nVent.com | 9
3.2 ELECTRICAL SIZING AND RUN LENGTH
Tables 2 and 3 show the maximum bundle length that may be powered from different sized
circuit breakers. Use Table 2 for European type circuit breakers. Use Table 3 for North American
circuit breakers. Note that ground-fault equipment protection (residual current device) is required
on each heating cable branch circuit. To reduce the risk of fire caused by damage or improper
installation, circuit breakers with a 30-mA trip level must be used. Alternative designs providing
comparable levels of ground-fault protection may also be acceptable. Contact your nVent
representative for assistance if you need to size circuit breakers for use under different start-up
conditions. For maximum protection, use the smallest circuit breaker consistent with the length of
heating cable installed.
Table 2: Maximum Circuit Length vs. Circuit Breaker Rating: 120 Vac
Start-up temp. 15 A20 A30 A 40
0 A
°C °F mftmft mftmft
t
10 50 55 180 73 240110 360117 385117 3855XTV1-CT-T3
–18049 16064210 98 320117 385117 385
–29–20 46 15061 200 93 305117 385117 385
–40–40 44 14559 195 88 290117 385117 385
10XTV1-CT-T3 10 50 34 110 44 145 67 22082270 82 270
–18029 95 40 13059195 79 26082270
–29–20 29 95 38 12558190 76 25082270
–40–40 27 90 37 12055180 73 24082270
15XTV1-CT-T2 10 50 23 75 30 10046150 61 20067220
–18020 65 27 90 41 13555180 67 220
–29–20 20 65 26 85 40 13052170 66 215
–40–40 18 60 24 80 38 12550165 62 205
20XTV1-CT-T2 10 50 15 502637 12049160 58 190
–18015 50 21 70 32 10543140 55 180
–29–20 15 50 20 65 32 10543140 52 170
–40–40 15 50 20 65 30 10040130 50 165
5BTV1-CT 10 50 70 23082 270 82 27082270 **
–18043 14058190 82 27082270 **
–29–20 38 12550 165 76 25082270
–40–40 34 11044 145 67 22082270
8BTV1-CT 10 50 46 15061 200 64 21064210 **
–18030 10040130 61 20064210 **
–29–20 26 85 35 11553175 64 210* *
–40–40 24 80 32 10547155 64 210* *
10BTV1-CT105037120 49 16055180 55 180* *
–18024 80 34 11049160 55 180* *
–29–20 21 70 29 95 43 14055180
–40–40 20 65 26 85 38 12552170
Heating Cable
* For these design conditions, use a smaller circuit breaker or alternate heating cable.