooling circuit bar g 32
lling ratio kg of NH
3
/l 0,146 0,150
uid group - group 1°
2 TRANSPORT AND POSITIONING
2.1 WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage dur-
ing appliance transport and installation.
On-site inspection
Upon arrival at the site, ensure there is no transport dam-
age on packing or metal panels.
After removing the packing materials, ensure the appli-
ance is intact and complete.
Packing
Only remove the packing after placing the appliance on
site.
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are po-
tentially dangerous.
Weight
The crane and lifting equipment must be suitable for the
load.
Do not stand under suspended loads.
2.2 HANDLING
Handling and lifting
Always handle the appliance in its packing, as delivered by
the factory.
To lift the appliance use straps or slings inserted in the holes
of the base (Figure 2.1
p.18
).
Use lifting beams to avoid damaging the outer panels and
nned coil (Figure 2.1
p.18
).
Comply with safety regulations at the installation site.
Figure2.1 Instruction for lifting
In the event of handling with forklift or pallet truck,
comply with the handling instructions shown on the
packing.
2.3 APPLIANCE POSITION OUTDOOR
VERSION
Do not install the outdoor version inside a room, not
even if it has openings. In no event the outdoor version
may be started inside a room.
Where to install the appliance
In the outdoor version the appliance:
May be only installed outside buildings, out of the dripping
line of rain gutters or the like. It does not require protection
from weathering.
The appliance may be installed at ground level, on a terrace
or on a roof, compatibly with its dimensions and weight.
The appliance's ue gas exhaust must not be immediately
close to openings or air intakes of buildings, and must com-
ply with environmental regulations.
Do not install near the exhaust of ues, chimneys or hot
polluted air. In order to work correctly, the appliance needs
clean air.
Heating engineer
Installation, use and maintenance manual – GAHP GS/WS
19
3
Acoustic issues
Pre-emptively assess the appliance's sound eect in connec-
tion to the site, taking into account that building corners, en-
closed courtyards, restricted spaces may amplify the acous-
tic impact due to the reverberation phenomenon.
2.4 INSTALLATION PREMISES INDOOR
VARIANT
The installation premises must meet all the requirements set
forth by laws, standards and regulations of the Country and place
of installation regarding gas appliances and cooling appliances
Do not install inside a room that has no aeration open-
ings.
Features of the installation premises
The premises must be provided with permanent and su-
ciently wide ventilation openings to permit even air ow for
aeration and possibly for combustion (if type B installation).
Combustion air intake may be ducted from the outside (type
C installation).
The ue gas exhaust must be ducted to the outside. The ue
opening must not be immediately close to openings or air
intakes of buildings, and must comply with environmental
regulations.
2.5 MINIMUM CLEARANCE DISTANCES
For both the indoor and outdoor version:
Distances from combustible or ammable materials
Keep the appliance away from combustible or ammable
materials or components, in compliance with applicable
regulations.
Clearances around the appliance
The minimum clearance distances shown in Figure 2.2
p. 19
(bar any stricter regulations) are required for safety, operation
and maintenance.
Figure2.2 Clearances
2.6 MOUNTING BASE
Base or oor construction features
Place the appliance on a levelled at surface made of re-
proof material and able to withstand its weight.
For the outdoor version:
(1) - installation at ground level
Failing a horizontal supporting base, make a at and levelled
concrete base, at least 100-150 mm larger than the appli-
ance size per side.
(2) - installation on terrace or roof
The structure of the building must support the total weight
of the appliance and the supporting base.
If necessary, provide a maintenance walkway around the ap-
pliance.
Anti vibration mountings
Although the appliance's vibrations are minimal, resonance
phenomena might occur in roof or terrace installations.
Use anti-vibration mountings.
Also provide anti-vibration joints between the appliance
and water and gas pipes.
3 HEATING ENGINEER
3.1 WARNINGS
General warnings
Read the warnings in Chapter III
p. 4
, providing im-
portant information on regulations and on safety.
Compliance with installation standards
Installation must comply with applicable regulations in
force, based on the installation Country and site, in mat-
ters of safety, design, implementation and maintenance
of:
heating systems
cooling systems
gas systems
ue gas exhaust
ue gas condensate discharge
Installation must also comply with the manufacturer's
provisions.
3.2 HYDRAULIC SYSTEM
Primary and secondary circuit
In many cases it is advisable to divide the water installation
(hot side) into two parts, primary and secondary circuit, un-
coupled by a hydraulic separator, or possibly by a tank that
also acts as inertial volume/thermal inertia.
Heating engineer
20
3
Constant ot variable water ow
The GAHP unit is able to operate with constant water ow rate
(always on the cold side) or variable (on hot side only), according
to ON/OFF or modulating operative mode.
System and components must be designed and installed
consistently.
Minimum water content
High thermal inertia is conducive to ecient appliance opera-
tion. Very short ON/OFF cycles are to be avoided.
If necessary, provide for an inertial volume (on hot side), to
be suitably sized (see planning manual).
Heating and/or cooling
It may be required to alternatively or simultaneously produce
hot water and/or chilled water. The selection of the type of op-
eration may be performed by the control device, by suitably se-
lecting the priority (cooling or heating).
3.3 HYDRAULIC CONNECTIONS
Plumbing ttings
on the rear panel (Figures 1.1
p.8
and 1.2
p.9
).
N (= out) 1"1/4 F -WATER OUTPUT (hot) (m = ow to the in-
stallation);
H (= in) 1"1/4 F- WATER INPUT (hot) (r = inlet from the in-
stallation).
M (= out) 1"1/4 F - WATER OUTPUT (cold) (m = ow to the
installation);
L (= in) 1"1/4 F - WATER INPUT (cold) (r = inlet from the
installation).
Hydraulic pipes, materials and features
Use pipes for heating/cooling installations, protected from
weathering, insulated for thermal losses, with vapour barrier
to prevent condensation.
Pipe cleaning
Before connecting the appliance,accurately wash the
water and gas piping and any other system component,
removing any residue.
Minimum components of primary water circuits
Always provide, near the appliance, both on the hot side and
cold side:
on water piping, both output and input (m/r)
2 antivibration joints on water ttings
2 pressure gauges
2 isolation ball valves
on the input water piping (r)
1 separator lter
1 ow regulation valve, if the circulation pump is with
constant ow
1 water circulation pump, towards the appliance
on the output water piping (m) (hot side only)
1 safety valve (3 bar)
1 expansion tank of the individual unit
For GAHP GS/WS with open circuit the EXCHANGER is
obligatory.
Figure3.1 GAHP GS Water diagram
The ow regulator valve must only be used when the
primary circuit circulation pump is constant
ow type
A Gas connection
1 Anti-vibration connection
2 Pressure gauge
3 Flow regulator valve
4 Water lter
5 Shut-o valves
6 Hot side circulation pump (primary circuit)
7 Cold side circulation pump (primary circuit)
8 Safety valve (3 bar)
9 Expansion tank
10 Hydraulic separator/4-pipe buer tank
11 Hot side circulation pump (secondary circuit)
12 Geothermal eld probes
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Robur GAHP WS Installation, Use And Maintenance Manual